Trouble Shooting
If your unit does not operate or cooling enough refer to the Chart below and check before
calling a Service Engineer.
TROUBLE SHOOTING CHART FOR DUCTABLE SPLIT TYPE
AIR-CONDITIONERS
Power failure.
Fuse blown or Circuit Breaker tripped.
Defective thermostat, contactor,
transformer or control relay.
Insufficient line voltage.
Incorrect or faulty wiring.
Thermostat setting too high.
Call power company.
Replace fuse or reset circuit breaker.
Replace component.
Determine the cause and replace.
Check wiring diagram & rewire correctly.
Lower thermostat setting below
room temperature.
Compressor and
condenser fan will not
start.
PROBLEM
CAUSE
REMEDY
Faulty wiring or loose connections in
compressor circuit.
Compressor motor burned out, seized, or
internal over load open.
Defective run/start capacitor, overload start
relay.
One leg of three-phase power dead.
Refrigerant overcharge or undercharge.
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Defective run/start capacitor, overload, or
start relay Defective thermostat.
Faulty condenser - fan motor or capacitor.
Restriction in refrigerant system.
Dirty air filter.
Unit undersized for load.
Thermostat set too low.
Low refrigerant charge.
Leaking valves in compressor
Air in system.
Condenser coil dirty or restricted.
Dirty air filter.
Dirty condenser coil.
Refrigerant overcharged.
Air in system.
Condenser air restricted or air short-
cycling.
Low refrigerant charge.
Compressor valve leaking.
Restriction in liquid tube.
High head load.
Compressor valves leaking.
Refrigerant overcharged.
Check wiring and repair or replace.
Determine cause, replace compressor.
Determine the cause and replace.
Replace fuse or reset circuit breaker.
Reclaim refrigerant, evacuate system,
and recharge to nameplate.
Determine the cause and replace.
Determine cause and correct.
Determine cause and correct.
Determine the cause and replace.
Replace thermostat. Replace.
Locate restriction and remove.
Replace filter.
Decrease load or increase unit size.
Reset thermostat.
Locate leak; repair and recharge.
Replace compressor.
Reclaim refrigerant, evacuate, & recharge.
Clean coil or remove restriction.
Replace air filter.
Clean coil.
Reclaim excess refrigerant.
Reclaim refrigerant,
evacuate & recharge.
Determine cause and correct.
Check for leaks; repair and recharge.
Replace compressor.
Reclaim excess refrigerant.
Check for source and eliminate.
Replace compressor.
Reclaim excess refrigerant.
Excessive suction
pressure.
Head pressure too low.
Excessive head
pressure.
Compressor operates
continuously.
Compressor cycles (other
than normally satisfying
thermostat).
Compressor will not
start but condenser fan
runs.
COMMERCIAL DUCTED SPLITS
38
Содержание Mr. Slim PK-1.6FLA
Страница 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL York Taurus Commercial Ducted Splits 2...
Страница 15: ...G A Drawing Outdoor units YE2CE 072 SINGLE CIRCUIT UNITS COMMERCIAL DUCTED SPLITS 17...
Страница 23: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications COMMERCIAL DUCTED SPLITS 25...
Страница 35: ...Exploded View EXPLODED VIEW OUTDOOR UNIT YE2CE240 300 ALL VOLTAGES COOL HEAT PUMP COMMERCIAL DUCTED SPLITS 37...
Страница 37: ......