SECTION 2 - FIELD CONTROL MODIFICATIONS 

For example, if the input is 5VDC and the 

 

Remote Reset Temp. Range setpoint is programmed 

for 40°F, the setpoint would be set to 43.8°F.

OFFSET (°F)  = (5 – 2)(10) 

 8 

= (3)(10) 

     8 

= 30 

  8

SETPOINT (°F)  = 40 + 3.8 

= 43.8°F

0-20mA

 - As shown in 

Figure 19 on page 16,

 con-

nect input to Microboard J22-4 (signal) and J22-5 

(Gnd). A 0mA signal produces a 0°F offset. A 20mA 

signal produces the maximum allowed offset (10 or 

20°F above the local setpoint value). The setpoint is 

changed linearly between these extremes as the input 

varies over the range of 0-20mA. This input will only 

be accepted when 

Analog Remote Mode

 is selected, 

the 

Remote Analog Input Range

 setpoint is set for 

“0-10VDC” and Microboard Program Jumper J24 has 

been placed on pins 1 and 2. Calculate the setpoint for 

various inputs as follows:

OFFSET (°F) = (MA)(REMOTE RESET TEMP RANGE) 

 

   20

SETPOINT(°F) = LOCAL SE OFFSET

For example, if the input is 8mA, the Remote Reset 

Temp Range Setpoint is programmed for 10°F and the 

Local Leaving Chilled Liquid Temperature setpoint 

is programmed for 40°F, the setpoint would be set to 

44°F as follows:

OFFSET (°F)  = (8)(10) 

    20 

= (80) 

   20 

= 4°F

SETPOINT (°F)  = 40 + 4 

= 44°F

LD04501

FIGURE 19 - 

REMOTE LEAVING CHILLED LIQUID 

TEMPERATURE SETPOINT WITH 0-20MA OR 

4-20MA SIGNAL

4-20mA

 - As shown in

  Figure 19 on page 16,

 con-

nect input to Micro Board J22-4 (signal) and J22-5 

(Gnd.). A 4mA signal produces a 0°F offset. A 20mA 

signal produces the maximum allowed offset (10 or 

20°F above the Local setpoint Value). The setpoint is 

changed linearly between these extremes as the input 

varies over the range of 0-20mA. This input will only 

be accepted when 

Analog Remote Mode

 is selected, 

the 

Remote Analog Input Range

 setpoint is set for 

“2-10VDC” and Microboard Program Jumper JP24 

has been placed on pins 1 and 2. Calculate the setpoint 

for various inputs as follows:

OFFSET(°F) = (MA – 4)(REMOTE  TEMP. RESET RANGE)

 

16

SETPOINT(°F) = LOCAL SE OFFSET

For example, if input is 8mA, and the Remote Reset 

Temp. Range setpoint is programmed for 10°F and the 

Local Leaving Chilled Liquid Temperature setpoint 

is programmed for 40°F, the setpoint would be set to 

42.5°F as follows:

OFFSET (°F)  = (8 – 4)(10) 

 16 

= (4)(10) 

    16 

= 40 

  16 

= 2.5°F

SETPOINT (°F)  = 40 + 2.5 

= 42.5°F

REMOTE LEAVING CHILLED LIQUID 

TEMPERATURE SETPOINT WITH PWM 

SIGNAL

PWM

 – The Pulse Width Modulation input is in the 

form of a 1 to 11 second relay contact closure that ap-

plies 115VAC to the I/O Board TB4-19 for 1-11 sec-

onds. As shown in 

Figure 20 on page 17

, connect 

dry closure relay contacts between I/O Board TB4-19 

(input) and TB4-1 (115VAC). A contact closure time 

(pulse width) of 1 second produces a 0°F offset. An 11 

second closure produces the maximum allowed offset 

(10 or 20°F above the local setpoint value).

Содержание YD

Страница 1: ...DATE ________ APPROVAL DATE ________ CONSTRUCTION DATE _______ Supersedes 160 79 PW2 616 Form 160 79 PW2 119 FIELD CONTROL MODIFICATIONS FOR YD CHILLER STYLE D WITH OPTIVIEW CONTROL CENTER Issue Date...

