background image

ELECTRIC CONTROLS

RETURN LIQUID TEMPERATURE CONTROL (TC)

The YORK model TC-6A return liquid temperature control is a
4 stage solid state thermostat that maintains the desired chilled
liquid temperature by sensing and regulating the liquid tem-
perature returning to the cooler. The control is mounted in the
compressor compartment, to the left of the main control box in
front of the system 2 compressor. The return water temperature
is sensed by a thermistor (SENSOR) located in the return liquid
line. Its resistance varies with changes in return liquid tempera-
ture. Changes in the thermistor resistance are interpreted by
the controller and are amplified to energize output relay con-
tacts. The circuitry is such that the controller shuts down the
compressor in the event the thermistor is disconnected or
accidentally cut. The return water temperature is adjustable
between 4

°

F and 70

°

F. This adjustable range is much greater

than applicable to this chiller. See Table 1 for limitations in
leaving liquid temperatures. The Between Stage Differential is
adjustable between 1

°

F and 3.75

°

F.

On both the W1LC420 and 530, the control is factory adjusted
to 54

°

F Return Liquid Temperature with the Between Stage

Differential set at 2.5

°

F which results in a 44

°

F (10

°

 Range)

leaving liquid temperature at nominal conditions. Check that
these settings are still correct or change the setting as required
but do not exceed the application limitations in Table 1.

If the factory temperature control settings which provide 44

°

F

leaving liquid temperature with a 10

°

F liquid temperature range

are not desired for the W1LC420 or 530 installation, the re-
quired leaving liquid temperature and liquid temperature range
must be specified before the new temperature control settings
can be determined. To determine the Between Stage Differen-
tial setpoint on the temperature control for the W1LC420/530,
divide the specified range by 4. The Return Liquid Temperature
setpoint on the control is calculated by adding the specified
liquid temperature range to the specified leaving liquid tem-
perature.

EXAMPLE:

(W1LC420/530) Specified 45

°

F leaving liquid temperature with

an 8

°

F liquid temperature range.

Calculate Between Stage Differential Setpoint.
8

°

F - 4

°

F = 2

°

F

Calculate Return Liquid Temperature Setpoint.
45

°

F + 8

°

F = 53

°

F

As an example of how the TC-6A control works in application,
consider the W1LC420 chiller with the control set to maintain
a 54

°

F return water temperature with a 2.5

°

F Between Stage

Differential. The flow rate is set to 2.4 GPM/measured TON,
(10

°

F range) and the working fluid is water. The W1LC420 is a

4 stage machine with stages at 25%, 50%, 75% and 100%

capacity. All temperatures considered are for a TC-6A control
and thermistor working at design conditions. Allowable toler-
ances could change the actuation temperatures by 

±

1.25

°

F.

With the RETURN water temperature to the cooler rising due
to increasing cooling load for the application, the #1 compres-
sor will start at part load when the RETURN water temperature
reaches 47.75

°

F. The LEAVING water temperature will quickly

drop to 45.25

°

F. If the cooling load continues to increase, the

#1 compressor will be fully loaded by the controller when the
RETURN water temperature reaches 50.25

°

F. With increasing

load, the controller will start the #2 compressor at 52.75

°

F

RETURN water temperature and fully loaded it at 55.25

°

F.

Under increasing load, the minimum LEAVING water tempera-
tue will be 45.25

°

F and the maximum 47.75

°

F. As the demand

for cooling load decreases, the controller will unload compres-
sor stages in reverse order to the way they were loaded at
52.75, 50.25, 47.75 and 47.75

°

F RETURN water temperature.

During decreasing load, the minimum LEAVING water tem-
perature will be 42.75

°

F and the maximum 45.25

°

F.

FREEZE CONTROL PREVENTION THERMOSTAT (FC)

The leaving liquid freeze prevention thermostat is designed to
prevent the liquid temperature in the cooler from dropping
below the freezing point of the fluid while the unit is running.

CAUTION: Freezing fluid in the cooler can cause damage

which can lead to total replacement of the cooler.

If the temperature of the liquid leaving the cooler drops below
its set point the control energizes 2R. 2R-1  and 2R-2 open and
shut both compressors off immediately. The control must be
manually reset when the bulb temperature rises to 6

°

F above

the setpoint cutout temperature. The body of the control is in
the compressor compartment attached to the left hand side of
the control box. The sensing bulb is the capillary type located
in a well in the leaving water connection at the far end of the
cooler. This is a cross ambient sensing device that is not
effected by changes in ambient temperature.

The freeze control is factory set to shut down the unit at 36

°

F

(

±

 2) and is manually reset when the bulb temperature reaches

42

°

F. This setting is for a working liquid of pure water and many

light brine applications. In heavy brine applications, the control
may be field adjusted using the adjustment screw at the top of
the control.

CAUTION: It is recommended that the adjusted cutout tem-

perature be at least 4

°

F above the freezing point of

the fluid. In no brine application should the setpoint
be adjusted below 30

°

F.

If during delivery to the job site or during non-op-
erational periods when the ambient temperature of
the freeze control bulb drops below 36

°

F, the freeze

control may have tripped and needs to be manually
reset before the unit will start.

570.05-N4Y

Unitary Products Group

11

Содержание W1LC420

Страница 1: ...referenced in this instruc tion may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York Pa 17405 INSPECTION As soon as a unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill A separate request for inspection by the carrier s agent should be made in...

Страница 2: ... 10 Condenser Fan Motor Control 10 Electric Controls 11 MAINTENANCE General 12 Cleaning Condenser Surface 12 Lubricating Fan Motors 12 Compressor Replacement 12 Secure Owner s Approval 12 TABLES No Description Page 1 Application Data 3 2 Physical Data 4 3 Electrical Data 6 4 Electrical Data International Models 6 5 Water Side Pressure Drop 6 FIGURES No Description Page 1 Unit Handling 3 2 Support ...

Страница 3: ... location should be selected for minimum sun exposure and to insure an adequate supply of fresh air for the condenser Avoid locations beneath windows or between struc tures where normal operating sounds may be objectionable The condenser fans are propeller type and are not suitable nor intended for use with duct work in the condenser air stream On either rooftop or ground level installations rubbe...

Страница 4: ...move the compressor hold down nuts and shipping spac ers Install rubber grommets shipped in bag tied to compressor Replace the hold down nuts and tighten until they start to bind the rubber grom mets Continue to tightened additional half turn See Figure 3 DISCHARGE LINE HOLD DOWN BRACKET CAUTION Do NOT remove the discharge line support brack ets located within the compressor compartment It reduces...

Страница 5: ...ut located on the bottom of the electrical box Remove the plastic plug from the knockout and discard See Table 3 or 4 for electrical data The disconnect switch may be bolted to the side of the unit but not to any of the removable panels this would interfere with access to the unit Make sure that no refrigerant lines or coils will be punctured when mounting the disconnect switch and note that it mu...

Страница 6: ...LC420 A50 380 415 3 50 2 38 0 each 1651 each 380 415 1 50 3 4 4 2 2 3 2 5 105 110 2 320 380 368 415 A40 380 3 60 2 52 1 each 208 each 460 1 60 3 4 4 2 2 3 2 5 135 150 0 377 W1LC530 A50 380 415 3 50 1 1 38 0 62 7 1651 2252 380 415 1 50 3 4 5 2 2 3 2 5 135 150 0 369 380 412 415 A40 380 3 60 1 1 52 1 77 8 208 307 460 1 60 3 4 5 2 2 3 2 5 170 200 00 357 1100 Amps on part winding start 4Based on three ...

Страница 7: ...GHT Lbs Oper Dry W1LC420 10 x 7 4 13 72 1 2 12 7 8 26 800 700 W1LC530 10 x 7 4 13 72 1 2 12 7 8 26 800 700 Nominal pipe size victaulic type COOLER DIMENSIONS WEIGHTS FRONT 36 BACK 24 LEFT SIDE 24 RIGHT SIDE 24 TOP 120 One side only NOTE The area within the clearances shown above and area under the unit must be kept clear of all obstructions that would impede free air flow to the unit In installati...

Страница 8: ... off after completion of the pumpdown cycle Turning OFF the main power supply will stop the unit immediately 6 To determine if the unit is operating properly the refrigerant subcooling and superheat should be checked SEQUENCE OF OPERATION NOTE The contact opening and closing times for 50 HZ units are 5 6 of those listed for 60 HZ units System start up and staging is controlled by the TC which is e...

Страница 9: ...ressor crankcase heater 2CCH while the compressor runs 4 After 2 minutes low pressure bypass timer 5TR 1 opens If the compressor suction pressure remains abnormally low after initial start up the compressor circuit will lock out as described in the HIGH LOW PRESSURE LOCKOUT section When the fourth stage of the TC 81 calls for cooling 1 Contacts TC 7 will close to energize relay 11R and 12R 2 When ...

Страница 10: ...e drops below 180 psig high pressure con trol 2HP will close to energize relay 3R When contact 3R 1 opens and contact 3R 2 closes condenser fan 3 will be powered through choke coil 1CH and its speed will drop to 450 RPM Timer 3TR will remain open for 10 seconds after unit start up so the condenser fan 3 will always start at high speed NO 2 20 TON SYSTEM Under 65 F the 4 condenser fan will shut off...

Страница 11: ... 100 capacity All temperatures considered are for a TC 6A control and thermistor working at design conditions Allowable toler ances could change the actuation temperatures by 1 25 F With the RETURN water temperature to the cooler rising due to increasing cooling load for the application the 1 compres sor will start at part load when the RETURN water temperature reaches 47 75 F The LEAVING water te...

Страница 12: ... means Take care so as not to damage or bend the condenser fins LUBRICATING FAN MOTORS The condenser fan motors are equipped with factory lubricated and sealed ball bearings requiring no maintenance COMPRESSOR REPLACEMENT Obtain replacement compressors or parts from your local Copeland Wholesaler See Instruction Form 55 72 RD2 2 for replacement compressor reference data SECURE OWNER S APPROVAL WHE...

Отзывы: