YORK INTERNATIONAL
13
FORM 150.62-NM7 (103)
EVAPORATOR PUMP START CONTACTS
Terminal block CTB2 – terminals 23 to 24, are nor mally-
open contacts that can be used to switch fi eld supplied
power to provide a start signal to the evapo rator pump
contactor. The contacts will be closed when any of the
following conditions occur:
1. Low Leaving Chilled Liquid Fault
2. Any compressor is running
3. Daily schedule is not programmed OFF and the
Unit Switch is ON
The pump will not run if the micro panel has been pow-
ered up for less than 30 seconds, or if the pump has
run in the last 30 seconds, to prevent pump motor over-
heat ing. Refer to Figure 6 and unit wiring dia gram.
SYSTEM RUN CONTACTS
Contacts are available to monitor system status. Nor-
mally-open auxiliary contacts from each com pressor
contactor are wired in parallel with CTB2 – terminals
25 to 26 for system 1, and CTB2 – termi nals 27 to 28
for system 2 (YCAL0117 - YCAL0377). Refer to Figure
6 and unit wiring diagram.
ALARM STATUS CONTACTS
Normally-open contacts are available for each re frigerant
system. These normally-open contacts close when the
system is functioning normally. The respective contacts
will open when the unit is shut down on a unit fault, or
locked out on a system fault. Field connections are at
CTB2 terminals 29 to 30 (system 1), and terminals 31
to 32 (system 2 YCAL0117 - YCAL0377).
REMOTE START/STOP CONTACTS
To remotely start and stop the chiller, dry contacts can be
wired in series with the fl ow switch and CTB1 - termi nals
13 to 14. Refer to Figure 6 and unit wiring diagram.
REMOTE EMERGENCY CUTOFF
Immediate shutdown of the chiller can be ac com plished
by opening a fi eld-installed dry contact to break the elec-
trical circuit between terminals 5 to L on terminal block
CTB2. The unit is shipped with a factory jumper in stalled
between terminals 5 to L, which must be removed if
emer gen cy shutdown contacts are installed. Refer to
Figure 6 and unit wiring diagram.
PWM INPUT
The PWM input allows reset of the chilled liquid set-
point by supplying a “timed” contact closure. Field wir ing
should be connected to CTB1 – terminals 13 to 20. A
de tailed explanation is pro vid ed in the Unit Control sec-
tion. Refer to Figure 6 and unit wiring diagram.
LOAD LIMIT INPUT
Load limiting is a feature that prevents the unit from
load ing beyond a desired value. The unit can be “load
limited” either 33%, 40%, 50%, 66% or 80%, de pend ing
on the number of compressors on unit. The fi eld con-
nec tions are wired to CTB1 – terminals 13 to 21, and
work in con junc tion with the PWM inputs. A de tailed
ex pla na tion is pro vid ed in the Unit Control sec tion. Refer
to Fig ure 6 and unit wiring diagram.
When using the Load Limit feature,
the PWM fea ture will not function
– SI MUL TA NEOUS OP ER A TION
OF LOAD LIMITING AND TEM-
PERATURE RE SET (PWM INPUT)
CAN NOT BE DONE.
FLOW SWITCH INPUT
The fl ow switch is fi eld wired to CTB1 ter mi nals 13 - 14.
See Figure 6 and unit wir ing diagram.
COMPRESSOR HEATERS
Compressor heaters are standard. If power is OFF more
than two hours, the crankcase heaters must be ener-
gized for 18 - 24 hours prior to restarting a compressor.
This will assure that liquid slugging and oil dilution does
not damage the compressors on start.
1
Содержание YCAL0043E Series
Страница 105: ...YORK INTERNATIONAL 105 FORM 150 62 NM7 103 2 This page intentionally left blank...
Страница 127: ...YORK INTERNATIONAL 127 FORM 150 62 NM7 103 LD07832 4 LD08851...
Страница 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM7 103 LD08855 4...
Страница 133: ...YORK INTERNATIONAL 133 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 135: ...YORK INTERNATIONAL 135 FORM 150 62 NM7 103 LD08858 4...
Страница 137: ...YORK INTERNATIONAL 137 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 139: ...YORK INTERNATIONAL 139 FORM 150 62 NM7 103 LD08862 4...
Страница 141: ...YORK INTERNATIONAL 141 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 143: ...YORK INTERNATIONAL 143 FORM 150 62 NM7 103 LD08865 4...
Страница 145: ...YORK INTERNATIONAL 145 FORM 150 62 NM7 103 4 LD08867...
Страница 147: ...YORK INTERNATIONAL 147 FORM 150 62 NM7 103 4 LD08869...
Страница 149: ...YORK INTERNATIONAL 149 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 151: ...YORK INTERNATIONAL 151 FORM 150 62 NM7 103 4 LD08872...
Страница 153: ...YORK INTERNATIONAL 153 FORM 150 62 NM7 103 LD08877 4...
Страница 155: ...YORK INTERNATIONAL 155 FORM 150 62 NM7 103 4 LD08874...
Страница 157: ...YORK INTERNATIONAL 157 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 159: ...YORK INTERNATIONAL 159 FORM 150 62 NM7 103 LD08830 4...
Страница 161: ...YORK INTERNATIONAL 161 FORM 150 62 NM7 103 LD08833 4...
Страница 163: ...YORK INTERNATIONAL 163 FORM 150 62 NM7 103 LD08835 4...
Страница 165: ...YORK INTERNATIONAL 165 FORM 150 62 NM7 103 This page intentionally left blank 4...
Страница 167: ...YORK INTERNATIONAL 167 FORM 150 62 NM7 103 LD08844 4...
Страница 169: ...YORK INTERNATIONAL 169 FORM 150 62 NM7 103 LD08847 4...
Страница 171: ...YORK INTERNATIONAL 171 FORM 150 62 NM7 103 LD08849 4...
Страница 173: ...YORK INTERNATIONAL 173 FORM 150 62 NM7 103 This page intentionally left blank 4...
Страница 182: ...YORK INTERNATIONAL 182 FORM 150 62 NM7 103 NOTES...
Страница 183: ...YORK INTERNATIONAL 183 FORM 150 62 NM7 103 NOTES...