Whenever the motor protector or discharge sensor shuts
down a compressor and the system, the internal com-
pressor contacts will open for a period of 30 minutes to
assure that the motor or scroll temperatures have time
to dissipate the heat and cool down.
After 30 minutes, the contacts will close and the system
will be permitted to restart. The micro will not try to restart
the compressors in a system that shuts down on this
safety for a period of 30 minutes to allow the internal
compressor timer to time out.
When System Current Feedback option is selected
(Op tion 11 under OPTIONS Key Current Feedback),
this safety will operate as follows. If the actual voltage
of the system exceeds the programmed trip voltage for
5 sec onds, the system will shutdown. This fault will not
be cleared until the condition is no longer present.
The Low Evaporator Temperature Cutout is to pro-
tect the evaporator from freeze-up with R-407C. This
safe ty uses the Cooler Inlet Refrigerant Temp Sensors
to mon i tor evaporator inlet refrigerant temperature on
each sys tem. These sensors are only installed on
R-407C units. This safety is ignored for the fi rst 270
seconds of runtime.
In water cooling mode, if the refrigerant temperature falls
below 21°F, the system will be shut down.
In glycol cooling mode, if the refrigerant temp. is below
21°F and falls 19°F below the leaving chilled liquid temp.,
the system will shut down.
In either cooling mode, if the cooler inlet refrigerant
temp. sensor reads out of range low, the system will
also shut down.
The Low Superheat Cutout is to protect the compressor(s)
from liquid fl oodback due to low suction superheat. This
safety is only active when EEV is se lect ed as the ex-
pan sion valve in SERVICE Mode. This safety is ignored
for the fi rst 15 sec onds of system runtime.
This cutout is ignored for the first 30 seconds of sys-
tem run time to avoid nuisance shut downs, especially
on units that utilize a low pressure switch in place of the
suction pressure transducer.
After the fi rst 3 minutes, if the suction pres sure falls
below the programmed cutout setting, a “transient
pro tec tion routine” is ac ti vat ed. This sets the cutout at
10% of the pro grammed value and ramps up the cutout
over the next 30 sec onds. If at any time during this 30
sec onds the suction pres sure falls below the ramped
cut out, the system will stop. This transient protection
scheme only works if the suc tion pressure transducer
is installed. When using the me chan i cal LP switch, the
operating points of the LP switch are: opens at 23 PSIG
+/- 5 PSIG (1.59 barg +/- .34 barg), and closes at 35
PSIG +/- 5 PSIG (2.62 barg +/- .34 barg).
The Motor Protector/Mechanical High Pressure Cutout
protects the compressor motor from overheating or the
system from experiencing dangerously high discharge
pressure.
This fault condition is present when CR1 (SYS 1) or
CR2 (SYS 2) relays de-energize due to the HP switch
or motor protector opening. This causes the re spec tive
CR contacts to open resulting in 0VDC to be applied on
the input to the microboard. The fault con di tion is cleared
when a 30VDC signal is restored to the input.
The internal motor protector opens at 185°F - 248°F
(85°C - 120°C) and auto resets. The me chan i cal HP
switch opens at 405 PSIG +/- 10 PSIG (27.92 barg +/-
.69 barg) and clos es at 330 PSIG +/- 25 PSIG (22.75
barg +/- 1.72 barg).
The compressor is also equipped with a discharge tem-
perature sensor for the purpose of sensing internal scroll
temperature. This sensor protects the scrolls from over-
heating due to inadequate cooling that may occur when
refrigerant charge is low, or superheat is too high.
When the sensor senses a high temperature, it opens
the motor protector ciricuit in the compressor causing
the compressor to shut down.
During the fi rst two faults an MP/HP INHIBIT message
will be displayed and the system will not be locked out.
Only after the third fault will the MP/HP Fault message
shown below be displayed on the status display. Ad-
ditionally, the system will be locked out.
S Y S 1 M P / H P C O I N H I B
S Y S 2 M P / H P C O I N H I B
2
S Y S 1 H I G H M T R C U R R
S Y S 2 H I G H M T R C U R R
S Y S 1 L O W E V A P T E M P
S Y S 2 L O W E V A P T E M P
S Y S 1 L O W S U P E R H E A T
S Y S 2 L O W S U P E R H E A T
S Y S 1 M P / H P C O F A U L T
S Y S 2 M P / H P C O F A U L T
Содержание YCAL0043E Series
Страница 105: ...YORK INTERNATIONAL 105 FORM 150 62 NM7 103 2 This page intentionally left blank...
Страница 127: ...YORK INTERNATIONAL 127 FORM 150 62 NM7 103 LD07832 4 LD08851...
Страница 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM7 103 LD08855 4...
Страница 133: ...YORK INTERNATIONAL 133 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 135: ...YORK INTERNATIONAL 135 FORM 150 62 NM7 103 LD08858 4...
Страница 137: ...YORK INTERNATIONAL 137 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 139: ...YORK INTERNATIONAL 139 FORM 150 62 NM7 103 LD08862 4...
Страница 141: ...YORK INTERNATIONAL 141 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 143: ...YORK INTERNATIONAL 143 FORM 150 62 NM7 103 LD08865 4...
Страница 145: ...YORK INTERNATIONAL 145 FORM 150 62 NM7 103 4 LD08867...
Страница 147: ...YORK INTERNATIONAL 147 FORM 150 62 NM7 103 4 LD08869...
Страница 149: ...YORK INTERNATIONAL 149 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 151: ...YORK INTERNATIONAL 151 FORM 150 62 NM7 103 4 LD08872...
Страница 153: ...YORK INTERNATIONAL 153 FORM 150 62 NM7 103 LD08877 4...
Страница 155: ...YORK INTERNATIONAL 155 FORM 150 62 NM7 103 4 LD08874...
Страница 157: ...YORK INTERNATIONAL 157 FORM 150 62 NM7 103 4 This page intentionally left blank...
Страница 159: ...YORK INTERNATIONAL 159 FORM 150 62 NM7 103 LD08830 4...
Страница 161: ...YORK INTERNATIONAL 161 FORM 150 62 NM7 103 LD08833 4...
Страница 163: ...YORK INTERNATIONAL 163 FORM 150 62 NM7 103 LD08835 4...
Страница 165: ...YORK INTERNATIONAL 165 FORM 150 62 NM7 103 This page intentionally left blank 4...
Страница 167: ...YORK INTERNATIONAL 167 FORM 150 62 NM7 103 LD08844 4...
Страница 169: ...YORK INTERNATIONAL 169 FORM 150 62 NM7 103 LD08847 4...
Страница 171: ...YORK INTERNATIONAL 171 FORM 150 62 NM7 103 LD08849 4...
Страница 173: ...YORK INTERNATIONAL 173 FORM 150 62 NM7 103 This page intentionally left blank 4...
Страница 182: ...YORK INTERNATIONAL 182 FORM 150 62 NM7 103 NOTES...
Страница 183: ...YORK INTERNATIONAL 183 FORM 150 62 NM7 103 NOTES...