237
JOHNSON CONTROLS
FORM 201.21-NM1 (616)
HISTORY KEY
LD10605
HISTORY
KEY
HISTORY Key Operation
The HISTORY key provides the user access to many
unit and system operating parameters captured at the
instant a unit or system safety (fault) shutdown occurs.
The history buffer will also capture system data at the
time of normal shutdowns such as cycling shutdowns.
When the HISTORY key is pressed the following screen
is displayed:
The
◄
and
►
(ARROW) keys allow choosing between
NORMAL SHUTDOWNS and FAULT SHUT-
DOWNS. “Fault” shutdowns provide information on
safety shutdowns, while “Normal” shutdowns provide
chiller cycling information on temperature (demand),
cycling, remote, system switch, etc., shutdowns that
are non-safety related shutdowns. Once the selection
is made, the
(ENTER) key must be pressed to enter
the selection.
HISTORY
CHOOSE HISTORY TYPE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
NORM HIST XX 18-JUN-20004 10:34:58 AM
SYS X COOLING DEMAND SHUTDOWN
NORM HIST XX 18-JUN-20004 10:34:58 AM
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
Normal Shutdowns History
If the NORMAL SHUTDOWNS History is selected,
the following screen will be displayed:
XX is the normal shutdown number. The display will
provide date and time of the shutdown and the reason
for the cycling shutdown (YYY….).
The operator can view any of the stored 20 single display
normal shutdown history buffers. History buffer number
1 provides the most recent shutdown information and
buffer number 20 is the oldest safety shutdown informa-
tion saved. The
◄
and
►
(ARROW) keys allow scrolling
between each of the history buffers. The
►
(ARROW)
key scrolls to the next normal history shutdown and the
◄
(ARROW) key scrolls to the previous normal history
shutdown.
The following display will typically be displayed on a
normal shutdown due to shutdown on lack of cooling
demand.
8
Содержание YCAV0157-0267
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519 ...
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM1 616 CONNECTION WIRING DIAGRAM 2 COMPRESSOR YCAV CHILLER CON T 6 LD12515 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM1 616 CONNECTION WIRING DIAGRAM 2 COMPRESSOR YCAV CHILLER CON T 6 LD12513 ...
Страница 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 616 LOCATION LABEL LD10519 TECHNICAL DATA ...
Страница 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 139: ...139 JOHNSON CONTROLS FORM 201 21 NM1 616 FIG 15 VSD LOGIC BOARD LD10582 COMPONENT LOCATIONS CON T 6 VSD LOGIC BOARD ...
Страница 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This Page Intentionally Left Blank ...
Страница 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 8 ...
Страница 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...
Страница 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...