YORK INTERNATIONAL
40
Dimensions -
YCAL0055EC - (English)
VIEW B-B
3 15/16"
3 1/4"
6 3/4"
BOTTOM OF PANEL
7/8" TYP.
62 5/8"
61 7/8"
45 1/8"
12 5/8"
3" VICTAULIC (typ)
90 1/4" BASE WIDTH
LEFT END
LIQUID OUT
34 11/16"
15 3/4"
9 15/16"
ELECTRICAL ACCESS
PANEL
LIQUID IN
Aluminum
Copper
YCAL
Center of Gravity (in.)
YCAL
Center of Gravity (in.)
X
Y
X
Y
0055
57.9
43.0
0055
62.5
43.2
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".
Содержание YCAL0041
Страница 10: ...YORK INTERNATIONAL 10 This page intentionally left blank...
Страница 61: ...YORK INTERNATIONAL 61 FORM 150 64 EG1 INTENTIONALLY LEFT BLANK...
Страница 68: ...YORK INTERNATIONAL 68 Power Wiring FIG 1 STANDARD POWER SUPPLY WIRING YCAL 0014 0080...
Страница 69: ...YORK INTERNATIONAL 69 FORM 150 64 EG1...
Страница 70: ...YORK INTERNATIONAL 70...
Страница 79: ...YORK INTERNATIONAL 79 FORM 150 64 EG1...