background image

998659-YIM-C-0614

Johnson Controls Unitary Products

45

Compressor Protection

In addition to the external pressure switches, the compressors 
also have inherent (internal) protection. If there is an abnormal 
temperature rise in a compressor, the protector will open to shut 
down the compressor. The UCB incorporates features to 
minimize compressor wear and damage. An

 Anti-Short Cycle 

Delay (ASCD)

 is utilized to prevent operation of a compressor 

too soon after its previous run. Additionally, a minimum run time 
is imposed any time a compressor is energized.

The ASCD is initiated on unit start-up and on any compressor 
reset or lock-out.

Flash Codes

The UCB will initiate a flash code associated with errors within 
the system. Refer to UNIT CONTROL BOARD FLASH CODES 
Table 23.

Reset

Remove the call for cooling, by raising thermostat setting higher 
than the conditioned space temperature. This resets any 
pressure or freezestat flash codes.

Heating Sequence of Operation

When the thermostat calls for the first stage of heating, the low 
voltage control circuit is completed between “R” and “W1”. This 
24vac signal is passed through the UCB to the RY1 Relay. 
Contacts RY1-2 open, assuring the reversing valve cannot be 
energized, except during defrost. Contacts RY1-1 close, 
completing the circuit to Y on the defrost control (DC). After its 
five minute ASCD timer is satisfied, the DC closes it’s internal 
compressor relay contacts, sending a 24vac signal to the MV 
terminal on the UCB. If its ASCD timer is satisfied the UCB will 
energize compressor #1 relay. After a two second delay, it then 
energizes compressor #2 relay (if applicable). Therefore, on a 
call for heat from W1, both compressors are always energized, 
unless one or the other is locked out by the UCB. Also on the 
call for heat, the DC energizes the M4 contactor which brings 
on both condenser fans.

A second stage call from the thermostat completes the circuit 
between R and W2. This 24vac signal is passed through the 
UCB to the defrost control board. If the unit is equipped with an 
optional electric heater it would be energized through a set of 
normally closed contacts on the defrost board. Take note that 
the MV terminal on the UCB is constantly monitored while there 
is a demand for heat. If the UCB does not see 24vac at terminal 
MV after six minutes, it initiates a fault code 9, indicating a 
heating problem. 

As mentioned earlier, the defrost control (DC) utilizes a time/
temperature defrost scheme. The following two conditions must 
be met before the DC will enter a defrost mode:

1.

The DC must first satisfy its accumulated minimum run 
time. This is factory set at 60 minutes, but is field 
adjustable to 30, 60 or 90 minutes. 

2.

Either of the two defrost thermostats (DF1 or DF2) must be 
closed. These normally open thermostats are mounted on 
the respective liquid lines and are set to close at 31 
degrees (+/-3) (28° F on XP090).

If neither defrost thermostat is closed at the completion of it’s 
minimum accumulated run time cycle, the DC initiates another 
run time cycle, which it must complete before it looks at the 
position of the defrost thermostats. This action is repeated until, 
at the completion of a run time cycle, one of the defrost 
thermostats is found to be closed and the DC enters defrost 
mode.

When the DC enters the defrost mode, it’s on-board defrost 
relay is powered. This energizes both reversing valves, de-
energizes both condenser fan motors and energizes the unit’s 
optional electric heater. The DC remains in defrost mode until 
either of the following two conditions is met:

1.

Both of the liquid line thermostats are open. Each is set to 
open at 55 degrees (+/- 3).

2.

The maximum defrost run time of 10 minutes is met.

The DC also contains a set of test pins. Placing a jumper across 
these pins will result in the following actions:

• If the ASCD timer is active, it is now by-passed, allowing 

the compressor to run.

• If the DC is in a lockout condition, the lockout is reset.

• If the compressor is running, the DC is forced into defrost 

mode. The control will remain in defrost mode for as long 
as the jumper is in place. When the jumper is removed, 
the control will terminate the defrost mode in the normal 
manner as described above.

NOTE: 

The DC has two flashing codes which are only initiated 
if the two pressure switch terminals are open. As used 
in the Predator

®

 there is a jumper across the pressure 

switch terminals. Therefore the field should never 
experience a DC lockout mode unless that jumper is 
removed or broken.

Electric Heat Operation Errors

Temperature Limit

If the UCB senses zero volts from the high temperature limit, 
the indoor blower motor is immediately energized.

This limit is monitored regardless of unit operation status, i.e. 
the limit is monitored at all times.

If the temperature limit opens three times within one hour, it will 
lock-on the indoor blower motor and a flash code is initiated 
(See Table 23).

Safety Controls

The UCB monitors the temperature limit switch of electric heat 
units.

The control circuit includes the following safety controls:

Содержание Predator XP Series

Страница 1: ...Application 37 16 RPM Selection 38 17 Indoor Blower Specifications 39 18 Power Exhaust Specifications 39 19 Motor Sheave Datum Diameters 41 20 Additional Static Resistance 42 21 Electric Heat Limit Se...

Страница 2: ...whenever working on air conditioning equipment Be sure to follow all other applicable safety precautions and codes including National Electric Code ANSI NFPA No 70 latest edition U S A and Canadian El...

Страница 3: ...as follows 1 For use as a cooling only unit cooling unit with supplemental electric heat or a forced air furnace 2 For outdoor installation only 3 For installation on combustible material and may be i...

Страница 4: ...n of Additional Options that Don t Have an Option Code Pre assigned AA None AB Phase Monitor AC Coil Guard AD Dirty Filter Switch AE Phase Monitor Coil Guard AF Phase Monitor Dirty Filter Switch AG Co...

Страница 5: ...st Edition 2 Local building codes and 3 Local electric utility requirements In Canada 1 Canadian Electrical Code CSA C22 1 2 Installation Codes CSA B149 1 3 Local plumbing and waste water codes and 4...

Страница 6: ...877 UPG SERV for guidance Additional accessories may be needed for stable operation at temperatures below 30 F Compressor 1 Access High Eff Compressor Toolless Door Latch Side entry power and control...

Страница 7: ...lings to the lifting holes provided in the base rails Spreader bars whose length exceeds the largest dimension across the unit MUST be used across the top of the unit Units may be moved or lifted with...

Страница 8: ...lbs Center of Gravity 4 Point Load Location lbs 6 Point Load Location lbs Shipping Operating X Y A B C D A B C D E F 078 6 5 XP 1085 1080 38 25 262 195 266 357 184 150 124 169 204 250 090 7 5 XP 1095...

Страница 9: ...e 9 XP150 Physical Dimensions Table 3 XP078 150 Unit Accessory Weights Unit Accessory Weight lbs Shipping Operating Economizer 90 85 Power Exhaust 40 35 Electric Heat1 49 49 1 Weight given is for the...

Страница 10: ...0 3 4 89 30 3 16 24 3 16 17 3 16 6 3 16 XP120 50 3 4 89 30 3 16 24 3 16 17 3 16 6 3 16 XP150 50 3 4 119 1 2 30 3 16 24 3 16 17 3 16 6 3 16 5 3 8 Table 5 XP078 150 Unit Clearances Direction Distance in...

Страница 11: ...it Electrical Entry Figure 12 XP078 120 Unit Side Duct Openings Disconnect Swith Cover Power Entry 2 1 2 Control Entry 7 8 Power Entry 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry 7 8...

Страница 12: ...Left Duct Opening Dot Plugs 2 7 8 5 5 32 D C 31 5 8 18 1 4 B A Table 6 Side Duct Dimensions Unit Model Number Dimension in A B C D XP078 28 1 4 18 1 16 28 1 4 18 1 4 XP090 28 1 4 18 1 16 28 1 4 18 1 4...

Страница 13: ...Curb Figure 16 XP078 150 Transition Roof Curb 8 or 14 50 1 2 30 20 20 80 5 8 6 2 TYP INSULATED DECK UNDER COMPRESSOR SECTION INSULATED DECK UNDER CONDENSER SECTION FRONT RIGHT SUPPLY RETURN 76 5 8 94...

Страница 14: ...ation no duct cover changes are necessary For side duct application remove the side duct covers and install over the bottom duct openings The panels removed from the side duct connections are designed...

Страница 15: ...l Mobil 3MA POE This oil is extremely hygroscopic meaning it absorbs water readily POE oil can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants Take all necessary pre...

Страница 16: ...e utilized for these units Factory installed disconnects are available If installing a disconnect field supplied or York International supplied accessory refer to Figure 4 for the recommended mounting...

Страница 17: ...r general installation procedure Seven 7 color coded insulated wires should be used to connect the thermostat to the unit Refer to Table 7 for control wire sizing and maximum length THREE PHASE POWER...

Страница 18: ...C OCC X R 2 TO REMOTE SENSOR 2ET04701324 IF USED 24 Volt Transformer THERMOSTAT1 TERMINALS UNIT TERMINALS STRIP TB1 1 Electronic programmable Thermostat 2ET0770010124 includes subbase 2 Terminals A1 a...

Страница 19: ...4 1 49 6 50 60 E09 6 8 1 18 9 67 7 73 2 70 80 E18 13 5 2 37 5 90 9 96 4 100 100 E24 18 2 50 0 106 6 112 1 110 125 E36 25 5 2 70 8 132 6 138 1 150 150 230 15 6 83 1 21 4 1 5 6 0 5 5 0 0 None 44 1 49 6...

Страница 20: ...3 5 2 37 5 114 1 119 6 125 125 E24 18 2 50 0 129 8 135 3 150 150 E36 25 5 2 70 8 155 8 161 3 175 175 E54 40 6 2 112 7 155 8 161 4 175 175 230 22 4 149 0 35 0 1 5 10 9 5 5 0 0 None 67 3 72 8 80 90 E18...

Страница 21: ...0 E09 6 8 1 18 9 71 3 76 8 80 80 E18 13 5 2 37 5 94 5 100 0 100 100 E24 18 2 50 0 110 2 115 7 125 125 E36 25 5 2 70 8 136 2 141 7 150 150 230 15 6 83 1 21 4 1 5 9 6 5 5 0 0 None 47 7 53 2 60 60 E09 9...

Страница 22: ...13 5 2 37 5 119 3 124 8 125 125 E24 18 2 50 0 135 0 140 5 150 150 E36 25 5 2 70 8 161 0 166 5 175 175 E54 40 6 2 112 7 161 0 167 9 175 175 230 22 4 149 0 35 0 1 5 16 1 5 5 0 0 None 72 5 78 0 90 100 E1...

Страница 23: ...E09 6 8 1 18 9 77 7 83 2 80 90 E18 13 5 2 37 5 100 9 106 4 110 110 E24 18 2 50 0 116 6 122 1 125 125 E36 25 5 2 70 8 142 6 148 1 150 150 230 15 6 83 1 21 4 1 5 6 0 5 5 10 0 None 54 1 59 6 60 70 E09 9...

Страница 24: ...8 13 5 2 37 5 124 1 129 6 125 150 E24 18 2 50 0 139 8 145 3 150 150 E36 25 5 2 70 8 165 8 171 3 175 175 E54 40 6 2 112 7 167 0 173 9 175 175 230 22 4 149 0 35 0 1 5 10 9 5 5 10 0 None 77 3 82 8 90 100...

Страница 25: ...E09 6 8 1 18 9 81 3 86 8 90 90 E18 13 5 2 37 5 104 5 110 0 110 110 E24 18 2 50 0 120 2 125 7 125 150 E36 25 5 2 70 8 146 2 151 7 150 175 230 15 6 83 1 21 4 1 5 9 6 5 5 10 0 None 57 7 63 2 70 70 E09 9...

Страница 26: ...13 5 2 37 5 129 3 134 8 150 150 E24 18 2 50 0 145 0 150 5 150 175 E36 25 5 2 70 8 171 0 176 5 175 200 E54 40 6 2 112 7 173 5 180 4 175 200 230 22 4 149 0 35 0 1 5 16 1 5 5 10 0 None 82 5 88 0 100 110...

Страница 27: ...35 7 9 3 35 8 6 3 30 13 2 3 0 17 F capacity rating Mbh 43 0 51 0 53 0 58 0 90 0 System power KW COP 5 7 2 20 6 4 2 25 6 9 2 25 7 8 2 20 13 5 2 2 HSPF Btu Watts hr DIMENSIONS inches Length 89 89 89 89...

Страница 28: ...AK71 AK69 AK69 AK89 AK74 AK84 AK74 AK74 BK77 Belt A54 A52 A52 A54 A56 A54 A56 A54 A54 BX56 Motor HP each 1 1 2 2 1 1 2 3 2 3 2 3 3 5 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725 Frame size 56...

Страница 29: ...Exhaust accessories 1 Down Flow application 2 Horizontal Flow application that requires the purchase of a barometric relief hood Rain Hood All of the hood components including the filters the gasketi...

Страница 30: ...ucture that is easy to use You press the and arrow buttons to move forward and backward through the menus and press the button to select and confirm setup item changes Time out and Screensaver When no...

Страница 31: ...damper 100 open and fan on high speed and the call will turn off OR If the call for additional cooling in the space has not been satisfied then the first stage of mechanical cooling will be enabled t...

Страница 32: ...sity of the air However since the air at high altitude is less dense less static pressure will be generated and less power will be required than a similar application at sea level Air density correcti...

Страница 33: ...given is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 1 5 832 1 80 Enter the blower table at 6000 sCFM and...

Страница 34: ...1 95 BHP exceeds the maximum continuous BHP rating of the 1 5 HP motor The 2 HP motor is required 6 1268 RPM is within the range of the 2 HP drives 7 Using the 2 HP motor and drive 5 turns open will...

Страница 35: ...1072 1 87 1124 2 04 2400 631 0 16 682 0 41 736 0 66 793 0 90 852 1 14 911 1 36 970 1 58 1028 1 78 1084 1 97 1136 2 13 2600 642 0 27 692 0 52 747 0 76 804 1 01 862 1 24 922 1 47 981 1 69 1039 1 89 1094...

Страница 36: ...ressure IWG1 1 Blower performance includes 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the ma...

Страница 37: ...065 1 81 1113 2 02 1153 2 24 2400 689 0 42 743 0 69 800 0 93 859 1 16 919 1 37 978 1 57 1035 1 77 1088 1 97 1135 2 18 1176 2 40 2600 712 0 60 766 0 87 823 1 11 882 1 34 942 1 55 1002 1 75 1058 1 95 11...

Страница 38: ...M BHP RPM BHP RPM BHP RPM BHP 3 HP Field Supplied Drive Standard 3 HP Drive Hi Static 5 HP Drive 3200 757 1 20 811 1 36 864 1 50 915 1 64 964 1 77 1012 1 89 1059 2 02 1104 2 14 1149 2 26 1192 2 38 340...

Страница 39: ...les one in the return air duct as close to the inlet of the unit as possible and another in the supply air duct as close to the outlet of the unit as possible 2 Using the whole drilled in step 1 inser...

Страница 40: ...nflow configuration 6 Determine the unit Measured CFM from the Blower Performance Table External Static Pressure and the number of turns the variable motor sheave is open 7 To adjust Measured CFM to R...

Страница 41: ...tallation for any installation errors leaks or undesirable systems effects that can result in loss of airflow Even small changes in blower speed can result in substantial changes in static pressure an...

Страница 42: ...0 0 04 0 14 0 07 0 08 0 09 0 10 0 13 2500 0 11 0 16 0 08 0 09 0 10 0 11 0 14 2700 0 18 0 17 0 09 0 10 0 12 0 13 0 16 2900 0 25 0 19 0 10 0 11 0 13 0 14 0 18 3100 0 31 0 20 0 12 0 13 0 15 0 16 0 20 330...

Страница 43: ...age of cooling continues for 20 minutes compressor 2 is energized provided it has not been locked out If there is an initial call for both stages of cooling the UCB will delay energizing compressor 2...

Страница 44: ...halted compressor Should a low pressure switch open three times within one hour of operation the UCB will lock out the associated compressor and flash a code Table 23 If the other compressor is inacti...

Страница 45: ...izes a time temperature defrost scheme The following two conditions must be met before the DC will enter a defrost mode 1 The DC must first satisfy its accumulated minimum run time This is factory set...

Страница 46: ...off position 3 Turn unit electrical power on 4 Set the room thermostat fan switch to on 5 Check indoor blower rotation If blower rotation is in the wrong direction Refer to Phasing Section in general...

Страница 47: ...the power connected to the unit Use extreme care when working with live circuits Check the unit nameplate for the correct line voltage and set the voltmeter to the correct range before making any con...

Страница 48: ...ion Byte will be turned on and the red status LED Heat Delay is turned off Press the COMM SETUP SELECT button to toggle into the Heat Delay Setup the green LED will turn off and the red LED for Heat D...

Страница 49: ...blades If the blades are open the economizer is providing free cooling and the compressors will not immediately operate If both stages of cooling are requested simultaneously and the economizer provid...

Страница 50: ...not the room thermostat fan switch is in the AUTO position 1 If installed check the position of the economizer blades If the blades are open the economizer is providing free cooling If the second stag...

Страница 51: ...energize all compressors on a loss of call for the first stage of cooling i e a loss if 24 volts at the Y1 terminal 8 If 24 volts are present at the UCB Y1 terminal the compressor may be out due to a...

Страница 52: ...reached For units without factory installed or with field installed economizers the UCB allows compressor operation all the time This programming can be checked or changed by the local distributor 14...

Страница 53: ...r standard warranty policy which states that Johnson Controls UPG will cover parts and labor on new equipment start up failures that are caused by a defect in factory workmanship or material for a per...

Страница 54: ...ncy drive is operating at 60 HZ Do not proceed with the equipment start up without the design CFM information Design Supply Air CFM __________________________ Design Return Air CFM ___________________...

Страница 55: ...omplete Air Moving Inspection Completed See Notes Alignment of drive components Belt tension adjusted properly Blower pulleys tight on shaft bearing set screws tight wheel tight to shaft Pressure swit...

Страница 56: ...to increase of decrease the airflow to meet the design conditions If the motor pulley size was changed measure the outside diameters of the motor and blower pulleys and record those diameters here Bl...

Страница 57: ...Return Air Temperature ________________ F db ________________ F wb ________________ RH Mixed Air Temperature ________________ F db ________________ F wb ________________ RH Supply Air Temperature ____...

Страница 58: ...____________________________________________________________________ ________________________________________________________________________________________________________ __________________________...

Отзывы: