background image

Unitary Products Group

3

550.39-TG5YI

STEAM COIL CAPACITY

1

,kW @ 14 kPa/Mbh @ 2 psig

2

Steam Coil Model

Blower Model

Used On

m

3

/s / CFM

Dry Bulb Temperature of Air Entering Coil, °C/°F

-12 / 10

-1 / 30

10 / 50

21 / 70

1NF0452

KEU180

2.3 / 4800

298.2 / 1018

268.4 / 916

236.7 / 808

211.5 / 722

2.8 / 6000

329.1 / 1124

297.0 / 1014

265.6 / 907

234.1 / 799

3.4 / 7200

356.4 / 1216

321.8 / 1099

287.9 / 983

254.0 / 867

1

These capacities do not include any blower motor heat.

2

Multiply these capacities by the following factors to correct for higher steam pressures

Steam pressure, kPa/psig

35 / 5

70 / 10

105 / 15

140 / 20

210 / 30

Capacity correction factor

1.06

1.12

1.19

1.25

1.30

NOTE: Steam rate (kg/hr) = 0.66 x kW

(lb/hr) = 1.025xMbh

CAUTION: Do not operate a motor above its nominal HP rating when a unit is equipped

with a steam coil accessory

Water Coil

Model

Blower Model

Used On

l/s / GPM

m

3

/s / CFM

Entering Water Temperature Minus Entering Air Temperature, °C/°F

21 / 70

32 / 90

43 / 110

54 / 130

66 / 150

1HW0451

KEU180

0.95 / 15

2.3 / 4800

135.5 / 463

175.1 / 598

215.8 / 737

257.4 / 879

294.1 / 1004

2.8 / 6000

150.0 / 512

195.0 / 666

240.3 / 820

285.9 / 976

326.6 / 1115

3.4 / 7200

162.4 / 554

210.8 / 720

260.4 / 889

309.8 / 1058

354.3 / 1210

1

These capacities do not include any blower motor heat.

NOTE: Water Temperature Drop, °C =

16 71

.

/

x

kW
l s

°F =

2 x

Mbh

GPM

CAUTION: Do NOT operate a motor above its nominal HP rating when a unit is equipped with a hot water coil accessory.

HOT WATER COIL CAPACITY

1

, kW/Mbh

1HW0450

l/s / GPM

0.63 / 10 /

1.26 / 20

1.90 / 30

Pressure Drop,

kPa / psig/

0.7 / 0.10

2.2 / 0.32

4.7 / 0.67

1HW0451

l/s / GPM

0.95 / 15

1.90 / 30

2.83 / 45

Pressure Drop,

kPa / psig

1.2 / 0.17

4.0 / 0.58

8.5 / 1.22

Meters (H

2

O) = 45,942 x kPa

Feet (H

2

O) = 2031 x psi

PRESSURE DROP VS L/S / GPM

1HW0450

l/s / GPM

1.26 / 20

1.90 / 30

Capacity

Correction

1.12

1.15

1HW0451

GPM

1.90 / 30

2.83 / 45

Capacity

Correction

1.11

1.15

CAPACITY CORRECTION VS
L/S / GPM

Содержание SUNLINE 2000 KEU180

Страница 1: ...can be selected to precisely match the cooling and heating requirements of the conditioned space These heaters are designed for easy field installation over the supply air opening of the unit Every he...

Страница 2: ...Air Grille and Base accessories can be applied on arrangement b The Supply Air Plenum Return Air Grille and Suspension accessories can be applied on arrangement c Heater Model UL Test Voltage Nominal...

Страница 3: ...ower Model Used On l s GPM m3 s CFM Entering Water Temperature Minus Entering Air Temperature C F 21 70 32 90 43 110 54 130 66 150 1HW0451 KEU180 0 95 15 2 3 4800 135 5 463 175 1 598 215 8 737 257 4 8...

Страница 4: ...SP2 IWG OUTPUT BHP INPUT kW ESP2 IWG OUTPUT BHP INPUT kW 4800 CFM 5400 CFM 6000 CFM 6600 CFM 7200 CFM 600 0 46 1 44 1 34 0 30 1 68 1 56 0 11 1 96 1 80 615 0 55 1 54 1 43 0 40 1 79 1 64 0 22 2 08 1 90...

Страница 5: ...04 0 05 0 06 0 07 Return Air Grille 0 04 0 05 0 06 0 07 0 08 Hot Water Coil 0 18 0 22 0 26 0 03 0 34 Steam Coil 0 15 0 18 0 22 0 26 0 30 Static resistance pascal Unit Model Accessory m3 s 2 26 2 55 2...

Страница 6: ...rtical Louvers1 0 Spread Horizontal Louvers2 Vertical Louvers1 221 2 Spread Horizontal Louvers2 Vertical Louvers1 45 Spread Horizontal Louvers2 Throw Meters 3 Spread Meters 3 0 18 Throw Meters 3 Sprea...

Страница 7: ...lectric Heater 10 kW 37 6 83 16 kW 29 9 66 26 kW 32 2 71 36 kW 33 5 74 Hot Water Coil Tube OD mm inches 1 2 12 7 copper Rows Deep 2 Fins per 25mm 1 in 8 aluminum Face Area square meters square feet 0...

Страница 8: ...ll dimension of the unit will vary if an electric heater a supply air plenum or a base is used 2 This dimension is required for removal of the DX coil Only 660mm 26 in is required for normal servicing...

Страница 9: ...tting on the electric heat accessory Connect the power wiring to the fuse block in the heater control box Route the control wires through the 22 2mm 7 8 in openings and connect them to the ter minals...

Страница 10: ...hrough 0 AWG Accessory Model Nom kW Heater Dimensions mm inches A B C D E F G H K L M 2HS04501050 2HS04501650 2HS04502650 2HS04503650 10 16 26 36 692 271 4 641 251 4 362 141 4 25 1 102 4 13 1 2 140 51...

Страница 11: ...11 550 39 TG5YI TERMINALS ON BLOCK 3TB OF THE BLOWER UNIT TERMINALS ON 1 STAGE COOLING THERMOSTAT 2TH13700424 FIELD WIRING Cooling only CONTROL WIRING Units with steam or hot water coil AC Units with...

Страница 12: ...o change without notice Printed in U S A Copyright by York International Corporation 2001 All Rights Reserved 5005 York Drive 550 39 TG5Y 0601 Supersedes 550 39 TG5Y 0501 Norman OK 73069 Unitary Produ...

Отзывы: