AFFINITY DUAL CAPACITY HYDRONIC INSTALLATION MANUAL
HydroZone Controller Instructions cont.
If no heating is selected, the screen shall go to the COOLING screen.
If cooling fixed is selected, the default temperature for tank setpoint is 80°F with a 10°F deadband. The set range is
40°F to 85°F, with increments of 1°F. The dead band is 2°F to 15°F with increments of 1°F.
Staging
The controller can control up to four stages of compressors or three compressors and one auxiliary heat. How the unit
stages the outputs will be determined by how the outputs are configured. When selecting a dual capacity unit, the next
available stage will automatically become dual stage 2. Example: If DUAL 1 STG 1 has been selected for C1 then C2 will
automatically be DUAL 1 STG 2.
Output
Setup Configuration Options
Factory Defaults
C1
Single
Dual1 Stage1
Single
C2
Single
Dual1 Stage2
Off
Off
C3
Single
Dual2 Stage1
Off
Off
C4/W
Single
Dual2 Stage2
Aux
Off
Off
STAGING
C1 SINGLE / DUAL1 STG1
C2 OFF / SINGLE / DUAL1 STG2
C3 OFF / SINGLE / DUAL2 STG1
C4 OFF / SINGLE / DUAL2 STG2 /
AUX
WANT TO CHANGE?
YES
NO
OPTION
ENTER
STAGING
C1 DUAL1
STG1
C2 DUAL1
STG2
C3 SINGLE
C4 AUX
ADDITIONAL DEAD
BAND FOR AUX 5°
MAXIMUM OAT FOR AUX
HEAT
40°
WANT TO CHANGE?
YES
NO
OPTION
ENTER
Staging Screen
Staging Setup of 1 Dual Compressor
and 1 Single with Aux Enabled