Unitary Products

21

3.

Redundant Gas Valve - There are two separate gas
valves in the furnace. Each valve contains a main and a
redundant valve. The redundant valves are located
upstream of the main gas valves. Should either or both
of the main gas valves fail in the open position the redun-
dant valves serve as back-ups and shuts off the flow of
gas.

4.

Flame Sensor Rod / 100% Ignition Control Lock-Out -
The flame rods and controls are located per Figure 15. If
an ignition control fails to detect a signal from the flame
sensor indicating the pilot flame is properly ignited, then
the main gas valve will not open. It will continue to try
and ignite the pilot for a maximum of 85 seconds, then if
the pilot flame is not detected, the ignition control will
lock out furnace operation until 24V power is removed
from the module either at the unit or by resetting the
room thermostat.

5.

Rollout Switch - This switch is located above the main
burners in the control compartment which in the event of
a sustained main burner rollout shuts off and locks out
both ignition controls closing both gas valves. The igni-
tion controls lock out furnace operation until 24V power
is removed from the controls either at the unit or by
resetting the room thermostat. Note the auto reset rollout
switch must reset before allowing furnace operation.

6.

Auxiliary limit switch (AUX) - This control is located
inside the heat exchanger compartment and is set to
open at 190F. It is a manual reset switch. If AUX limit
trips, then the primary limit has not functioned correctly.
Replace the primary limit switch.

HEAT ANTICIPATOR SETPOINTS

It is important that the anticipator setpoint be correct. Too
high of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter ON cycles
and may result in the lowering of the temperature within the
conditioned space.

START UP

PRE-START CHECK LIST

Complete the following checks before starting the unit.

1.

Check the type of gas being supplied. Be sure that it is
the same as listed on the unit nameplate.

2.

Make sure that the vent and combustion air hoods have
been properly installed.

OPERATING INSTRUCTIONS

TO LIGHT PILOT AND MAIN BURNERS:

1.

Turn off electric power to unit.

2.

Turn room thermostat to lowest setting.

3.

Turn gas valve knob to on position.

4.

Turn on electric power to unit.

FIGURE 15 : GAS VALVE AND CONTROLS

I G N .   C O N T R O L   # 1

I G N .   C O N T R O L   # 2

I G N I T O R   # 1

G V   1

G A S

V A L V E

G V 2

G A S

V A L V E

I G N I T O R   # 2

S E N S O R   # 2

S E N S O R   # 1

R O L L O U T   S W .

B U R N E R   C O M P A R T M E N T

TABLE 16: LIMIT CONTROL SETTING

Units

(Tons)

Capacity, MBH

Limit

Control

Opens, °F

Input

Output

15 & 20

300

240

195

15 & 20

400

320

195

TABLE 17: HEAT ANTICIPATOR SETPOINT

Gas Valve

1st Stage

2nd Stage

Honeywell VR8440

0.30 amp

0.11 amp

White-Rodgers 36C68

This furnace is equipped with an intermittent pilot
and automatic re-ignition system. DO NOT attempt
to manually light the pilot.

Содержание SUNLINE DHG 180

Страница 1: ...ATION 19 MAINTENANCE 25 COMPLETE TABLE OF CONTENTS ON FOLLOWING PAGE INSTALLATION INSTRUCTION SAVE THIS MANUAL SUNLINE GAS ELECTRIC SINGLE PACKAGE AIR CONDITIONERS 035 17233 000 C 0702 MODELS DHG180 1...

Страница 2: ...PLY AIR CFM 23 ADJUSTMENT OF TEMPERATURE RISE 24 BELT DRIVE BLOWER 24 CHECKING GAS INPUT 24 NATURAL GAS 24 SECURE OWNER S APPROVAL 24 MAINTENANCE 25 NORMAL MAINTENANCE 25 FILTERS 25 MOTORS 25 OUTDOOR...

Страница 3: ...equipment Observe all precautions in the literature on labels and tags accompanying the equipment whenever working on air condi tioning equipment Be sure to follow all other safety precau tions that...

Страница 4: ...hese units must be installed in accordance with the follow ing national and local safety codes 1 National Electrical Code ANSI NFPA No 70 2 National Fuel Gas Code Z223 1 3 Gas Fired Central Furnace St...

Страница 5: ...so be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used Refer to Table 6 for unit weights and to Figure 2 for approxi mate center of gravity CLEARANC...

Страница 6: ...to installing the hood Extend gasketing 1 4 beyond the top and bottom of the two side flanges to insure adequate sealing Adjusting the damper to the desired air flow may be done before mounting the h...

Страница 7: ...ions enclosed with thermostat for general installation procedure Seven color coded insulated wires 18 AWG should be used to connect thermostat to unit POWER AND CONTROL WIRING Field wiring to the unit...

Страница 8: ...ght iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only 4 All piping should be cleaned of dirt and scale by ham mering on the outside of the pipe and blowin...

Страница 9: ...m i z e r d a m p e r s w h e n t h e t h e r m o s t a t s w i t c h e s t o t h e s e t b a c k p o s i t i o n N O T E F a n s s w i t c h m u s t b e i n O N p o s i t i o n f o r m i n i m u m v...

Страница 10: ...ding tank sizing for vaporization recommended regulator settings and pipe sizing is available from most regulator manufacturers and L P propane gas suppliers L P propane gas is an excellent solvent an...

Страница 11: ...o not remove the two panel latches 1 The enthalpy set point may now be set by selecting the desired setpoint shown in Figure 9 Adjust as follows For a single enthalpy operation carefully turn the set...

Страница 12: ...035 17233 000 C 0702 12 Unitary Products FIGURE 9 ENTHALPY SETPOINT ADJUSTMENT...

Страница 13: ...518 506 1 Utilization Range A in accordance with ARI Standard 110 TABLE 8 MINIMUM CLEARANCES LOCATION CLEARANCE Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Econ...

Страница 14: ...1 2 33 35 5 7 8 46 5 8 7 1 8 6 3 8 VENT AIR OUTLET HOODS COMBUSTION AIR INLET HOOD GAS HEAT ACCESS C GAS SUPPLY ENTRY 46 5 8 11 1 8 D GAS SUPPLY ENTRY RETURN AIR SUPPLY AIR OUTDOOR AIR OUTDOOR AIR Eco...

Страница 15: ...includes a power exhaust option The cov ering consists of a heavy black paper composition 3 Replace the side supply and return air compartment pan els For side duct applications 1 Replace the side pan...

Страница 16: ...1 3 9 3 5 1 9 4 7 4 2 1 6 5 5 4 9 230 460 VOLT AND STANDARD DRIVE 870 6 04 1 0 2 5 2 2 0 7 3 0 2 7 0 4 3 5 3 1 915 5 0 1 1 2 6 2 4 0 8 3 1 2 8 0 5 3 6 3 2 0 2 4 1 3 7 965 4 0 1 2 2 7 2 5 0 9 3 2 2 9...

Страница 17: ...7 4 3 3 7 0 2 5 1 4 3 900 5 0 1 4 3 8 3 2 0 9 4 7 4 0 0 4 5 6 4 7 930 4 0 1 6 4 1 3 4 1 1 5 0 4 2 0 6 5 9 5 0 0 1 6 7 5 7 950 3 5 1 7 4 2 3 6 1 3 5 1 4 3 0 8 6 0 5 1 0 2 6 9 5 8 965 2 5 1 9 4 5 3 8 1...

Страница 18: ...3700 0 74 3000 0 78 1 Power exhaust motor is a 3 4 HP PSC type with sleeve bearings a 48 frame and inherent protection 2 The factory setting TABLE 15 BLOWER MOTOR AND DRIVE DATA MODEL SIZE DRIVE BLWR...

Страница 19: ...Y1 energizes the economizer The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energ...

Страница 20: ...l 24V power is removed from the module either at the unit or by resetting the room thermostat At the same time power was supplied to the RW1 a parallel circuit activates ETD which closes the ETD conta...

Страница 21: ...exchanger compartment and is set to open at 190F It is a manual reset switch If AUX limit trips then the primary limit has not functioned correctly Replace the primary limit switch HEAT ANTICIPATOR S...

Страница 22: ...minals 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure turn the adjusting screw clockwise NOTE The correct manifold pressure for these furnaces...

Страница 23: ...holes for sufficient penetration into the air flow on both sides of the indoor coil NOTE The tubes must be inserted and held in a position per pendicular to the air flow so that velocity pressure wil...

Страница 24: ...size of the test dial increment find the cubic feet of gas consumed per hour from Table 18 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible rang...

Страница 25: ...o show at the seals Do not over lubricate Use any lithium base grease recommended for ball bearing service OUTDOOR COIL Dirt should not be allowed to accumulate on the outdoor coil surface or other pa...

Страница 26: ...the vent motor and clean the wheel and housings Run the wire brush down the flue extensions at the outlet of the vent hous ings 10 After brushing is complete blow all brushed areas with air or nitrog...

Страница 27: ...back to the relay board Check control wiring to the room thermostat If all is fine replace the relay board f If the blower motor runs with the fan switch in the ON position but does not run soon after...

Страница 28: ...wiring between the ignitor control and the gas valve Check to make sure the ground connec tions are intact c If the wiring is intact check for 24 volts across termi nals PV and COMMON on the ignitor...

Отзывы: