background image

5894307-UIM-B-0920

26

Johnson Controls Ducted Systems

ADJUSTMENT OF MANIFOLD GAS PRESSURE AND 

INPUT RATE

Inlet and manifold gas pressure can be measured by connecting the U
tube  manometer  to  the  gas  valve  with  a  piece  of  tubing.  Follow  the
appropriate section in the instructions below. See Figure 30 for the loca-
tions of the pressure ports on the gas valve.

Turn gas off at the ball valve or gas cock on gas supply line 
before the gas valve. Find the pressure ports on the gas 
valve marked Out P and In P.

1. The manifold pressure must be taken at the port marked OUT P.
2. The gas line pressure must be taken at the port marked IN P.
3. Using a 3/32 in. (2.4 mm) hex head wrench, loosen the set screw

by  turning  it  one  turn counter  clockwise.  DO  NOT REMOVE THE
SET SCREW FROM THE PRESSURE PORT.

Read the inlet gas pressure

Connect the positive side of the manometer to the IN P tap on the gas
valve. Do not connect any tubing to the negative side of the manometer,
because it references atmospheric pressure. See Figures 30 and 31 for
connection details.
1. Turn on gas and electrical supplies and follow the operating instruc-

tions to place the unit back in operation.

2. Once  the  correct  gas  inlet  pressure  has  been  established  (see

Table 13), turn the gas valve to OFF and turn the electrical supply
switch to OFF. Remove the flexible tubing from the gas valve pres-
sure tap and tighten the pressure tap plug using the 3/32 in. (2.4
mm) hex head wrench.

3. Turn  on  the  electrical  and  gas  supplies,  and  with  the  burners  in

operation,  check  for  gas  leakage  around  the  gas  valve  pressure
port  using  an  approved  non-corrosive  gas  leak  detection  fluid  or
other non-flammable leak detection methods.

Read the manifold gas pressure

Connect the positive side of the manometer to the OUT P tap on the
gas  valve.  Do  not  connect  any  tubing  to  the  negative  side  of  the
manometer, because it references atmospheric pressure. See Figures
30 and 31 for connection details.

1. See Figure 30 for location of pressure regulator adjustment cap and

adjustment screws on main gas valve.

2. Turn on gas and electrical supplies and follow the operating instruc-

tions to place the unit back in operation.

3. Adjust manifold pressure by adjusting gas valve regulator screw for

the appropriate gas per the following:

4. After the manifold pressure has been adjusted, re-calculate the fur-

nace input to make sure you have not exceeded the specified input
on the rating plate. See the CALCULATING THE FURNACE INPUT
section.

5. Once  the  correct  BTU  (kW)  input  has  been  established,  turn  the

gas  valve  to  OFF  and  turn  the  electrical  supply  switch  to  OFF.
Remove  the  flexible  tubing  from  the  gas  valve  pressure  tap  and
tighten the pressure tap plug using the 3/32 in. (2.4 mm) hex head
wrench.

6. Turn  on  the  electrical  and  gas  supplies,  and  with  the  burners  in

operation,  check  for  gas  leakage  around  the  gas  valve  pressure
port  using  an  approved  non-corrosive  gas  leak  detection  fluid  or
other non-flammable leak detection methods.

Table 13: 

Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Natural Gas

Minimum*

4.5 in. W.C. (1.12 kPa)

Maximum

10.5 in. W.C. (2.61 kPa)

IMPORTANT:  

The inlet gas pressure operating range table specifies

what the minimum and maximum gas line pressures must be for the
furnace to operate correctly. The gas line pressure 

MUST BE

 a mini-

mum of:

• 7 in. W.C. (1.74 kPA)

This is in order to obtain the BTU input specified on the rating plate
and/or the nominal manifold pressure specified in these instructions
and on the rating plate.

IMPORTANT:  

The cap for the pressure regulator must be removed

entirely to gain access to the adjustment screw. Loosening or tighten-
ing the cap does not adjust the flow of gas.

Table 14: 

Nominal Manifold Pressure

NOMINAL MANIFOLD PRESSURE

Natural Gas

3.5 in. W.C. (0.87 kPa)

 Figure 30: 

Gas Valve

IMPORTANT:  

If gas valve regulator is turned in (clockwise), manifold

pressure increases. If screw is turned out (counterclockwise), mani-
fold pressure decreases.

MANIFOLD PRESSURE U TUBE CONNECTION

 Figure 31: 

Reading Gas Pressure

INLET

WRENCH
BOSS

INLET
PRESSURE
PORT

ON

OFF

ON/OFF SWITCH
(Shown in ON position)

MAIN REGULATOR
ADJUSTMENT

OUTLET

OUTLET
PRESSURE
PORT

VENT PORT

BURNER

BURNER

¼" TUBING

3.5" W.C.
GAS
PRESSURE
SHOWN

GAS
VALVE

MANIFOLD
PRESSURE TAP

INLET
PRESSURE TAP

A1132-001

Содержание TL9E Series

Страница 1: ...Wiring Diagram 32 LIST OF TABLES Unit Clearances to Combustibles 4 Cabinet and Duct Dimensions 6 Recommended Filter Sizes High Velocity 600 FPM 7 Ratings and Physical Electrical Data 8 Maximum Equival...

Страница 2: ...alled directly on carpeting tile or other combustible material other than wood flooring Check the rating plate and power supply to be sure that the elec trical characteristics match All models use nom...

Страница 3: ...t piping and elbows are required As centralized with the air distribution as possible Where adequate combustion air is available particularly when the appliance is not using outdoor combustion air Whe...

Страница 4: ...be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct such that smoke or reflected light would be observable...

Страница 5: ...ION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The line contact is only permissible between lines that are formed by the inters...

Страница 6: ...t and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joists See Figure 5 for details and...

Страница 7: ...p leg and ground union is required See Figure 10 For left side supply gas pipe arrangement two 1 2 in elbows and two 1 2 in x 1 1 2 in pipe nipples must be used The arrangement shown in Figure 9 align...

Страница 8: ...with DOE test procedures Wire size and overcurrent protection must comply with the National Electrical Code NFPA 70 latest edition and all local codes The furnace must be installed so the electrical...

Страница 9: ...Figure 11 LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the m...

Страница 10: ...1 67 LU RQGLWLRQHU 9ROW RPPRQ RPSUHVVRU RQWDFWRU XOO 6WDJH HDW 7 50267 7 Figure 13 Thermostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJ...

Страница 11: ...pplied to the hose con nected to the top of the condensate trap Screw the condensate trap to the condensate trap bracket supplied Then thread the hose adapters together below the furnace casing using...

Страница 12: ...collec tor box as shown in Figures 16 and 17 The drain hose must not sag or droop after it is installed If glue is used when connecting the intake pipe to the intake coupling the drain opening in the...

Страница 13: ...5894307 UIM B 0920 Johnson Controls Ducted Systems 13 Figure 16 Upflow Configuration UPFLOW LEFT SIDE DRAIN UPFLOW RIGHT SIDE DRAIN EXTERNAL CONDENSATE TRAP EXTERNAL CONDENSATE TRAP A1128 001...

Страница 14: ...DRAIN AIRFLOW EXTERNAL CONDENSATE TRAP HORIZONTAL LEFT HORIZONTAL RIGHT MOVE RAIN GUTTER HOSE TO THIS POSITION MOVE CONDENSATE DRAIN HOSE TO THIS POSITION INTAKE PIPE DRAIN AIRFLOW EXTERNAL CONDENSAT...

Страница 15: ...models are supplied with 2 in 5 1 cm vent connections When the pipe must be increased to 3 in 7 6 cm diameter the transition from 2 in to 3 in must be done as close to the furnace as possible The 2 i...

Страница 16: ...igure 18 Elbow Dimensions A A A A STANDARD ELBOW LONG SWEEP ELBOW Table 6 Elbow Dimensions Elbow A Dimension Illustrated in Figure 18 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 i...

Страница 17: ...nform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight and watertight seal 8 Install the combustion air and vent piping such that it has a 1 4 in ft 21...

Страница 18: ...equirements of the gas supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with...

Страница 19: ...3 to 24 Each furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 23 and 24 can...

Страница 20: ...tion See Figure 28 VENTILATED COMBUSTION AIR Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated att...

Страница 21: ...operated damper or manually adjustable louvers are not permitted for use An automatically operated damper or automatically adjustable louvers must be interlocked so the main burner can not operate un...

Страница 22: ...kW of the total input rating of all equipment located in the enclosure Not less than the sum of all vent connectors in the confined space The duct must be least the same cross sectional area as the fr...

Страница 23: ...s dryers and TURN ON any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Open the fireplace dampers Do not operate a summer exhaust fan 4 Follow the light...

Страница 24: ...surface igniter glows for about 17 s b After this warm up the induced draft blower starts again and the ignition module opens the main gas valve c After flame is established the supply air blower sta...

Страница 25: ...0 300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 23...

Страница 26: ...ws on main gas valve 2 Turn on gas and electrical supplies and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw...

Страница 27: ...gas sample for analysis it is permissi ble to drill a small hole in the plastic flue pipe for a sample probe pro vided that the vent piping is PVC and the hole is correctly sealed afterwards If using...

Страница 28: ...ated on the furnace vesti bule panel near the gas valve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by the following A dirty...

Страница 29: ...sensed within 1 0 s The gas valve de energizes and the control begins a recycle operation A normal ignition sequence begins after a 15 s inter purge If during the five recycles the gas supply does not...

Страница 30: ...d Red Flashes Indicates incorrect line voltage polarity The polar ity of the incoming power to the furnace is reversed Soft Lockout The control includes a soft lockout that resets automati cally after...

Страница 31: ...Door 1 5 ft required GROMMET 3 required HARNESS WIRING HOSE CONDENSATE HOSE RAIN GUTTER KNOB QUARTER TURN 4 required MOTOR MOUNT ORIFICE BURNER PAN CONDENSATE PLUG SEAL 7 8 in PLUG SEAL 2 3 8 in PLUG...

Страница 32: ...5894307 UIM B 0920 32 Johnson Controls Ducted Systems SECTION XII WIRING DIAGRAM Figure 33 Wiring Diagram...

Страница 33: ...ree Ells of 90 Degree Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control b...

Страница 34: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Отзывы: