1.

Remove the burner assembly as outlined in BURNER
INSTRUCTIONS.

2.

Remove the roof over the gas heat section.

3.

At the top plate from the top draft blower housing and the
top draft blower wheel.

4.

Remove the screws holding the top of the flue collector
box. Carefully remove the top of the flue collector box
without ripping the adjacent insulation. Then remove the
center divider plate separating the upper and lower flue
boxes.

5.

On the inside of the flue collector box, remove the flue
baffles from the tube interiors. Note the last bend of the
baffle fits tightly against the tube forcing the end of the
baffle to lock into the tube collar. This collar is formed
when the tube is expanded into the end sheet. To
remove, move the end of the baffle toward the center of
the tube releasing the end of the baffle from the tube col-
lar, then pull straight out of the tube. Refer to Figure 20.

6.

Using a wire brush on a flexible wand, brush out the
inside of each heat exchanger from the burner inlet and
flue outlet ends.

7.

Brush out the inside of the flue collector box and the flue
baffles.

8.

Run the wire brush down the vent hoods from the flue
collector end.

9.

If soot build-up is particularly bad, remove the vent motor
and clean the wheel and housings. Run the wire brush
down the flue extensions at the outlet of the vent hous-
ings.

10. After brushing is complete, blow all brushed areas with

air or nitrogen. Vacuum as needed.

11. Replace parts in the order they were removed in Steps 1

through 4.

12. When replacing the center and top of the flue collector

box, be careful not to tear the adjoining insulation.

13. Ensure that all seams on the vent side of the combustion

system are air tight. Apply a high temperature (+500°F)
sealing compound where needed.

TROUBLESHOOTING

NOTE: To find the Btu input, multiply the number of cubic feet
of gas consumed per hour by the Btu content of the gas in
your particular locality (contact your gas company for this
information - it varies widely from city to city.)

FIGURE 21 : TYPICAL FLUE BAFFLE INSTALLA-

TION

Troubleshooting

of

components

necessarily

requires opening the electrical control box with the
power connected to the unit. Use extreme care
when working with live circuits! Check the unit
nameplate for the correct line voltage and set the
volt meter to the correct range before making any
connections with line terminals.

Prior to any of the following maintenance proce-
dures, shut off all electric power to the unit to pre-
vent personal injury.

Label all wires prior to disconnection when servic-
ing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.

Содержание SUNLINE DHG 180

Страница 1: ...ATION 19 MAINTENANCE 25 COMPLETE TABLE OF CONTENTS ON FOLLOWING PAGE INSTALLATION INSTRUCTION SAVE THIS MANUAL SUNLINE GAS ELECTRIC SINGLE PACKAGE AIR CONDITIONERS 035 17233 000 C 0702 MODELS DHG180 1...

Страница 2: ...PLY AIR CFM 23 ADJUSTMENT OF TEMPERATURE RISE 24 BELT DRIVE BLOWER 24 CHECKING GAS INPUT 24 NATURAL GAS 24 SECURE OWNER S APPROVAL 24 MAINTENANCE 25 NORMAL MAINTENANCE 25 FILTERS 25 MOTORS 25 OUTDOOR...

Страница 3: ...equipment Observe all precautions in the literature on labels and tags accompanying the equipment whenever working on air condi tioning equipment Be sure to follow all other safety precau tions that...

Страница 4: ...hese units must be installed in accordance with the follow ing national and local safety codes 1 National Electrical Code ANSI NFPA No 70 2 National Fuel Gas Code Z223 1 3 Gas Fired Central Furnace St...

Страница 5: ...so be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used Refer to Table 6 for unit weights and to Figure 2 for approxi mate center of gravity CLEARANC...

Страница 6: ...to installing the hood Extend gasketing 1 4 beyond the top and bottom of the two side flanges to insure adequate sealing Adjusting the damper to the desired air flow may be done before mounting the h...

Страница 7: ...ions enclosed with thermostat for general installation procedure Seven color coded insulated wires 18 AWG should be used to connect thermostat to unit POWER AND CONTROL WIRING Field wiring to the unit...

Страница 8: ...ght iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only 4 All piping should be cleaned of dirt and scale by ham mering on the outside of the pipe and blowin...

Страница 9: ...m i z e r d a m p e r s w h e n t h e t h e r m o s t a t s w i t c h e s t o t h e s e t b a c k p o s i t i o n N O T E F a n s s w i t c h m u s t b e i n O N p o s i t i o n f o r m i n i m u m v...

Страница 10: ...ding tank sizing for vaporization recommended regulator settings and pipe sizing is available from most regulator manufacturers and L P propane gas suppliers L P propane gas is an excellent solvent an...

Страница 11: ...o not remove the two panel latches 1 The enthalpy set point may now be set by selecting the desired setpoint shown in Figure 9 Adjust as follows For a single enthalpy operation carefully turn the set...

Страница 12: ...035 17233 000 C 0702 12 Unitary Products FIGURE 9 ENTHALPY SETPOINT ADJUSTMENT...

Страница 13: ...518 506 1 Utilization Range A in accordance with ARI Standard 110 TABLE 8 MINIMUM CLEARANCES LOCATION CLEARANCE Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Econ...

Страница 14: ...1 2 33 35 5 7 8 46 5 8 7 1 8 6 3 8 VENT AIR OUTLET HOODS COMBUSTION AIR INLET HOOD GAS HEAT ACCESS C GAS SUPPLY ENTRY 46 5 8 11 1 8 D GAS SUPPLY ENTRY RETURN AIR SUPPLY AIR OUTDOOR AIR OUTDOOR AIR Eco...

Страница 15: ...includes a power exhaust option The cov ering consists of a heavy black paper composition 3 Replace the side supply and return air compartment pan els For side duct applications 1 Replace the side pan...

Страница 16: ...1 3 9 3 5 1 9 4 7 4 2 1 6 5 5 4 9 230 460 VOLT AND STANDARD DRIVE 870 6 04 1 0 2 5 2 2 0 7 3 0 2 7 0 4 3 5 3 1 915 5 0 1 1 2 6 2 4 0 8 3 1 2 8 0 5 3 6 3 2 0 2 4 1 3 7 965 4 0 1 2 2 7 2 5 0 9 3 2 2 9...

Страница 17: ...7 4 3 3 7 0 2 5 1 4 3 900 5 0 1 4 3 8 3 2 0 9 4 7 4 0 0 4 5 6 4 7 930 4 0 1 6 4 1 3 4 1 1 5 0 4 2 0 6 5 9 5 0 0 1 6 7 5 7 950 3 5 1 7 4 2 3 6 1 3 5 1 4 3 0 8 6 0 5 1 0 2 6 9 5 8 965 2 5 1 9 4 5 3 8 1...

Страница 18: ...3700 0 74 3000 0 78 1 Power exhaust motor is a 3 4 HP PSC type with sleeve bearings a 48 frame and inherent protection 2 The factory setting TABLE 15 BLOWER MOTOR AND DRIVE DATA MODEL SIZE DRIVE BLWR...

Страница 19: ...Y1 energizes the economizer The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energ...

Страница 20: ...l 24V power is removed from the module either at the unit or by resetting the room thermostat At the same time power was supplied to the RW1 a parallel circuit activates ETD which closes the ETD conta...

Страница 21: ...exchanger compartment and is set to open at 190F It is a manual reset switch If AUX limit trips then the primary limit has not functioned correctly Replace the primary limit switch HEAT ANTICIPATOR S...

Страница 22: ...minals 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure turn the adjusting screw clockwise NOTE The correct manifold pressure for these furnaces...

Страница 23: ...holes for sufficient penetration into the air flow on both sides of the indoor coil NOTE The tubes must be inserted and held in a position per pendicular to the air flow so that velocity pressure wil...

Страница 24: ...size of the test dial increment find the cubic feet of gas consumed per hour from Table 18 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible rang...

Страница 25: ...o show at the seals Do not over lubricate Use any lithium base grease recommended for ball bearing service OUTDOOR COIL Dirt should not be allowed to accumulate on the outdoor coil surface or other pa...

Страница 26: ...the vent motor and clean the wheel and housings Run the wire brush down the flue extensions at the outlet of the vent hous ings 10 After brushing is complete blow all brushed areas with air or nitrog...

Страница 27: ...back to the relay board Check control wiring to the room thermostat If all is fine replace the relay board f If the blower motor runs with the fan switch in the ON position but does not run soon after...

Страница 28: ...wiring between the ignitor control and the gas valve Check to make sure the ground connec tions are intact c If the wiring is intact check for 24 volts across termi nals PV and COMMON on the ignitor...

Отзывы: