223
JOHNSON CONTROLS
FORM 201.21-NM1 (616)
High Flash Tank Level Cutout Fault
The Flash tank level Cutout prevents the system from
running when the liquid level in the flash tank is too
high. The safety will be ignored for the first 15 seconds
of system operation.
A fault will occur if the tank level is greater than 85%
for 10 seconds.
Below is a sample Status fault display fault message:
SYSTEM SAFETIES (FAULTS) (CON'T)
SYS X YYYYYYYY HIGH FLASH TANK LEVEL
X indicates the system and YYYYYYY indicates the
system is in a “FAULT” condition and will restart when
the 120 second anti-recycle timer times out or “LOCK-
OUT” and will not restart until the operator clears the
fault using the keypad.
System Control Voltage Cutout Fault
The System Control Voltage Cutout alerts the operator
the 115VAC Control voltage to one of the systems is
missing. This could be due to a system fuse that has
been removed or is blown. The affected system will
fault and shut down immediately when the 115VAC
supply is lost.
The safety will “not” shut down a system if the Unit
Switch is OFF, which electrically removes the 115VAC
to “all” systems. The safety is only used to indicate a
situation where a single system is missing the 115VAC.
The safety will not cause a lockout and the system fault
will reset when power is returned. A sample message
is shown below:
SYS X YYYYYYYY CONTROL VOLTAGE
X indicates the system and YYYYYYY indicates the
system is in a “FAULT” condition and will restart when
the fault clears or “LOCKOUT” and will not restart until
the operator clears the fault using the keypad.
8
Содержание YCAV0157-0267
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519 ...
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM1 616 CONNECTION WIRING DIAGRAM 2 COMPRESSOR YCAV CHILLER CON T 6 LD12515 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM1 616 CONNECTION WIRING DIAGRAM 2 COMPRESSOR YCAV CHILLER CON T 6 LD12513 ...
Страница 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 616 LOCATION LABEL LD10519 TECHNICAL DATA ...
Страница 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 139: ...139 JOHNSON CONTROLS FORM 201 21 NM1 616 FIG 15 VSD LOGIC BOARD LD10582 COMPONENT LOCATIONS CON T 6 VSD LOGIC BOARD ...
Страница 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This Page Intentionally Left Blank ...
Страница 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 8 ...
Страница 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...
Страница 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...