SECTION 2 - FIELD CONTROL MODIFICATIONS 

FORM 160.79-PW2 

ISSUE DATE: 01/31/2019

2

FIGURE 20 - 

REMOTE LEAVING CHILLED LIQUID 

TEMPERATURE SETPOINT WITH PWM SIGNAL

LD06833

The relay contacts should close for 1 to 11 seconds at 

least once every 30 minutes to maintain the setpoint 

to the desired value. If a 1 to 11 second closure is not 

received within 30 minutes of the last closure, the 

setpoint is defaulted to the Local setpoint value. A clo-

sure is only accepted at rates not to exceed once every 

70 seconds. This input will only be accepted in 

Digital 

Remote Mode

. Calculate the setpoint for various pulse 

widths as follows:

OFFSET(°F) =  (PULSE WIDTH IN SECONDS)  

(REMOTE RESET TEMP. RANGE) 
  10

SETPOINT(°F) = LOCAL SE OFFSET

For example, if the relay contacts close for 5 sec-

onds and the Remote Reset Temp Range setpoint is  

programmed for 10°F, and the Local Leaving Chilled 

Liquid Temperature setpoint is programmed for 40°F, 

the setpoint would be set to 44°F as follows:

OFFSET (°F)  = (5 – 1)(10) 

 10 

= (4)(10) 

     10 

= 40 

  10 

= 4°F 

SETPOINT (°F)  = 40 + 4 

= 44°F

EXTERNAL SIGNAL FOR REFRIGERATION 

UNIT FAILURE

When the Safety Shutdown Contacts (see 

Figure 3 on 

page 9

) are not connected to an Energy Manage-

ment System they may be employed to energize a local 

or remote safety alarm (by others). When the normally 

open Safety Shutdown Contacts close, the alarm will 

indicate shutdown of the unit. The cause of shutdown 

will be one or more of the safety conditions listed 

in 

Unit Operations Manual (Forms 160.69‑O1 and 

160.69‑O3).

FIGURE 21 - 

EXTERNAL SIGNAL FOR 

REFRIGERATION UNIT FAILURE (NOTE 6)

LD06834

CONFIGURED FOR MANUAL RESTART 

AFTER POWER FAILURE

If the unit was shut down because of 

Cycling Shutdown Contacts (see Fig‑

ure 7 page 10) the alarm will not be 

energized, but the unit will have been 

shut down. A closure of the safety alarm 

contacts means that an operator must 

manually reset and restart the unit.

When the Safety Shutdown contacts close, the 

 

OptiView Control Center will display the follow-

ing message: SAFETY SHUTDOWN – MANUAL  

RESTART, and cause of shutdown.

FIGURE 22 - 

AUXILIARY SAFETY SHUTDOWN 

INPUT

LD04399

Содержание YD

Страница 1: ...DATE ________ APPROVAL DATE ________ CONSTRUCTION DATE _______ Supersedes 160 79 PW2 616 Form 160 79 PW2 119 FIELD CONTROL MODIFICATIONS FOR YD CHILLER STYLE D WITH OPTIVIEW CONTROL CENTER Issue Date...

Страница 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Страница 3: ...these documents to the equipment If there is any question regarding the applicability of these documents rig ging lifting and operating service personnel should verify whether the equipment has been m...

Страница 4: ...JOHNSON CONTROLS 4 FORM 160 79 PW2 ISSUE DATE 01 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 5: ...Thermal Type Flow Sensor 12 Digital Type Flow Sensors 12 Electro Mechanical Starter Manual Reset Overloads 12 Remote Current Limit Setpoint with 0 10VDC 2 10VDC 0 20mA 4 20mA or Pulse Width Modulation...

Страница 6: ...Manual Reset Overloads 2300 To 4160 Volts U l Or C S A Approved Units Only 12 FIGURE 14 Electro Mechanical Starter Manual Reset Overloads 2300 To 4160 Volts U l Or C S A Approved Units Only 13 FIGURE...

Страница 7: ...ication of Sequence Control Kit so only one unit is running when a single unit can carry the cooling load 2 When multiple unit installations are controlled by an EMS a remote run stop switch input is...

Страница 8: ...signal a 0 to 10 or 2 to 10 volt D C signal 7 The Building Automation System BAS may be interfaced with the chiller OptiView Control Center to provide unified chiller plant system control The BAS Syst...

Страница 9: ...not per mitted to start due to a CYCLING shutdown condition The unit will automatically restart after the cycling condition is no longer present Unit Operation Manual Form 160 79 O1 provides a list an...

Страница 10: ...M EMS When the OptiView Control Center is in the Digital Analog or ISN remote operating mode and the Local Run Stop is in the RUN mode with the Remote Run Stop Switch contact connected to TB4 1 and TB...

Страница 11: ...UNIT SEQUENCE For multiple chiller installation application Multi Unit Sequence contacts are available to start and stop each unit The maintained closure of a device contacts across terminals 1 and 9...

Страница 12: ...0 available at additional cost When condenser water is flowing the flow switch contact will close Opening of the condenser water flow switch contacts for 2 continuous seconds will cause unit shutdown...

Страница 13: ...ion this jumper Important The signal type used for Re mote Current Limit Setpoint reset and the signal type used for Remote Leaving Chilled Liquid Temperature setpoint re set must be the same For exam...

Страница 14: ...4 X 4 375 100 17 5 82 5 83 LD06832 Figure 17 REMOTE CURRENT LIMIT SETPOINT WITH PWM SIGNAL PWM The Pulse Width Modulation input is in the form of a 1 to 11 second relay contact closure that applies 1...

Страница 15: ...oint then a 0 10VDC signal must be used for Leaving Chilled Liquid Temperature reset LD04500 Figure 18 REMOTE CURRENT LIMIT SETPOINT WITH 0 1VDC OR 2 10VDC SIGNAL 0 10VDC As shown in Figure 18 on page...

Страница 16: ...H 0 20MA OR 4 20MA SIGNAL 4 20mA As shown in Figure 19 on page 16 con nect input to Micro Board J22 4 signal and J22 5 Gnd A 4mA signal produces a 0 F offset A 20mA signal produces the maximum allowed...

Страница 17: ...int would be set to 44 F as follows OFFSET F 5 1 10 10 4 10 10 40 10 4 F SETPOINT F 40 4 44 F EXTERNAL SIGNAL FOR REFRIGERATION UNIT FAILURE When the Safety Shutdown Contacts see Figure 3 on page 9 ar...

Страница 18: ...o Unit Operation Manual Form 160 79 O1 When flow is sensed the flow sensor contacts are closed Opening of the flow sensor contacts no flow for 2 continuous seconds causes a cycling shutdown displaying...

Страница 19: ...des 6 Each 115VAC field connected inductive load i e relay coil motor starter coil etc shall have a tran sientsuppressorwired byothers inparallelwithits coil physically located at the coil Spare trans...

Страница 20: ...Pennsylvania USA 17349 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2019 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 79 PW2 119 Issue Date Januar...

Отзывы: