Check all connections for leaks when piping is completed,
using a soap solution. NEVER USE A FLAME.

VENT AND COMBUSTION AIR HOODS

Two vent hoods and a combustion air hood (with screens) are
shipped attached to the blower housing in the blower com-
partment. These hoods must be installed to assure proper
unit function. All hoods must be fastened to the outside of the
gas heat access panel with the screws provided in the bag
also attached to the blower housing.

The screen for the combustion air intake hood is secured as
shown on the label attached to the hood. The top flange of
this hood slips in under the top of the access panel opening
when installing. Refer to Figure 8.

Each vent hood is installed by inserting the top flange of the
hood into the slotted opening in the access panel and secur-
ing in place.

OPTIONAL ECONOMIZER/MOTORIZED DAMPER
RAIN HOOD

The

instruction

for

the

optional

economizer/motorized

damper rain hood can be found in form 44-320-2. Use these
instructions when field assembling an economizer rain hood
onto a unit.

The outdoor and return air dampers, the damper actuator, the
damper linkage, the outdoor and return air divider baffles,
and all the control sensors are factory mounted as part of the
Factory installed economizer option.

ENTHALPY SET POINT ADJUSTMENT

Remove the economizer access panel from the unit to check
the following adjustments. Loosen but do not remove the two

panel latches.

1.

The enthalpy set point may now be set by selecting the
desired setpoint shown in Figure 9. Adjust as follows:

For a single enthalpy operation, carefully turn the set
point adjusting screw to the A, B, C or D setting corre-
sponding to the lettered curve.

For a dual enthalpy operation, carefully turn the set point
adjusting screw fully clockwise past the D setting.

2.

To check that the damper blades move smoothly without
binding, carefully turn the minimum position adjusting
screw fully clockwise and then energize and de-energize
terminals R to G. With terminals R to G energized, turn
the minimum position screw counterclockwise until the
desired minimum position has been attained.

3.

Replace the economizer access panel. Reposition the
two latches horizontally and retighten the screws.

POWER EXHAUST/BAROMETRIC RELIEF DAMPER
AND RAIN HOOD OPTION

The instructions for the power exhaust/barometric relief
damper and rain hood can be found in form 44-320-10. The
exhaust fan, all supporting brackets, angles, and the wiring
are factory installed as part of the power exhaust option.

All of the components, including the dampers, hardware, and
mounting instructions are shipped in a single package exter-
nal from the unit. The hood must be field assembled and
installed.

Power exhaust is not available as a field installed option.

FIGURE 8 : VENT AND COMBUSTION AIR

HOODS

VENT AIR
OUTLET
HOODS

SLOTTED
OPENINGS IN 
ACCESS PANEL

COMBUSTION
AIR INTAKE
HOOD

GAS HEAT
ACCESS
PANELS

Extreme care must be exercised in turning both
the setpoint and minimum position adjusting
screws to prevent twisting them off.

Содержание SUNLINE DHG 180

Страница 1: ...ATION 19 MAINTENANCE 25 COMPLETE TABLE OF CONTENTS ON FOLLOWING PAGE INSTALLATION INSTRUCTION SAVE THIS MANUAL SUNLINE GAS ELECTRIC SINGLE PACKAGE AIR CONDITIONERS 035 17233 000 C 0702 MODELS DHG180 1...

Страница 2: ...PLY AIR CFM 23 ADJUSTMENT OF TEMPERATURE RISE 24 BELT DRIVE BLOWER 24 CHECKING GAS INPUT 24 NATURAL GAS 24 SECURE OWNER S APPROVAL 24 MAINTENANCE 25 NORMAL MAINTENANCE 25 FILTERS 25 MOTORS 25 OUTDOOR...

Страница 3: ...equipment Observe all precautions in the literature on labels and tags accompanying the equipment whenever working on air condi tioning equipment Be sure to follow all other safety precau tions that...

Страница 4: ...hese units must be installed in accordance with the follow ing national and local safety codes 1 National Electrical Code ANSI NFPA No 70 2 National Fuel Gas Code Z223 1 3 Gas Fired Central Furnace St...

Страница 5: ...so be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used Refer to Table 6 for unit weights and to Figure 2 for approxi mate center of gravity CLEARANC...

Страница 6: ...to installing the hood Extend gasketing 1 4 beyond the top and bottom of the two side flanges to insure adequate sealing Adjusting the damper to the desired air flow may be done before mounting the h...

Страница 7: ...ions enclosed with thermostat for general installation procedure Seven color coded insulated wires 18 AWG should be used to connect thermostat to unit POWER AND CONTROL WIRING Field wiring to the unit...

Страница 8: ...ght iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only 4 All piping should be cleaned of dirt and scale by ham mering on the outside of the pipe and blowin...

Страница 9: ...m i z e r d a m p e r s w h e n t h e t h e r m o s t a t s w i t c h e s t o t h e s e t b a c k p o s i t i o n N O T E F a n s s w i t c h m u s t b e i n O N p o s i t i o n f o r m i n i m u m v...

Страница 10: ...ding tank sizing for vaporization recommended regulator settings and pipe sizing is available from most regulator manufacturers and L P propane gas suppliers L P propane gas is an excellent solvent an...

Страница 11: ...o not remove the two panel latches 1 The enthalpy set point may now be set by selecting the desired setpoint shown in Figure 9 Adjust as follows For a single enthalpy operation carefully turn the set...

Страница 12: ...035 17233 000 C 0702 12 Unitary Products FIGURE 9 ENTHALPY SETPOINT ADJUSTMENT...

Страница 13: ...518 506 1 Utilization Range A in accordance with ARI Standard 110 TABLE 8 MINIMUM CLEARANCES LOCATION CLEARANCE Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Econ...

Страница 14: ...1 2 33 35 5 7 8 46 5 8 7 1 8 6 3 8 VENT AIR OUTLET HOODS COMBUSTION AIR INLET HOOD GAS HEAT ACCESS C GAS SUPPLY ENTRY 46 5 8 11 1 8 D GAS SUPPLY ENTRY RETURN AIR SUPPLY AIR OUTDOOR AIR OUTDOOR AIR Eco...

Страница 15: ...includes a power exhaust option The cov ering consists of a heavy black paper composition 3 Replace the side supply and return air compartment pan els For side duct applications 1 Replace the side pan...

Страница 16: ...1 3 9 3 5 1 9 4 7 4 2 1 6 5 5 4 9 230 460 VOLT AND STANDARD DRIVE 870 6 04 1 0 2 5 2 2 0 7 3 0 2 7 0 4 3 5 3 1 915 5 0 1 1 2 6 2 4 0 8 3 1 2 8 0 5 3 6 3 2 0 2 4 1 3 7 965 4 0 1 2 2 7 2 5 0 9 3 2 2 9...

Страница 17: ...7 4 3 3 7 0 2 5 1 4 3 900 5 0 1 4 3 8 3 2 0 9 4 7 4 0 0 4 5 6 4 7 930 4 0 1 6 4 1 3 4 1 1 5 0 4 2 0 6 5 9 5 0 0 1 6 7 5 7 950 3 5 1 7 4 2 3 6 1 3 5 1 4 3 0 8 6 0 5 1 0 2 6 9 5 8 965 2 5 1 9 4 5 3 8 1...

Страница 18: ...3700 0 74 3000 0 78 1 Power exhaust motor is a 3 4 HP PSC type with sleeve bearings a 48 frame and inherent protection 2 The factory setting TABLE 15 BLOWER MOTOR AND DRIVE DATA MODEL SIZE DRIVE BLWR...

Страница 19: ...Y1 energizes the economizer The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energ...

Страница 20: ...l 24V power is removed from the module either at the unit or by resetting the room thermostat At the same time power was supplied to the RW1 a parallel circuit activates ETD which closes the ETD conta...

Страница 21: ...exchanger compartment and is set to open at 190F It is a manual reset switch If AUX limit trips then the primary limit has not functioned correctly Replace the primary limit switch HEAT ANTICIPATOR S...

Страница 22: ...minals 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure turn the adjusting screw clockwise NOTE The correct manifold pressure for these furnaces...

Страница 23: ...holes for sufficient penetration into the air flow on both sides of the indoor coil NOTE The tubes must be inserted and held in a position per pendicular to the air flow so that velocity pressure wil...

Страница 24: ...size of the test dial increment find the cubic feet of gas consumed per hour from Table 18 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible rang...

Страница 25: ...o show at the seals Do not over lubricate Use any lithium base grease recommended for ball bearing service OUTDOOR COIL Dirt should not be allowed to accumulate on the outdoor coil surface or other pa...

Страница 26: ...the vent motor and clean the wheel and housings Run the wire brush down the flue extensions at the outlet of the vent hous ings 10 After brushing is complete blow all brushed areas with air or nitrog...

Страница 27: ...back to the relay board Check control wiring to the room thermostat If all is fine replace the relay board f If the blower motor runs with the fan switch in the ON position but does not run soon after...

Страница 28: ...wiring between the ignitor control and the gas valve Check to make sure the ground connec tions are intact c If the wiring is intact check for 24 volts across termi nals PV and COMMON on the ignitor...

Отзывы: