background image

5168274-BIM-I-1121

Johnson Controls Ducted Systems

37

Evaporator Low Limit

During cooling operation, if the 

Evaporator Low Limit Sensor 

(EC1, 2)

 (Located on the Suction Line at the Evaporator Coil.) 

detects a temperature below 26 Deg. F (default), the UCB will 
de-energize the associated compressor, initiate the ASCD, and, 
if the other compressor is idle, stop the condenser fans. If the 
call for cooling is still present at the conclusion of the ASCD, the 
UCB will re-energize the halted compressor. Should the UCB 
detect the evaporator low limit sensor 

(EC1, 2)

 falling below 26 

Deg. F (default) three times within two hours of operation, the 
UCB will lock-out the associated compressor. If the other 
compressor is inactive, the condenser fans will be de-
energized.

Low Ambient Cooling

To determine when to operate in low ambient mode, the UCB 
has an 

Outdoor Air Temperature Sensor (OAT)

 with a low 

ambient setpoint at 45ºF (default). When the 

OAT Sensor

 

senses a temperature below the low ambient setpoint and the 
thermostat is calling for cooling, the UCB will operate in the low 
ambient mode.

Low ambient mode operates the compressors in this manner: 
10 minutes on, 5 minutes off. The indoor blower is operated 
throughout the cycle. The 5-minute off period is necessary to 
defrost the indoor coil.

Low ambient mode always begins with compressor operation. 
Compressor minimum run time may extend the minutes of 
compressor operation. The off cycle will begin immediately 
following the elapse of the minimum run time.

When operating in low ambient mode, an evaporator low limit 
sensor

 (EC1, 2)

 temperature below 26ºF will de-energize the 

associated compressor. If the call for cooling is still present at 
the end of the ASCD and the and the evaporator temperature 
sensor 

(EC1, 2)

 temperature is above 26°F, the unit will resume 

operation.

Safety Controls

The unit control board monitors the following inputs for each 
cooling system:
1.

An evaporator low limit sensor 

(EC1, 2) 

(Located on the 

Suction Line at the Evaporator Coil.) to protect against low 
evaporator temperatures due to a low airflow or a low 
return air temperature, set at 26°F.

2.

A high-pressure switch to protect against excessive 
discharge pressures due to a blocked condenser coil or a 
condenser motor failure, (opens at 625 ± 25 psig and 
resets 525 ± 25 psig).

3.

A low-pressure switch to protect against loss of refrigerant 
charge, (opens at 23 ± 5 psig and resets at 38 ± 5 psig).

The refrigeration systems are independently monitored and 
controlled. On any fault, only the associated system will be 
affected by any safety/preventive action. The other refrigerant 
system will continue in operation unless it is affected by the 
fault as well.

The unit control board monitors the temperature limit switch of 
electric heat units.

Compressor Protection

In addition to the external pressure switches, the compressors 
also have inherent (internal) protection. If there is an abnormal 
temperature rise in a compressor, the protector will open to shut 
down the compressor. The UCB incorporates features to 
minimize compressor wear and damage. An

 Anti-Short Cycle 

Delay (ASCD)

 is utilized to prevent operation of a compressor 

too soon after its previous run. Additionally, a minimum run time 
is imposed any time a compressor is energized.

The ASCD is initiated on unit start-up and on any compressor 
reset or lock-out.

Reset

Remove the call for cooling or heating, by raising or lowering 
thermostat setting higher than the conditioned space 
temperature.

Electric Heating Sequence Of Operations

With Electric Heat

When the thermostat calls for the first stage of heating, the low 
voltage control circuit is completed between “R” and “W1”. This 
24vac signal is passed through the UCB to the RW1 Relay. 
Contacts RW1 open, assuring the reversing valve cannot be 
energized, except during defrost. Contacts RW1 close. After its 
five minute ASCD timer is satisfied, the UCB closes its internal 
compressor relay contacts, sending a 24vac signal to the MV 
terminal of the UCB. If its ASCD timer is satisfied the UCB will 
energize compressor #1 contactor M1. After a two second 
delay, it then energizes compressor #2 contactor M2. 
Therefore, on a call for heat from W1, both sets of compressors 
are always energized, unless one or the other is locked out by 
the UCB. Also on the call for heat, the UCB energizes the M4 
and M10 contactor which brings on the condenser fans.

If the compressors alone cannot satisfy the heating 
requirements a second stage call from the thermostat 
completes the circuit between “R” and “W2”. This 24vac signal 
is passed through the UCB to the RW2 relay. Contacts RW2 
close, completing the circuit to the electric heat section (if 
available). For the 18 kW heater 18 kW will be energized, for 
the 36 kW heater 18 kW will be energized, for the 54 kW heater 
18 kW will be energized, and for 72 kW heater 36 kW will be 
energized. In the event that all compressors are locked out by 
the UCB, the total available kW of electric heat will be energized 
on a call for “W2”. Take note that the MV terminal on the UCB is 
constantly monitored while there is a demand for heat. If the 
UCB does not see 24vac at terminal MV after six minutes, it 
initiates an LCD display alarm, indicating a heating problem.

Without Electric Heat

When the thermostat calls for heating, the low voltage control 
circuit is completed between “R” and “W1”. This 24vac signal is 
passed through the UCB to the RW1 Relay and the MV terminal 
on the UCB. Contacts RW1 open, assuring the reversing valve 

Содержание XA Series

Страница 1: ...XA 15 XA 20 Physical Data 21 8 Electric Heat Minimum Supply Air 22 9 Smart Equipment Economizer Board Details 25 10 Altitude Temperature Correction Factors 30 11 Air Flow Performance Side Duct Applica...

Страница 2: ...other applicable safety precautions and codes including ANSI Z223 1 or CSA B149 1 latest edition Wear safety glasses and work gloves Use quenching cloth and have a fire extinguisher available during b...

Страница 3: ...t your local Ducted Systems parts distribution center for authorized replacement parts Approvals Design certified by CSA as follows 1 For use as a Heat Pump unit with supplemental electric heat 2 For...

Страница 4: ...ys Single Zone N Verasys Change Over Bypass P Verasys VAV Controls Option 15 20 Ton Model Number Nomenclature 00 00 Cooling Only A B Standard Static D High Static E VFD VAV Std Static G VFD VAV High S...

Страница 5: ...dian Electrical Code CSA C22 1 2 Installation Codes CSA B149 1 3 Local plumbing and waste water codes and 4 Other applicable local codes Refer to unit application data found in this document If compon...

Страница 6: ...60 5 432 504 125 575 3 60 5 540 630 125 Smart Equipment Control Board 110 Volt Convenience Outlet Powered or Non Powered Optional Disconnect Location Optional Disconnect Switch Bottom Power and Contr...

Страница 7: ...to Table 4 for clearances required for combustible construction servicing and proper unit operation Rigging And Handling Exercise care when moving the unit Do not remove any packaging until the unit i...

Страница 8: ...Weight Figure 6 Center of Gravity A D B C A D E C F B A B C D FRONT A C D F B E FRONT Table 2 XA 15 XA 20 Unit Weight Size Tons Model Weight lbs Center of Gravity 4 Point Load Location lbs 6 Point Loa...

Страница 9: ...ont 3 4 NPS Fem Bottom B 3 5 8 KO Power Wiring Front 3 NPS Fem Bottom 6 7 8 A CONTROL WIRING ENTRY COIL GUARD KIT CONDENSER COILS B POWER WIRING ENTRY 5 43 3 4 9 3 4 35 5 7 8 136 1 4 DOT PLUG For pres...

Страница 10: ...roper size of the supply and return air duct connections UNIT BASE WITH RAILS Shown separately to illustrate Bottom Duct openings and Power Connection locations 12 1 2 9 1 4 8 1 8 9 3 4 3 3 4 B POWER...

Страница 11: ...ncludes a power exhaust option The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels...

Страница 12: ...may be installed on combustable floors made from wood or class A B or C roof covering materials 0 Rear 24 W O Economizer Left 24 W O Economizer 49 W Economizer 36 W Economizer 3 3 If economizer is fac...

Страница 13: ...ges to insure adequate sealing Adjusting the damper to the desired air flow may be done before mounting the hood into position or after installation by removing the front hood panel or the screen on t...

Страница 14: ...essor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1 The internal wiring harnesses furnished with this unit are an integral part of the design cert...

Страница 15: ...tions enclosed with thermostat for general installation procedure Color coded insulated wires should be used to connect the thermostat to the unit Refer to Table 5 for control wire sizing and maximum...

Страница 16: ...Y1 G OCC Y2 X R SD 24 C W1 2 24V C 24 VAC Class 2 SD 24 Jumper Located on Harness Smoke Detector SD R 24V Output R If No Smoke Detector If Smoke Detector Is Used R Occ Jumper Smart Equipment Control...

Страница 17: ...100 19 2 15 6 5 0 NONE 38 3 50 E18 18 1 21 7 65 3 70 E36 36 2 43 3 65 3 70 E54 54 2 65 73 1 80 E72 72 2 86 6 94 7 110 575 3 60 9 78 14 1 6 5 2 0 NONE 28 7 35 E18 18 1 17 3 50 3 60 E36 36 2 34 6 50 3 6...

Страница 18: ...4 2 129 9 158 7 175 E72 72 2 173 2 202 225 460 3 60 12 2 100 19 2 15 6 5 5 NONE 43 3 50 E18 18 1 21 7 70 3 80 E36 36 2 43 3 70 3 80 E54 54 2 65 79 3 90 E72 72 2 86 6 101 110 575 3 60 9 78 14 1 6 5 2 4...

Страница 19: ...137 6 150 E54 54 2 129 9 154 2 175 E72 72 2 173 2 197 5 225 460 3 60 12 2 100 19 2 15 9 7 0 NONE 41 5 50 E18 18 1 21 7 68 5 70 E36 36 2 43 3 68 5 70 E54 54 2 65 77 1 90 E72 72 2 86 6 98 7 110 575 3 60...

Страница 20: ...50 E54 54 2 129 9 166 7 175 E72 72 2 173 2 210 225 460 3 60 12 2 100 19 2 15 9 7 5 NONE 46 5 50 E18 18 1 21 7 73 5 80 E36 36 2 43 3 73 5 80 E54 54 2 65 83 3 90 E72 72 2 86 6 105 110 575 3 60 9 78 14 1...

Страница 21: ...Capacity Btu hr 99 000 136 000 System power KW COP 13 62 2 05 20 96 2 05 DIMENSIONS inches Length 136 1 4 180 19 32 Width 92 92 Height 52 5 8 52 5 8 OPERATING WT lbs 2140 2650 COMPRESSORS Type Scroll...

Страница 22: ...drive the economizer including minimum position free cooling economizer loading and minimum outdoor air supply Economizer Minimum Position The economizer minimum position is set during occupied mode w...

Страница 23: ...modulate to control the supply air temperature to the Economizer Setpoint If the supply air temperature cannot be maintained within 5 F of the economizer setpoint the first stage compressor C1 will b...

Страница 24: ...ation Operation details include a Compares economizer output to the Economizer Damper Position For Exhaust Fan On and OFF b Energizes exhaust fan when economizer output is above Economizer Damper Posi...

Страница 25: ...mistor MAT parameter reports input status F C 3 65 VDC reading MAT to COM with open circuit Read only use in current control revision IN1 MAT LEDs at left on upper edge of economizer board POWER POWER...

Страница 26: ...power exhaust actuator and economizer actuator Connects through circuit trace to 24V IN pin HOT ECON 2 10 VDC output for the Economizer actuator Econ parameter reports output status 0 100 Used to posi...

Страница 27: ...negative for the indoor air quality sensor Connects through circuit trace to 24V IN pin COM R 24V 24 VAC hot supplied for the outdoor air quality sensor Connects through circuit trace to 24V IN pin HO...

Страница 28: ...panel from the unit Loosen but do not remove the two panel latches Locate the economizer actuator where the following adjustment can be made With power exhaust option each building pressurization req...

Страница 29: ...creases In order to use the indoor blower tables for high altitude applications certain corrections are necessary A centrifugal fan is a constant volume device This means that if the rpm remains const...

Страница 30: ...iven is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 1 5 832 1 80 Enter the blower table at 6000 sCFM and...

Страница 31: ...5 0 HP motor The 7 5 HP motor is required 6 1020 RPM is within the range of the 7 5 HP drives 7 Using the 7 5 HP motor and drive 3 5 turns open will achieve 1020 RPM Example Supply Air Blower Performa...

Страница 32: ...880 5 52 916 5 90 954 6 27 992 6 61 1030 6 94 1067 7 26 1103 7 58 7 5 HP Field Supplied Drive XA 20 20 Ton Side Duct Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes...

Страница 33: ...7 49 7600 852 4 73 885 5 21 920 5 63 956 6 01 992 6 36 1027 6 68 1063 6 98 1097 7 27 1130 7 56 7 5 HP Field Supplied Drive XA 20 20 Ton Bottom Duct Air Flow CFM Available External Static Pressure IWG...

Страница 34: ...e actual CFM through the unit can be determined from the curve in Pressure Drop vs Supply Air CFM Figure 19 After readings have been obtained remove the tubes and reinstall the two 5 16 dot plugs that...

Страница 35: ...tment Figure 17 4 Tighten blower pulley and motor sheave set screws after any adjustments Re check set screws after 10 12 hours run time recommended Belt drive blower systems MUST be adjusted to the s...

Страница 36: ...ower is energized whenever a cooling or heating operation is requested The blower is energized after any specified delay associated with the operation When energized the indoor blower has a minimum ru...

Страница 37: ...it is affected by the fault as well The unit control board monitors the temperature limit switch of electric heat units Compressor Protection In addition to the external pressure switches the compress...

Страница 38: ...emperature conditions must call for defrost continuously for 4 1 2 minutes before another defrost cycle is initiated A temperature inhibit feature prohibits defrost if the coil temperature is above 40...

Страница 39: ...Instructions 1 Turn unit electrical power on 2 Set the room thermostat setting to lower than the room temperature 3 First stage compressors will energize after the built in time delay five minutes 4...

Страница 40: ...naccurate 2 This chart is applicable to unit with the TXV s left to the factory setting If the TXV s have been adjusted in the field the charging chart may no longer apply 200 250 300 350 400 450 500...

Страница 41: ...ressure grease gun pump grease Chevron SRI 2 or equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is pu...

Страница 42: ...microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for factory accessory smoke detector condensate overflow and or user shutdown relay switching in series Connec...

Страница 43: ...t indicates 24 VAC is present at C and 24V terminals FAULT Red hard lockout networking error and firmware error indicator 1 2 second on off flashing indicates one or more alarm is currently active 1 1...

Страница 44: ...2 with open circuit Used in suction line temperature safety Pinned connections on right edge of UCB RAH Return Air Humidity input from 0 10 VDC 0 100 RH sensor Input required for reheat units optional...

Страница 45: ...r contactor coil indoor blower VFD enable relay coil Output with heat cool operation G input or schedule demand C1 24 VAC hot output for compressor 1 If demand is present and permissions allow compres...

Страница 46: ...er of the board Posi tive of the 15 VDC reading to C circuit for powering an optional netstat and or MultiTouch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8...

Страница 47: ...indicates the UCB is supplying power to the communication sub board 1 When wiring unit and other devices using the SA Bus and FC Bus see Table 20 Table 19 Smart Equipment UCB Details Continued Descri...

Страница 48: ...WLDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HT...

Страница 49: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Страница 50: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Страница 51: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Страница 52: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Страница 53: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Отзывы: