8

Unitary Products Group

550.39-TG5YI

UNIT DIMENSIONS

ACCESSORIES

•ELECTRIC HEATER

Add 381mm (15 in.) to Unit Height when using 10, 16, 26 or 36kW Heater

•SUPPLY AIR PLENUM

Add 686mm (27 in.) to Unit Height when used

•BASE

Add 610mm (24 in.) to Unit Height when used

MINIMUM CLEARANCES (mm/in.)

Side with RETURN AIR opening

- 610 / 24

Side with SUPPLY AIR opening

- 610 / 24

1

Side with PIPING CONNECTIONS

- 1549 / 61

2

Side opposite PIPING CONNECTIONS - 660 / 26

3

Bottom

-

4

1 Overall dimension of the unit will vary if an electric heater, a supply air plenum or a base is used.

2

This dimension is required for removal of the DX coil. Only 660mm (26 in.) is required for normal

servicing.

3

If the DX coil has to be removed, this dimension is required to loosen screws that secure the coil to

the unit frame. This dimension will also be required for blower motor access if the piping
connections are made on the opposite side of the unit.

4

Allow enough clearance to trap the condensate drain line.

All dimensions are in millimeters and inches. They are sub-
ject to change without notice. Certified dimensions will be
provided upon request.

Содержание SUNLINE 2000 KEU180

Страница 1: ...can be selected to precisely match the cooling and heating requirements of the conditioned space These heaters are designed for easy field installation over the supply air opening of the unit Every he...

Страница 2: ...Air Grille and Base accessories can be applied on arrangement b The Supply Air Plenum Return Air Grille and Suspension accessories can be applied on arrangement c Heater Model UL Test Voltage Nominal...

Страница 3: ...ower Model Used On l s GPM m3 s CFM Entering Water Temperature Minus Entering Air Temperature C F 21 70 32 90 43 110 54 130 66 150 1HW0451 KEU180 0 95 15 2 3 4800 135 5 463 175 1 598 215 8 737 257 4 8...

Страница 4: ...SP2 IWG OUTPUT BHP INPUT kW ESP2 IWG OUTPUT BHP INPUT kW 4800 CFM 5400 CFM 6000 CFM 6600 CFM 7200 CFM 600 0 46 1 44 1 34 0 30 1 68 1 56 0 11 1 96 1 80 615 0 55 1 54 1 43 0 40 1 79 1 64 0 22 2 08 1 90...

Страница 5: ...04 0 05 0 06 0 07 Return Air Grille 0 04 0 05 0 06 0 07 0 08 Hot Water Coil 0 18 0 22 0 26 0 03 0 34 Steam Coil 0 15 0 18 0 22 0 26 0 30 Static resistance pascal Unit Model Accessory m3 s 2 26 2 55 2...

Страница 6: ...rtical Louvers1 0 Spread Horizontal Louvers2 Vertical Louvers1 221 2 Spread Horizontal Louvers2 Vertical Louvers1 45 Spread Horizontal Louvers2 Throw Meters 3 Spread Meters 3 0 18 Throw Meters 3 Sprea...

Страница 7: ...lectric Heater 10 kW 37 6 83 16 kW 29 9 66 26 kW 32 2 71 36 kW 33 5 74 Hot Water Coil Tube OD mm inches 1 2 12 7 copper Rows Deep 2 Fins per 25mm 1 in 8 aluminum Face Area square meters square feet 0...

Страница 8: ...ll dimension of the unit will vary if an electric heater a supply air plenum or a base is used 2 This dimension is required for removal of the DX coil Only 660mm 26 in is required for normal servicing...

Страница 9: ...tting on the electric heat accessory Connect the power wiring to the fuse block in the heater control box Route the control wires through the 22 2mm 7 8 in openings and connect them to the ter minals...

Страница 10: ...hrough 0 AWG Accessory Model Nom kW Heater Dimensions mm inches A B C D E F G H K L M 2HS04501050 2HS04501650 2HS04502650 2HS04503650 10 16 26 36 692 271 4 641 251 4 362 141 4 25 1 102 4 13 1 2 140 51...

Страница 11: ...11 550 39 TG5YI TERMINALS ON BLOCK 3TB OF THE BLOWER UNIT TERMINALS ON 1 STAGE COOLING THERMOSTAT 2TH13700424 FIELD WIRING Cooling only CONTROL WIRING Units with steam or hot water coil AC Units with...

Страница 12: ...o change without notice Printed in U S A Copyright by York International Corporation 2001 All Rights Reserved 5005 York Drive 550 39 TG5Y 0601 Supersedes 550 39 TG5Y 0501 Norman OK 73069 Unitary Produ...

Отзывы: