998659-YIM-C-0614
36
Johnson Controls Unitary Products
XP120 (10 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
Standard 2 HP & Drive
Hi Static 3 HP & Drive
2600
646
0.41
698
0.62
748
0.82
797
1.02
844
1.21
890
1.39
936
1.57
980
1.74
1023
1.92
1065
2.09
2800
654
0.50
706
0.71
756
0.92
805
1.11
852
1.30
898
1.48
943
1.66
987
1.83
1031
2.01
1073
2.18
3000
663
0.60
714
0.81
765
1.02
813
1.21
861
1.40
907
1.58
952
1.76
996
1.93
1039
2.11
1082
2.28
3200
673
0.71
724
0.93
774
1.13
823
1.32
871
1.51
917
1.69
962
1.87
1006
2.05
1049
2.22
1091
2.39
3400
684
0.84
735
1.05
785
1.25
834
1.45
882
1.63
928
1.82
973
2.00
1017
2.17
1060
2.34
1102
2.52
3600
696
0.98
747
1.19
798
1.39
846
1.59
894
1.78
940
1.96
985
2.14
1029
2.31
1072
2.48
1115
2.66
3800
709
1.14
761
1.35
811
1.55
860
1.75
907
1.93
953
2.12
999
2.29
1043
2.47
1086
2.64
1128
2.81
4000
724
1.31
776
1.52
826
1.72
874
1.92
922
2.11
968
2.29
1013
2.47
1057
2.64
1100
2.82
1143
2.99
4200
740
1.50
792
1.71
842
1.92
890
2.11
938
2.30
984
2.48
1029
2.66
1073
2.83
1116
3.01
1159
3.18
4400
757
1.71
809
1.92
859
2.13
908
2.32
955
2.51
1001
2.69
1046
2.87
1091
3.04
1134
3.22
1176
3.39
4600
776
1.94
827
2.15
877
2.35
926
2.55
974
2.74
1020
2.92
1065
3.10
1109
3.27
1152
3.45
-
-
4800
795
2.19
847
2.40
897
2.60
946
2.79
993
2.98
1040
3.16
1085
3.34
-
-
-
-
-
-
5000
816
2.45
868
2.66
918
2.86
967
3.06
1014
3.25
1061
3.43
-
-
-
-
-
-
-
-
3 HP & Field Supplied Drive
XP150 (12.5 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive
Standard 3 HP & Drive
3200
673
0.71
724
0.93
774
1.13
823
1.32
871
1.51
917
1.69
962
1.87
1006
2.05
1049
2.22
1091
2.39
3400
684
0.84
735
1.05
785
1.25
834
1.45
882
1.63
928
1.82
973
2.00
1017
2.17
1060
2.34
1102
2.52
3600
696
0.98
747
1.19
798
1.39
846
1.59
894
1.78
940
1.96
985
2.14
1029
2.31
1072
2.48
1115
2.66
3800
709
1.14
761
1.35
811
1.55
860
1.75
907
1.93
953
2.12
999
2.29
1043
2.47
1086
2.64
1128
2.81
4000
724
1.31
776
1.52
826
1.72
874
1.92
922
2.11
968
2.29
1013
2.47
1057
2.64
1100
2.82
1143
2.99
4200
740
1.50
792
1.71
842
1.92
890
2.11
938
2.30
984
2.48
1029
2.66
1073
2.83
1116
3.01
1159
3.18
4400
757
1.71
809
1.92
859
2.13
908
2.32
955
2.51
1001
2.69
1046
2.87
1091
3.04
1134
3.22
1176
3.39
4600
776
1.94
827
2.15
877
2.35
926
2.55
974
2.74
1020
2.92
1065
3.10
1109
3.27
1152
3.45
1194
3.62
4800
795
2.19
847
2.40
897
2.60
946
2.79
993
2.98
1040
3.16
1085
3.34
1129
3.52
1172
3.69
1214
3.86
5000
816
2.45
868
2.66
918
2.86
967
3.06
1014
3.25
1061
3.43
1106
3.61
1150
3.78
1193
3.95
1235
4.13
5200
839
2.73
890
2.94
940
3.14
989
3.34
1037
3.53
1083
3.71
1128
3.89
1172
4.06
1215
4.23
1257
4.41
5400
862
3.03
914
3.24
964
3.44
1012
3.64
1060
3.82
1106
4.01
1151
4.18
1195
4.36
1238
4.53
1281
4.70
5600
886
3.34
938
3.55
988
3.76
1037
3.95
1084
4.14
1131
4.32
1176
4.50
1220
4.67
1263
4.85
1305
5.02
5800
912
3.67
964
3.89
1014
4.09
1063
4.28
1110
4.47
1156
4.65
1201
4.83
1246
5.01
1289
5.18
1331
5.35
6000
939
4.02
990
4.23
1041
4.44
1089
4.63
1137
4.82
1183
5.00
1228
5.18
1272
5.35
1315
5.53
1358
5.70
6200
967
4.39
1018
4.60
1068
4.80
1117
4.99
1165
5.18
1211
5.36
1256
5.54
1300
5.72
-
-
-
-
Hi Static 5 HP & Drive