YORK INTERNATIONAL
13
FORM 150.64-EG1
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK Office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system (for YCAL0041-0065
models only).
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
Design Parameters
ENGLISH
YCAL
LEAVING WATER
TEMPERATURE (°F)
COOLER FLOW (GPM)
AIR ON CONDENSER (°F)
MIN
MAX
MIN
MAX
MIN
MAX
0041
40
55
40
200
0
125
0045
40
55
40
200
0
125
0051
40
55
40
200
0
125
0055
40
55
60
300
0
125
0061
40
55
60
300
0
125
0065
40
55
60
300
0
125
SI UNITS
YCAL
LEAVING WATER
TEMPERATURE (°DC)
COOLER FLOW (L/S)
AIR ON CONDENSER (°C)
MIN
MAX
MIN
MAX
MIN
MAX
0041
4.4
12.8
2.5
12.6
-17.7
51.7
0045
4.4
12.8
2.5
12.6
-17.7
51.7
0051
4.4
12.8
2.5
12.6
-17.7
51.7
0055
4.4
12.8
3.8
18.9
-17.7
51.7
0061
4.4
12.8
3.8
18.9
-17.7
51.7
0065
4.4
12.8
3.8
18.9
-17.7
51.7
Содержание YCAL0041
Страница 10: ...YORK INTERNATIONAL 10 This page intentionally left blank...
Страница 61: ...YORK INTERNATIONAL 61 FORM 150 64 EG1 INTENTIONALLY LEFT BLANK...
Страница 68: ...YORK INTERNATIONAL 68 Power Wiring FIG 1 STANDARD POWER SUPPLY WIRING YCAL 0014 0080...
Страница 69: ...YORK INTERNATIONAL 69 FORM 150 64 EG1...
Страница 70: ...YORK INTERNATIONAL 70...
Страница 79: ...YORK INTERNATIONAL 79 FORM 150 64 EG1...