273
JOHNSON CONTROLS
FORM 201.21-NM1 (616)
8
UNIT SETUP MODE (CON'T)
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 1 STARTS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 2 STARTS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 3 STARTS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 4 STARTS
= XXXXX
The following setup display is selectable as YES or NO
using the
◄
and
►
(ARROW) keys.
The following (3) setup OPTION displays are select-
able as ENABLED or DISABLED using the
◄
and
►
(ARROW) keys according to the options installed on
the chiller:
SETUP MODE CLEAR HISTORY BUFFERS?
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE REMOTE TEMP RESET OPTION
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE REMOTE CURRENT LIMIT OPTION
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE SOUND LIMIT OPTION
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXX
The following setup OPTION display is selectable as
ENABLED or DISABLED using the
◄
and
►
(AR-
ROW) keys:
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
REMOTE INPUTS SERVICE TIME = XX MIN
The following OPTION displays are selectable as EN-
ABLED or DISABLED using the
◄
and
►
(ARROW)
keys. The choices are:
·
NONE (default)
·
TEMP SENSOR 1
·
TEMP SENSOR 2
·
TEMP SENSOR 3
If a motor temperature sensor fails, a single sensor may
be ignored by making a program change in the Unit
Setup Mode. The default setting is “NONE”, indicating
all sensors are being monitored.
SETUP MODE SYS 1 MOTOR SENSOR TO IGNORE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE SYS 2 MOTOR SENSOR TO IGNORE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE SYS 3 MOTOR SENSOR TO IGNORE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE SYS 4 MOTOR SENSOR TO IGNORE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXX
Содержание YCAV0157-0267
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 55: ...55 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 57: ...57 JOHNSON CONTROLS FORM 201 21 NM1 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519 ...
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM1 616 CONNECTION WIRING DIAGRAM 2 COMPRESSOR YCAV CHILLER CON T 6 LD12515 ...
Страница 63: ...63 JOHNSON CONTROLS FORM 201 21 NM1 616 CONNECTION WIRING DIAGRAM 2 COMPRESSOR YCAV CHILLER CON T 6 LD12513 ...
Страница 64: ...64 JOHNSON CONTROLS FORM 201 21 NM1 616 LOCATION LABEL LD10519 TECHNICAL DATA ...
Страница 65: ...65 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 123: ...123 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 6 ...
Страница 139: ...139 JOHNSON CONTROLS FORM 201 21 NM1 616 FIG 15 VSD LOGIC BOARD LD10582 COMPONENT LOCATIONS CON T 6 VSD LOGIC BOARD ...
Страница 211: ...211 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This Page Intentionally Left Blank ...
Страница 233: ...233 JOHNSON CONTROLS FORM 201 21 NM1 616 This page intentionally left blank 8 ...
Страница 253: ...253 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...
Страница 281: ...281 JOHNSON CONTROLS FORM 201 21 NM1 616 8 This page intentionally left blank ...