Страница 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Страница 3: ...these documents to the equipment If there is any question regarding the applicability of these documents rig ging lifting and operating service personnel should verify whether the equipment has been m...

Страница 4: ...JOHNSON CONTROLS 4 FORM 160 79 PW2 ISSUE DATE 01 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 5: ...Thermal Type Flow Sensor 12 Digital Type Flow Sensors 12 Electro Mechanical Starter Manual Reset Overloads 12 Remote Current Limit Setpoint with 0 10VDC 2 10VDC 0 20mA 4 20mA or Pulse Width Modulation...

Страница 6: ...Manual Reset Overloads 2300 To 4160 Volts U l Or C S A Approved Units Only 12 FIGURE 14 Electro Mechanical Starter Manual Reset Overloads 2300 To 4160 Volts U l Or C S A Approved Units Only 13 FIGURE...

Страница 7: ...ication of Sequence Control Kit so only one unit is running when a single unit can carry the cooling load 2 When multiple unit installations are controlled by an EMS a remote run stop switch input is...

Страница 8: ...signal a 0 to 10 or 2 to 10 volt D C signal 7 The Building Automation System BAS may be interfaced with the chiller OptiView Control Center to provide unified chiller plant system control The BAS Syst...

Страница 9: ...not per mitted to start due to a CYCLING shutdown condition The unit will automatically restart after the cycling condition is no longer present Unit Operation Manual Form 160 79 O1 provides a list an...

Страница 10: ...M EMS When the OptiView Control Center is in the Digital Analog or ISN remote operating mode and the Local Run Stop is in the RUN mode with the Remote Run Stop Switch contact connected to TB4 1 and TB...

Страница 11: ...UNIT SEQUENCE For multiple chiller installation application Multi Unit Sequence contacts are available to start and stop each unit The maintained closure of a device contacts across terminals 1 and 9...

Страница 12: ...0 available at additional cost When condenser water is flowing the flow switch contact will close Opening of the condenser water flow switch contacts for 2 continuous seconds will cause unit shutdown...

Страница 13: ...ion this jumper Important The signal type used for Re mote Current Limit Setpoint reset and the signal type used for Remote Leaving Chilled Liquid Temperature setpoint re set must be the same For exam...

Страница 14: ...4 X 4 375 100 17 5 82 5 83 LD06832 Figure 17 REMOTE CURRENT LIMIT SETPOINT WITH PWM SIGNAL PWM The Pulse Width Modulation input is in the form of a 1 to 11 second relay contact closure that applies 1...

Страница 15: ...oint then a 0 10VDC signal must be used for Leaving Chilled Liquid Temperature reset LD04500 Figure 18 REMOTE CURRENT LIMIT SETPOINT WITH 0 1VDC OR 2 10VDC SIGNAL 0 10VDC As shown in Figure 18 on page...

Страница 16: ...H 0 20MA OR 4 20MA SIGNAL 4 20mA As shown in Figure 19 on page 16 con nect input to Micro Board J22 4 signal and J22 5 Gnd A 4mA signal produces a 0 F offset A 20mA signal produces the maximum allowed...

Страница 17: ...int would be set to 44 F as follows OFFSET F 5 1 10 10 4 10 10 40 10 4 F SETPOINT F 40 4 44 F EXTERNAL SIGNAL FOR REFRIGERATION UNIT FAILURE When the Safety Shutdown Contacts see Figure 3 on page 9 ar...

Страница 18: ...o Unit Operation Manual Form 160 79 O1 When flow is sensed the flow sensor contacts are closed Opening of the flow sensor contacts no flow for 2 continuous seconds causes a cycling shutdown displaying...

Страница 19: ...des 6 Each 115VAC field connected inductive load i e relay coil motor starter coil etc shall have a tran sientsuppressorwired byothers inparallelwithits coil physically located at the coil Spare trans...

Страница 20: ...Pennsylvania USA 17349 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2019 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 79 PW2 119 Issue Date Januar...

Отзывы: