York MILLENNIUM YT J Скачать руководство пользователя страница 7

FORM 160.55-PW7

7

YORK INTERNATIONAL

FIG. 9 – CONDENSER WATER FLOW INTERLOCK

If desired, a condenser water flow interlock can be ap-
plied. Flow switch – McDonnel type FS8W, max. 150
psi (YORK Part No. 024-15793) available at additional
cost. If condenser water flow switch is not used, a
jumper must be installed between terminals 1 and 11 .

When condenser water is flowing, the flow switch con-
tact will close. Opening of the condenser water flow
switch contacts for 2 continuous seconds will cause unit
shutdown. The Flow Switch Status is checked 30 sec-
onds into “System Run” and continuously thereafter.
The Graphic Control Center will display the following
message: “CYCLING SHUTDOWN – AUTO RE-
START” and “CONDENSER FLOW SWITCH
OPEN”.

LD04390

FIG. 8 – MULTI-UNIT SEQUENCE

FIG. 9  – CONDENSER WATER FLOW INTERLOCK

LD04391

FIG. 8 – MULTI-UNIT SEQUENCE

For multiple chiller installation application, Multi-Unit
Sequence contacts are available to start and stop each
unit. The maintained closure of a device contacts across
terminals   

1

   and    

9

    will permit the unit to operate in

all the operating modes with the “compressor” switch
in the “RUN” (

l

) position. Conversely, an opening of

the device contacts will inhibit the unit from operating;
the Graphic Control Center will then display the fol-
lowing message: “CYCLING SHUTDOWN – AUTO
RESTART” and “MULTIUNIT CYCLING – CON-
TACTS OPEN”. An accessory sequence control kit
for two, three or four units is available from YORK –
See Fig. 10 for Two Unit Sequence Control kit.

Содержание MILLENNIUM YT J

Страница 1: ...isions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contacts are factory furnished through a field wiring...

Страница 2: ...f full load amperes for 1 to 255 minutes following each compressor start For more details refer to Graphic Control Center Instructions Form 160 55 O1 6 Controlling the maximum allowable compressor mot...

Страница 3: ...ical Starter Manual Reset Overloads 9 2300 To 4160 Volts U l Or C S A Approved Units Only Fig 15 Remote Current Limit Setpoint With 0 10VDC 0r 2 10VDC Signal 10 Fig 16 Remote Current Limit Setpoint Wi...

Страница 4: ...READY TO START CONTACTS When closed these contacts signify the following 1 The Graphic Control Center is in digital ana log or ISN remote operating mode allowing for energy management system or remot...

Страница 5: ...performed by plac ing the Graphic Control Center COMPRESSOR Switch in the Stop Reset position O The unit can then be restarted Safety Shutdown contacts function in all op erating modes FIG 5 ANTICIPAT...

Страница 6: ...essor from the Graphic Control Cen ter and prevent the chiller from restart ing However the operator cannot lo cally start the compressor using com pressor start switch when the con trol center is in...

Страница 7: ...e following message CYCLING SHUTDOWN AUTO RE START and CONDENSER FLOW SWITCH OPEN LD04390 FIG 8 MULTI UNIT SEQUENCE FIG 9 CONDENSER WATER FLOW INTERLOCK LD04391 FIG 8 MULTI UNIT SEQUENCE For multiple...

Страница 8: ...T SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag unit follo...

Страница 9: ...ature when both units are operating When either unit is cycled off by the sequence control Fig 10 mixed chilled water temperature will rise as a result of uncooled return wa ter flowing through the in...

Страница 10: ...Liquid Temperature Reset then a 0 10VDC signal must be used for Re mote Current Limit Reset SIGNAL COMMON 5 1 J22 LD04498 0 10VDC As shown in Fig 15 connect input to Mi cro Board J22 1 signal and J22...

Страница 11: ...input will only be accepted in Digital Re mote Mode Calculate the setpoint for various pulse widths as follows SETPOINT 100 PULSE WIDTH IN SECONDS 1 X 7 For example if the relay contacts close for 3...

Страница 12: ...F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 10 F and the Local Leaving Chilled Liquid Temperature setpoint is programmed for 40...

Страница 13: ...ed offset 10 or 20 F above the local setpoint value The setpoint is changed linearly between these extremes as the input varies over the range of 0 20mA This input will only be accepted when Ana log R...

Страница 14: ...em perature high discharge temperature auxiliary safety power failure when the Auto Restart After Power Fail ure Dip Switch on the Micro Board Fig 21 is in the OFFposition SW1 position5 OFF whichimpli...

Страница 15: ...System EMS connect by others as shown in the diagram The EMS control relay shutdown and run lights are furnished by others When the N O contacts close between terminals 35 and 36 on field wiring ter...

Страница 16: ...onsor of the 2000 U S Olympic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1999 ALL RIGHTS RE...

Отзывы: