30
The Aurora Base Control System cont.
CC2
EH1
Fa
ct
or
y
Fault
AL
G
AL
M
LS
ES
AC
C c
Status
AURORA BASE
CONTROL™
RV – K1
CC
2
CC – K2
CC Hi – K3
Fan – K4
Alarm – K5
Acc – K6
AC
C n
o
AC
C n
c
O/
B
C
R
LO
G
Y1
Y2
W
DH
3A
-F
us
e
O/
B
C
R
LO
G
Y1
Y2
W
DH
LO
G
HI
CCG
CC
FG
F
R
HP
HP
LP
FP2
FP2
FP1
REV
REV
CF
M
PW
M
ECM PWM
Fa
ct
or
y
Factory Fan Connection
R
R
CC
C
RS
4
85
EH2
C
EH1
C
CO
(+)
(-)
R
C
RS
485 E
xp
Fa
ct
or
y
Com1
Com2
Config
G
G
G
Y
R
SW1 Test
FP1 – 15
o
F/30
o
F
JW2 -
Alarm
P11
P5
P2
P1
P8
P7
P9
P6
P3
SW2
P13
P4
FP2 – 15
o
F/30
o
F
RV – B/O
ACC – Dip 4
ACC – Dip 5
CC – Dual/Single
L – Pulse/Continuous
Reheat/Normal
Fa
ct
or
y U
se
Field Connections
Field Connections
C
LP
FP1
F
CC
G
Y1
1
2
3
4
5
6
7
8
Off
On
N/A
R
S485 N
ET
LED3
LED2
LED1
ABC Control Board Layout
Aurora ‘Base’ Control LED Displays
These three LEDs display the status, configuration, and
fault codes for the control. These can also be read in plain
English via the Aurora AID Tool.
Status LED (LED3, Green)
Description of Operation
Fault LED, Green
Normal Mode
ON
Control is Non-functional
OFF
Test Mode
Slow Flash
Lockout Active
Fast Flash
Dehumidification Mode
Flash Code 2
(Future Use)
Flash Code 3
(Future Use)
Flash Code 4
Load Shed
Flash Code 5
ESD
Flash Code 6
(Future Use)
Flash Code 7
Fault LED (LED1, Red)
Red Fault LED
LED Flash
Code*
Lockout
Reset/
Remove
ABC Basic F
aults
Normal - No Faults
OFF
–
Fault - Input
1
No
Auto
Fault - High Pressure
2
Yes
Hard or Soft
Fault - Low Pressure
3
Yes
Hard or Soft
Fault - Freeze Detection FP2
4
Yes
Hard or Soft
Fault - Freeze Detection FP1
5
Yes
Hard or Soft
Fault - Condensate Overflow
7
Yes
Hard or Soft
Fault - Over/Under Voltage
8
No
Auto
Fault - FP1 & FP2 Sensor Error
11
Yes
Hard or Soft
NOTE:
All codes >11 use long flash for tens digit and short flash for the ones
digit. 20, 30, 40, 50, etc. are skipped.
Aurora Interface and Diagnostics (AID) Tool
The Aurora Interface and
Diagnostics (AID) Tool is
a device that is a member
of the Aurora network.
The AID Tool is used to
troubleshoot equipment
which uses the Aurora
control via Modbus RTU
communication. The AID
Tool provides diagnostics,
fault management, ECM
setup, and system configuration capabilities to the Aurora
family of controls. An AID Tool is recommended, although
not required, for ECM airflow settings. The AID Tool simply
plugs into the exterior of the cabinet in the AID Tool port.
AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL