Correction of the actual air inlet temperature on the outdoor coil for different air flows to the nominal flow
% Flow
70
80
90
100
110
120
130
Correction in °C of the actual air inlet temper‐
ature on the outdoor coil
5
3
1,5
0
-1
-2
-2,5
Correction factors for heating capacities
Indoor unit supply air
DB temperature °C
Indoor unit air DB temperature °C
14
10
6
0
-8
23
1,2
1,04
0,96
0,77
0,58
20
1,25
1,1
1
0,8
0,69
17
1,3
1,13
1,04
0,83
0,63
Heating capacity correction factors according to length and height between units
H Vertical distance between the indoor unit and
the outdoor unit
L
E
Equivalent length of pipes between the indoor
unit and the outdoor unit
(consider a single line)
A Outdoor unit above indoor unit
B Indoor unit above outdoor unit
1 Indoor unit
2 Outdoor unit
Correction of the actual air inlet temperature on the outdoor coil for different air flows to the nominal flow
% Flow
70
80
90
100
110
120
130
Correction in °C of the actual air inlet
temperature on the outdoor coil
-2
-1,5
-0,5
0
0,5
1
1,2
A
B
A
B
1
2
1
2
Installation manual
1
Technical data
1.4
5