York SUNLINE DHG 180 Скачать руководство пользователя страница 25

035-17233-000-C-0702

Unitary Products

25

MAINTENANCE

NORMAL MAINTENANCE

Periodic maintenance normally consists of changing or clean-
ing filters and (under some conditions) cleaning the main
burners

FILTERS

Inspect once a month. Replace disposable or clean perma-
nent type as necessary. DO NOT replace permanent type
with disposable. The dimensional size of the replacement fil-
ter must be the same as the replaced filter.

MOTORS

Outdoor fan motors are permanently lubricated and require
no maintenance.

Ventor motor is factory lubricated for an estimated 10 year
life.

Indoor Blower Motor and Drive - The indoor blower motor fea-
tures ball bearings that do not require periodic lubrication.
Periodic lubrication of the motor and bearings can extend the

life of components but is optional.

On an annual basis, check the motor for accumulations of
dust, etc. that may block the cooling slots in the motor shell.
Check for loose, damaged or misaligned drive components.
Check that all mounting bolts are tight. Replace defective
parts as required.

If desired, every three years remove both pipe plugs at each
end shell and clean out any hardened grease or foreign mat-
ter. Replace one plug on each end with a clean grease fitting.
Using a low pressure grease gun, pump grease (Chevron
SRI-2 or equivalent) into the bearing cavity until new grease
shows at the open port. Do not over lubricate. Run the motor
for ten minutes until excess grease is purged from the cavity.
Replace the plugs.

On 20 ton only, units are supplied with blower shaft bearings
that do not require maintenance but may be relubricated if
desired. Every three years, using a low pressure grease gun,
pump grease into the bearing grease fitting until grease just
begins to show at the seals. Do not over lubricate. Use any
lithium base grease recommended for ball bearing service.

OUTDOOR COIL

Dirt should not be allowed to accumulate on the outdoor coil
surface or other parts in the air circuit. Cleaning should be as
often as necessary to keep coil clean. Use a brush, vacuum
cleaner attachment, or other suitable means. If water is used
to clean coil, be sure electric power to the unit is shut off prior
to cleaning.

NOTE: Exercise care when cleaning the coil so that the coil
fins are not damaged.

NOTE: Do not permit the hot condenser air discharge to be
obstructed by overhanging structures of shrubs.

BURNER & PILOT

Periodically (at least annually at the beginning of each heat-
ing season) make a visual check of the pilot and main burner
flame. If necessary, adjust main burner primary air shutters to
give a distinct, sharp blue flame as explained under BURNER
AIR SHUTTER ADJUSTMENT. If it is not possible to adjust
for the proper flame, the burners may need cleaning.

TO CLEAN BURNERS

Remove them from the furnace as explained in Burner
Instructions. Clean burners with hot water applied along top
of the burner.

COMBUSTION AIR DISCHARGE

Visually inspect discharge outlet periodically to make sure
that the buildup of soot and dirt is not excessive. If necessary,
clean to maintain adequate combustion air discharge.

CLEANING FLUE PASSAGES AND HEATING ELE-
MENTS

With proper combustion adjustment the heating element of a
gas fired furnace will seldom need cleaning. If the element
should become sooted, it can be cleaned as follows:

Prior to any of the following maintenance proce-
dures, shut off all electric power to the unit to pre-
vent personal injury.

Damage can occur if the bearings are overlubri-
cated. Use grease sparingly.

Perform all maintenance operations on the blower
motor with electric power disconnected from the
unit. Do not attempt to lubricate bearings with the
unit in operation.

Содержание SUNLINE DHG 180

Страница 1: ...ATION 19 MAINTENANCE 25 COMPLETE TABLE OF CONTENTS ON FOLLOWING PAGE INSTALLATION INSTRUCTION SAVE THIS MANUAL SUNLINE GAS ELECTRIC SINGLE PACKAGE AIR CONDITIONERS 035 17233 000 C 0702 MODELS DHG180 1...

Страница 2: ...PLY AIR CFM 23 ADJUSTMENT OF TEMPERATURE RISE 24 BELT DRIVE BLOWER 24 CHECKING GAS INPUT 24 NATURAL GAS 24 SECURE OWNER S APPROVAL 24 MAINTENANCE 25 NORMAL MAINTENANCE 25 FILTERS 25 MOTORS 25 OUTDOOR...

Страница 3: ...equipment Observe all precautions in the literature on labels and tags accompanying the equipment whenever working on air condi tioning equipment Be sure to follow all other safety precau tions that...

Страница 4: ...hese units must be installed in accordance with the follow ing national and local safety codes 1 National Electrical Code ANSI NFPA No 70 2 National Fuel Gas Code Z223 1 3 Gas Fired Central Furnace St...

Страница 5: ...so be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used Refer to Table 6 for unit weights and to Figure 2 for approxi mate center of gravity CLEARANC...

Страница 6: ...to installing the hood Extend gasketing 1 4 beyond the top and bottom of the two side flanges to insure adequate sealing Adjusting the damper to the desired air flow may be done before mounting the h...

Страница 7: ...ions enclosed with thermostat for general installation procedure Seven color coded insulated wires 18 AWG should be used to connect thermostat to unit POWER AND CONTROL WIRING Field wiring to the unit...

Страница 8: ...ght iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only 4 All piping should be cleaned of dirt and scale by ham mering on the outside of the pipe and blowin...

Страница 9: ...m i z e r d a m p e r s w h e n t h e t h e r m o s t a t s w i t c h e s t o t h e s e t b a c k p o s i t i o n N O T E F a n s s w i t c h m u s t b e i n O N p o s i t i o n f o r m i n i m u m v...

Страница 10: ...ding tank sizing for vaporization recommended regulator settings and pipe sizing is available from most regulator manufacturers and L P propane gas suppliers L P propane gas is an excellent solvent an...

Страница 11: ...o not remove the two panel latches 1 The enthalpy set point may now be set by selecting the desired setpoint shown in Figure 9 Adjust as follows For a single enthalpy operation carefully turn the set...

Страница 12: ...035 17233 000 C 0702 12 Unitary Products FIGURE 9 ENTHALPY SETPOINT ADJUSTMENT...

Страница 13: ...518 506 1 Utilization Range A in accordance with ARI Standard 110 TABLE 8 MINIMUM CLEARANCES LOCATION CLEARANCE Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Econ...

Страница 14: ...1 2 33 35 5 7 8 46 5 8 7 1 8 6 3 8 VENT AIR OUTLET HOODS COMBUSTION AIR INLET HOOD GAS HEAT ACCESS C GAS SUPPLY ENTRY 46 5 8 11 1 8 D GAS SUPPLY ENTRY RETURN AIR SUPPLY AIR OUTDOOR AIR OUTDOOR AIR Eco...

Страница 15: ...includes a power exhaust option The cov ering consists of a heavy black paper composition 3 Replace the side supply and return air compartment pan els For side duct applications 1 Replace the side pan...

Страница 16: ...1 3 9 3 5 1 9 4 7 4 2 1 6 5 5 4 9 230 460 VOLT AND STANDARD DRIVE 870 6 04 1 0 2 5 2 2 0 7 3 0 2 7 0 4 3 5 3 1 915 5 0 1 1 2 6 2 4 0 8 3 1 2 8 0 5 3 6 3 2 0 2 4 1 3 7 965 4 0 1 2 2 7 2 5 0 9 3 2 2 9...

Страница 17: ...7 4 3 3 7 0 2 5 1 4 3 900 5 0 1 4 3 8 3 2 0 9 4 7 4 0 0 4 5 6 4 7 930 4 0 1 6 4 1 3 4 1 1 5 0 4 2 0 6 5 9 5 0 0 1 6 7 5 7 950 3 5 1 7 4 2 3 6 1 3 5 1 4 3 0 8 6 0 5 1 0 2 6 9 5 8 965 2 5 1 9 4 5 3 8 1...

Страница 18: ...3700 0 74 3000 0 78 1 Power exhaust motor is a 3 4 HP PSC type with sleeve bearings a 48 frame and inherent protection 2 The factory setting TABLE 15 BLOWER MOTOR AND DRIVE DATA MODEL SIZE DRIVE BLWR...

Страница 19: ...Y1 energizes the economizer The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energ...

Страница 20: ...l 24V power is removed from the module either at the unit or by resetting the room thermostat At the same time power was supplied to the RW1 a parallel circuit activates ETD which closes the ETD conta...

Страница 21: ...exchanger compartment and is set to open at 190F It is a manual reset switch If AUX limit trips then the primary limit has not functioned correctly Replace the primary limit switch HEAT ANTICIPATOR S...

Страница 22: ...minals 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure turn the adjusting screw clockwise NOTE The correct manifold pressure for these furnaces...

Страница 23: ...holes for sufficient penetration into the air flow on both sides of the indoor coil NOTE The tubes must be inserted and held in a position per pendicular to the air flow so that velocity pressure wil...

Страница 24: ...size of the test dial increment find the cubic feet of gas consumed per hour from Table 18 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible rang...

Страница 25: ...o show at the seals Do not over lubricate Use any lithium base grease recommended for ball bearing service OUTDOOR COIL Dirt should not be allowed to accumulate on the outdoor coil surface or other pa...

Страница 26: ...the vent motor and clean the wheel and housings Run the wire brush down the flue extensions at the outlet of the vent hous ings 10 After brushing is complete blow all brushed areas with air or nitrog...

Страница 27: ...back to the relay board Check control wiring to the room thermostat If all is fine replace the relay board f If the blower motor runs with the fan switch in the ON position but does not run soon after...

Страница 28: ...wiring between the ignitor control and the gas valve Check to make sure the ground connec tions are intact c If the wiring is intact check for 24 volts across termi nals PV and COMMON on the ignitor...

Отзывы: