The System Evaporator Inlet Refrig-
erant Tem per a ture will be printed if
the unit is in R407C mode.
SUCTION SUPERHEAT 3.4 DEGF
SAT DISCHARGE TEMP 74.5 DEGF
DISCHARGE SUPERHEAT 6.3 DEGF
SLIDE VALVE STEP 0
EEV OUTPUT 0.0 %
EVAPORATOR INLET REFRIG 44.6 DEGF
LIQUID LINE SOLENOID OFF
ECONOMIZER TXV SOLENOID OFF
CONDENSER FAN STAGE OFF
COMPRESSOR HEATER ON
WYE-DELTA RELAY OFF
SYSTEM 2 DATA
COMPRESSORS STATUS ON
RUN TIME 0- 0-15-26 D-H-M-S
MOTOR CURRENT 104 AMPS 87 %FLA
SUCTION PRESSURE 57 PSIG
DISCHARGE PRESSURE 233 PSIG
OIL PRESSURE 218 PSIG
SUCTION TEMPERATURE 42.9 DEGF
DISCHARGE TEMPERATURE 145.5 DEGF
OIL TEMPERATURE 102.8 DEGF
SAT SUCTION TEMP 31.7 DEGF
SUCTION SUPERHEAT 11.2 DEGF
SAT DISCHARGE TEMP 112.1 DEGF
DISCHARGE SUPERHEAT 33.4 DEGF
SLIDE VALVE STEP 70
EEV OUTPUT 35.6 %
EVAPORATOR INLET REFRIG 23.6 DEGF
LIQUID LINE SOLENOID ON
ECONOMIZER TXV SOLENOID ON
CONDENSER FAN STAGE 3
COMPRESSOR HEATER OFF
WYE-DELTA RELAY ON
DAILY SCHEDULE
S M T W T F S *=HOLIDAY
MON START=00:00AM STOP=00:00AM
TUE START=00:00AM STOP=00:00AM
WED START=00:00AM STOP=00:00AM
THU START=00:00AM STOP=00:00AM
FRI START=00:00AM STOP=00:00AM
SAT START=00:00AM STOP=00:00AM
HOL START=00:00AM STOP=00:00AM
Micro Panel Contents
4.5
HISTORY KEY
If a safety shutdown occurs on the chiller, a com pre -
hen sive list of operating and programmed settings data
is stored by the microprocessor. The information is
stored at the instant of the fault, regardless of whether
the fault caused a lockout to occur. This information is
not af fect ed by power failures or manual resetting of a
fault lockout.
The microprocessor stores data for up to 6 safety shut-
downs on 2 System units and 4 safety shutdowns on
3 or 4 compressor units. Once this limit is reached, a
fur ther shutdown will cause the oldest set of data to be
discarded in favor of storing the new shutdown data. The
Safety Shutdowns are numbered from 1 to 6 or 1 to 4
with num ber 1 always being the most recent.
If a remote printer is not connected, pressing the His-
to ry key allows the operator to locally scroll through
in for ma tion relating to the stored safety shutdowns on
the con trol panel display.
If a remote printer is connected, pressing the History key
will cause data from the last 6 shutdowns on a 2 com-
pressor chiller or 4 shutdowns on a 3 or 4 com pres sor
chiller to be transmitted from the mi cro pro ces sor to the
remote printer. The printout will begin with the most
recent fault which occurred. This does not affect the
stored data and as many prints as desired may be tak en.
See Section 4.7 for a HISTORY printout sample.
4.6
FAULT HISTORY DATA –
LOCAL DISPLAY MESSAGES
When the History key is pressed, the following mes sage
will appear:
To select a Safety Shutdown, press the appropriate key
on the numeric key pad, then press Enter. Remember that
the most recent fault information is stored as shut down
No. 1. After the ENTER Key is pressed, a mes sage in-
dicating the time and date of the Fault Shut down will
appear:
S H U T D O W N O C C U R R E D
5 : 5 9 A M 2 9 N O V 0 2
D I S P L A Y S A F E T Y S H U T -
D O W N N O . 1 ( 1 T O 4 )
Содержание YCAS
Страница 35: ...35 YORK INTERNATIONAL FORM 201 19 NM6 804 4 FIG 10 OPTION PANEL SECTION OPTION PANEL LAYOUT TYPICAL 00246VIP...
Страница 43: ...43 YORK INTERNATIONAL FORM 201 19 NM6 804 5 This page intentionally left blank...
Страница 45: ...45 YORK INTERNATIONAL FORM 201 19 NM6 804 6 This page intentionally left blank...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 19 NM6 804 7 LD09359 Electronic Panel 035 19205 104 Rev A...
Страница 79: ...79 YORK INTERNATIONAL FORM 201 19 NM6 804 LD09376 FIG 40 CONNECTION DIAGRAM 4 COMPRESSOR Power Panel...
Страница 81: ...81 YORK INTERNATIONAL FORM 201 19 NM6 804 LD09378 CONNECTION WIRING DIAGRAM Electronic Panel...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 19 NM6 804 FIG 43 CONNECTION DIAGRAM 4 COMPRESSOR LD09380 Power Panel...
Страница 91: ...91 YORK INTERNATIONAL FORM 201 19 NM6 804 This page intentionally left blank...
Страница 125: ...125 YORK INTERNATIONAL FORM 201 19 NM6 804 COMPRESSOR COMPONENTS CONT D FIG 68 COMPRESSOR COMPONENTS LD03669 7...
Страница 147: ...147 YORK INTERNATIONAL FORM 201 19 NM6 804 8 This page intentionally left blank...
Страница 205: ...205 YORK INTERNATIONAL FORM 201 19 NM6 804 8 This page intentionally left blank...