30
AFFINITY DUAL CAPACITY HYDRONIC INSTALLATION MANUAL
Main Screen
After exiting from the setup mode, controller displays the main screen.
OPERATION, displays the current controller setup selection. They are OUTDOOR, TANK CONTROL AUTO, and TANK CONTROL
MANUAL MODE. If the operation mode is outdoor reset or tank control auto, the MODE should display OFF, ON, or EHEAT. If the
operation mode is tank control manual, the MODE should display OFF, HEAT, COOL, or EMHT. OUTPUT shall display the current
status of the outputs (WARM WEATHER SHUTDOWN, STANDBY, C1, C2, C3, C4, or AUX). STANDBY mode is active when the
controller is satisfied and waiting for a call. C1, C2, C3, and C4 will be off and O will stay in its previous state. If the outputs are off
due to a warm weather shutdown condition, the proper message should be displayed.
Mode Select Display
Manual Tank Control Display
Outdoor Reset or Tank Auto Control
OPERATING MODE
SELECTION
OFF
HEATING ONLY
COOLING ONLY
EMERGENCY HEAT
SELECTION
PREVIOUS ENTER
OPERATING MODE
SELECTION
OFF
ON
EMERGENCY HEAT
SELECTION
PREVIOUS ENTER
Change setpoint,
temperature, or
mode selection
Change setpoint
temperature or
mode selection
Enter or save selection
Change selection or mode
Maximum water
temperature needed for
minimum OAT
Lowest design outside
air temperature
Highest design outside air
temperature
Lowest design
water temperature
Tank setpoint temperature
Current mode of operation
Outdoor air temperature
Current tank temperature
Current compressor outputs
OFF, ON, EMERGENCY
SET DATE, SET TIME,
BACKLIGHTING, F/C, LOCK/
UNLOCK, SERVICE CONTACT INFO
HydroZone Controller Instructions cont.