5168274-BIM-I-1121
Johnson Controls Ducted Systems
19
XA-15, XA-20 - High Static Drive Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat
(Field Installed Accessory Only)
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
-15
(15)
208-3-60 25
164
39
4.1
20
0
NONE
-
-
-
84.5
100
E18
13.5
1
37.5
131.3
150
E36
27
2
74.9
131.3
150
E54
40.6
2
112.7
165.9
175
E72
54.1
2
150.2
178.1
200
230-3-60 25
164
39
3.9
19.4
0
NONE
-
-
-
83.5
100
E18
18
1
43.3
137.6
150
E36
36
2
86.6
137.6
150
E54
54
2
129.9
154.2
175
E72
72
2
173.2
197.5
225
460-3-60 12.2
100
19
2.15
9.7
0
NONE
-
-
-
41.5
50
E18
18
1
21.7
68.5
70
E36
36
2
43.3
68.5
70
E54
54
2
65
77.1
90
E72
72
2
86.6
98.7
110
575-3-60
9
78
14
1.6
7.8
0
NONE
-
-
-
31.3
40
E18
18
1
17.3
52.9
60
E36
36
2
34.6
53.1
60
E54
54
2
52
61.7
70
E72
72
2
69.3
79
90
-20
(20)
208-3-60 34.3
239
52
3.4
26
NONE
-
-
-
116.8
150
E18
13.5
1
37.5
163.7
175
E36
27
2
74.9
163.7
175
E54
40.6
2
112.7
173.4
175
E72
54.1
2
150.2
210.4
225
230-3-60
3.4
25
NONE
-
-
-
115.8
150
E18
18
1
43.3
169.9
175
E36
36
2
86.6
169.9
175
E54
54
2
129.9
169.9
175
E72
72
2
173.2
224.1
225
460-3-60 17.9
125
28
1.8
12.5
NONE
-
-
-
60
70
E18
18
1
21.7
87.1
90
E36
36
2
43.3
87.1
90
E54
54
2
65
87.1
90
E72
72
2
86.6
114.1
125
575-3-60 12.8
80
20
1.4
10
NONE
-
-
-
44.4
50
E18
18
1
17.3
66
70
E36
36
2
34.6
66
70
E54
54
2
52
66
70
E72
72
2
69.3
87.7
90