5168274-BIM-I-1121
Johnson Controls Ducted Systems
17
Table 6: Electrical Data
XA-15, XA-20 - Standard Drive Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat
(Field Installed Accessory Only)
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
-15
(15)
208-3-60 25
164
39
4.1
13.5
0
NONE
-
-
-
78
100
E18
13.5
1
37.5
124.8
125
E36
27
2
74.9
124.8
125
E54
40.6
2
112.7
157.7
175
E72
54.1
2
150.2
171.6
200
230-3-60 25
164
39
3.9
13
0
NONE
-
-
-
77.1
100
E18
18
1
43.3
131.2
150
E36
36
2
86.6
131.2
150
E54
54
2
129.9
146.2
175
E72
72
2
173.2
189.5
225
460-3-60 12.2
100
19
2.15
6.5
0
NONE
-
-
-
38.3
50
E18
18
1
21.7
65.3
70
E36
36
2
43.3
65.3
70
E54
54
2
65
73.1
80
E72
72
2
86.6
94.7
110
575-3-60
9
78
14
1.6
5.2
0
NONE
-
-
-
28.7
35
E18
18
1
17.3
50.3
60
E36
36
2
34.6
50.3
60
E54
54
2
52
58.5
70
E72
72
2
69.3
75.8
90
-20
(20)
208-3-60 34.3
239
52
3.4
20
NONE
-
-
-
110.8
125
E18
13.5
1
37.5
157.7
175
E36
27
2
74.9
157.7
175
E54
40.6
2
112.7
165.9
175
E72
54.1
2
150.2
204.4
225
230-3-60
3.4
19.4
NONE
-
-
-
110.2
125
E18
18
1
43.3
164.3
175
E36
36
2
86.6
164.3
175
E54
54
2
129.9
164.3
175
E72
72
2
173.2
218.5
225
460-3-60 17.9
125
28
1.8
9.7
NONE
-
-
-
57.2
70
E18
18
1
21.7
84.3
90
E36
36
2
43.3
84.3
90
E54
54
2
65
84.3
90
E72
72
2
86.6
111.3
125
575-3-60 12.8
80
20
1.4
7.8
NONE
-
-
-
42.2
50
E18
18
1
17.3
63.8
70
E36
36
2
34.6
63.8
70
E54
54
2
52
63.8
70
E72
72
2
69.3
85.5
90
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.