background image

5894307-UIM-B-0920

Johnson Controls Ducted Systems

29

SECTION X: NORMAL OPERATION AND 

DIAGNOSTICS

NORMAL OPERATION SEQUENCE

The following describes the sequence of operation of the furnace. Refer
to Owners Manual for component location.

Continuous Blower

Cooling/heating  thermostats  have  a  fan  switch  that  has  an  ON  and
AUTO position. In the ON position, the thermostat circuit is completed
between  terminals  R  and  G. The  motor  operates  continuously  on  the
speed  tap  wire  that  is  connected  to  the  FAN  terminal  on  the  furnace
control board. To obtain a different circulating fan (continuous blower)
speed, change the wire connected to the FAN connection with one of
the speed tap wires located on the PARK terminals. 

Intermittent Blower - Cooling

Cooling/heating  thermostats  have  a  fan  switch  that  has  an  ON  and
AUTO  position.  In  the AUTO  position,  the  thermostat  circuit  is  com-
pleted between terminals R and G when there is a call for cooling. The
motor operates on the speed tap wire that is connected to the COOL
cooling terminal on the control board. The fan off setting is fixed at 60 s
to improve cooling efficiency.

Heating Cycle

When the thermostat switch is set on HEAT and the fan is set on AUTO,
and there is a call for heat, a circuit is completed between terminals R
and W of the thermostat. The induced draft blower starts and runs for
several  seconds  to  bring  fresh  combustion  air  into  the  combustion
chamber. Then the induced draft blower shuts off and the hot surface
igniter glows for about 17 s. After this warm up, the induced draft blower
starts  again  and  the  ignition  module  opens  the  main  gas  valve.  The
blower  motor  energizes  30  s  after  the  gas  valve  opens,  if  a  flame  is
detected. Normal furnace operation continues until the thermostat cir-
cuit between R and W is opened, which causes the ignition system and
gas valve to de-energize and the burner flames to be extinguished. The
vent  motor  operates  for  15  s  and  the  blower  motor  operates  for  the
amount of  time  set  by the fan-off  delay jumper located on the control
board. See Figure 32. The heating cycle is now complete, and ready for
the start of the next heating cycle.
If the flame is not detected within 7 s of the gas valve opening, the gas
valve is shut off and a retry operation begins. Also, if the flame is lost for
2 s during the 10-s stabilization period, the gas valve is shut off and a
retry operation begins. During a retry operation, the vent motor starts a
15-s inter-purge and the ignitor warm-up time is extended to 27 s. If the
flame is established for more than 10 s after ignition during a retry, the
control clears the ignition attempt (retry) counter. If three retries occur
during a call for heat, the furnace shuts down for 1 h. If at the end of the
1-h shut down there is a call for heat, the furnace initiates a normal start
cycle. If the problem has not been corrected, the furnace locks out after
three retries.
A  momentary  loss  of  gas  supply,  a  flame  blowout,  or  a  faulty  flame
probe  circuit  results  in  a  disruption  in  the  flame  and  is  sensed  within
1.0  s.  The  gas  valve  de-energizes  and  the  control  begins  a  recycle
operation. A normal ignition sequence begins after a 15-s inter-purge. If
during the five recycles, the gas supply does not return, or the fault con-
dition is not corrected, the ignition control locks out for 60 min.
During burner operation, a momentary loss of power for 50 milliseconds
or longer de-energizes the gas valve. When the power is restored, the
gas valve remains de-energized and the ignition sequence immediately
restarts.

TROUBLESHOOTING

Make the following visual checks before troubleshooting:
1. Check that the power to the furnace and the ignition control module

is ON.

2. Check that the manual shut-off valves in the gas line to the furnace

are open.

3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the

thermostat  above  the  room  temperature.  Observe  the  system’s
response,  then  use  the  NORMAL OPERATION  SEQUENCE  sec-
tion to check the system’s operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. A blinking LED light
on the control board can flash red, green, or amber to indicate various
conditions. The control continuously monitors its own operation and the
operation  of  the  system.  If  a  fault  occurs,  the  LED  light  indicates  the
fault code. 
The  flash  codes  listed  below  have  the  following  timing:  the  LED  light
turns on for 1/4 s and turns off for 1/4 s. This pattern is repeated the
number  of  times  equal  to  the  code.  There  is  a  1.5-s  pause  between
codes.  For  example,  the  6  Red  Flashes

 

code  means  the  LED  light

flashes on and off six times and then remains off for 1.5 s. This pattern
repeats as long as the fault condition remains.

Steady on Green: 

Indicates normal operation with no thermostat calls.

1  Green  Flash: 

Indicates  normal  operation  with  a  thermostat  call  for

heat.

2 Green Flashes: 

Indicates normal operation with a thermostat call for

cooling. 

3 Green Flashes: 

Indicates normal operation with a thermostat call for

continuous fan.

LED Steady Off:

 If the LED light does not flash at all, check for power

to the control board. If the control board is correctly powered, the con-
trol board may need to be replaced.

 

Steady on Red: 

Indicates a control failure. Turn off the power to the fur-

nace  and  turn  on  the  power  to  the  furnace  again.  If  the  fault  code
returns,  the  control  board  must  be  replaced. The  control  board  is  not
field-repairable.

1 Red Flash: 

Indicates system lockout due to too many retries.

2  Red  Flashes: 

Indicates  a  pressure  switch  null  error.  The  pressure

sensor  is  sensing  pressure  when  there  should  not  be  any  pressure.
Check for a faulty pressure sensor or miswiring.

3 Red Flashes:

 Indicates a pressure switch span error. The pressure

sensor is not sensing the correct pressure. Check for the following:

• Faulty inducer
• Blocked vent pipe
• Broken pressure sensor hose
• Disconnected pressure sensor or inducer wires
• Faulty pressure sensor

 WARNING

Never bypass any safety control to allow furnace operation. To
do so will allow furnace to operate under potentially hazardous
conditions.
Do  not  try  to  repair  controls.  Replace  defective  controls  with
OEM Source 1 Parts.
Never adjust pressure switch to allow furnace operation.

!

Содержание TL9E Series

Страница 1: ...Wiring Diagram 32 LIST OF TABLES Unit Clearances to Combustibles 4 Cabinet and Duct Dimensions 6 Recommended Filter Sizes High Velocity 600 FPM 7 Ratings and Physical Electrical Data 8 Maximum Equival...

Страница 2: ...alled directly on carpeting tile or other combustible material other than wood flooring Check the rating plate and power supply to be sure that the elec trical characteristics match All models use nom...

Страница 3: ...t piping and elbows are required As centralized with the air distribution as possible Where adequate combustion air is available particularly when the appliance is not using outdoor combustion air Whe...

Страница 4: ...be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct such that smoke or reflected light would be observable...

Страница 5: ...ION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The line contact is only permissible between lines that are formed by the inters...

Страница 6: ...t and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joists See Figure 5 for details and...

Страница 7: ...p leg and ground union is required See Figure 10 For left side supply gas pipe arrangement two 1 2 in elbows and two 1 2 in x 1 1 2 in pipe nipples must be used The arrangement shown in Figure 9 align...

Страница 8: ...with DOE test procedures Wire size and overcurrent protection must comply with the National Electrical Code NFPA 70 latest edition and all local codes The furnace must be installed so the electrical...

Страница 9: ...Figure 11 LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the m...

Страница 10: ...1 67 LU RQGLWLRQHU 9ROW RPPRQ RPSUHVVRU RQWDFWRU XOO 6WDJH HDW 7 50267 7 Figure 13 Thermostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJ...

Страница 11: ...pplied to the hose con nected to the top of the condensate trap Screw the condensate trap to the condensate trap bracket supplied Then thread the hose adapters together below the furnace casing using...

Страница 12: ...collec tor box as shown in Figures 16 and 17 The drain hose must not sag or droop after it is installed If glue is used when connecting the intake pipe to the intake coupling the drain opening in the...

Страница 13: ...5894307 UIM B 0920 Johnson Controls Ducted Systems 13 Figure 16 Upflow Configuration UPFLOW LEFT SIDE DRAIN UPFLOW RIGHT SIDE DRAIN EXTERNAL CONDENSATE TRAP EXTERNAL CONDENSATE TRAP A1128 001...

Страница 14: ...DRAIN AIRFLOW EXTERNAL CONDENSATE TRAP HORIZONTAL LEFT HORIZONTAL RIGHT MOVE RAIN GUTTER HOSE TO THIS POSITION MOVE CONDENSATE DRAIN HOSE TO THIS POSITION INTAKE PIPE DRAIN AIRFLOW EXTERNAL CONDENSAT...

Страница 15: ...models are supplied with 2 in 5 1 cm vent connections When the pipe must be increased to 3 in 7 6 cm diameter the transition from 2 in to 3 in must be done as close to the furnace as possible The 2 i...

Страница 16: ...igure 18 Elbow Dimensions A A A A STANDARD ELBOW LONG SWEEP ELBOW Table 6 Elbow Dimensions Elbow A Dimension Illustrated in Figure 18 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 i...

Страница 17: ...nform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight and watertight seal 8 Install the combustion air and vent piping such that it has a 1 4 in ft 21...

Страница 18: ...equirements of the gas supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with...

Страница 19: ...3 to 24 Each furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 23 and 24 can...

Страница 20: ...tion See Figure 28 VENTILATED COMBUSTION AIR Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated att...

Страница 21: ...operated damper or manually adjustable louvers are not permitted for use An automatically operated damper or automatically adjustable louvers must be interlocked so the main burner can not operate un...

Страница 22: ...kW of the total input rating of all equipment located in the enclosure Not less than the sum of all vent connectors in the confined space The duct must be least the same cross sectional area as the fr...

Страница 23: ...s dryers and TURN ON any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Open the fireplace dampers Do not operate a summer exhaust fan 4 Follow the light...

Страница 24: ...surface igniter glows for about 17 s b After this warm up the induced draft blower starts again and the ignition module opens the main gas valve c After flame is established the supply air blower sta...

Страница 25: ...0 300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 23...

Страница 26: ...ws on main gas valve 2 Turn on gas and electrical supplies and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw...

Страница 27: ...gas sample for analysis it is permissi ble to drill a small hole in the plastic flue pipe for a sample probe pro vided that the vent piping is PVC and the hole is correctly sealed afterwards If using...

Страница 28: ...ated on the furnace vesti bule panel near the gas valve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by the following A dirty...

Страница 29: ...sensed within 1 0 s The gas valve de energizes and the control begins a recycle operation A normal ignition sequence begins after a 15 s inter purge If during the five recycles the gas supply does not...

Страница 30: ...d Red Flashes Indicates incorrect line voltage polarity The polar ity of the incoming power to the furnace is reversed Soft Lockout The control includes a soft lockout that resets automati cally after...

Страница 31: ...Door 1 5 ft required GROMMET 3 required HARNESS WIRING HOSE CONDENSATE HOSE RAIN GUTTER KNOB QUARTER TURN 4 required MOTOR MOUNT ORIFICE BURNER PAN CONDENSATE PLUG SEAL 7 8 in PLUG SEAL 2 3 8 in PLUG...

Страница 32: ...5894307 UIM B 0920 32 Johnson Controls Ducted Systems SECTION XII WIRING DIAGRAM Figure 33 Wiring Diagram...

Страница 33: ...ree Ells of 90 Degree Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control b...

Страница 34: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Отзывы: