York MILLENNIUM YT J Скачать руководство пользователя страница 2

YORK INTERNATIONAL

2

3. The Graphic Control Center has a programmable

time clock function as a standard feature with holi-
day capability. This offers one preset automatic
Start-Stop per day on a seven day calendar basis
with the ability to program a single additional holi-
day start and stop time up to a week in advance.
Chilled water pump control contacts (see Note 13)
are also provided, allowing for efficient automatic
operation of the chilled water pump to reduce en-
ergy. Two chilled water pump operating modes are
available via the CHW PUMP programming dip
switch (position 8 of SW1) on the Micro Board.
With the switch in the OFF position, the chilled
water pump operates for 30 seconds prior to chiller
start, during chiller operation, coastdown, and
LWT cycling shutdowns. With the switch in the
ON position, the chilled water pump operates as
above plus it operates during MULTI-UNIT and
REMOTE/LOCAL cycling shutdowns.

4. Reduce the compressor-motor kW input (and thus

amps), by raising the leaving chilled liquid
temperature through remote temperature control
setpoint in the “remote” operating mode. When
remote temperature reset is accomplished by sup-
plying a 1 to 11 second pulse-width modulated sig-
nal, refer to Fig. 20. Through use of the remote
temperature control analog input on the Micro
Board, the leaving chilled liquid temperature may
be reset via a 0 to 20 or 4 to 20mA D.C. current
signal, a 0 to 10 or 2 to 10 volt D.C. signal.

5. Current limiting of demand during pulldown may

be accomplished by using the standard
PULLDOWN DEMAND LIMIT function pro-
vided in the Graphic Control Center. The
“Pulldown Demand Limit” key can be programmed
to limit compressor motor current from 30 to 100
percent of full load amperes, for 1 to 255 minutes
following each compressor start. For more details
refer to Graphic Control Center Instructions, Form
160.55-O1.

6. Controlling the maximum allowable compressor

motor amps from 30 to 100% through remote cur-
rent limit setpoint. Refer to Fig. 17 when the re-
mote current limit is accomplished by supplying a 1
to 11 second pulse-width modulated signal in the
“remote” operating mode. A jumper configurable
analog input is available for remote current limit
setpoint via a 0 to 20 or 4 to 20mA D.C. current
signal, a 0 to 10 or 2 to 10 volt D.C. signal.

7. The YORK ISN System may be interfaced with

the chiller Graphic Control Center to provide uni-
fied chiller plant system control. The ISN System
directly communicates with the Graphic Control
Center via the ISN GPIC card which may be in-
stalled in the Control Center. All temperatures, pres-
sures, safety alarms and cycling information known
to the Graphic Control Center are then available to
the ISN System for integrated chiller plant control,
data logging, and local and remote operator dis-
plays. The ISN GPIC card also allows the ISN to
start, stop, and reset the chiller’s leaving chilled
water and current limit setpoints.

ENERGY MANAGEMENTS SYSTEMS (CONT’D)

External wiring, unless specified as
an optional connection in the
manufacturer’s product literature, is
not to be connected inside this cabi-
net. Furthermore, auxiliary devices

such as relays, switches, transducers and controls
may not be installed inside this enclosure. All
wiring must be in accordance with YORK’s pub-

lished specifications and must be performed only
by qualified personnel. YORK will not be respon-
sible for damages resulting from improper con-
nection to these controls or application of im-
proper control signals. Failure to follow this
warning will void the manufacturer’s warranty
and may cause serious damage to property or in-
jury to persons.

Содержание MILLENNIUM YT J

Страница 1: ...isions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contacts are factory furnished through a field wiring...

Страница 2: ...f full load amperes for 1 to 255 minutes following each compressor start For more details refer to Graphic Control Center Instructions Form 160 55 O1 6 Controlling the maximum allowable compressor mot...

Страница 3: ...ical Starter Manual Reset Overloads 9 2300 To 4160 Volts U l Or C S A Approved Units Only Fig 15 Remote Current Limit Setpoint With 0 10VDC 0r 2 10VDC Signal 10 Fig 16 Remote Current Limit Setpoint Wi...

Страница 4: ...READY TO START CONTACTS When closed these contacts signify the following 1 The Graphic Control Center is in digital ana log or ISN remote operating mode allowing for energy management system or remot...

Страница 5: ...performed by plac ing the Graphic Control Center COMPRESSOR Switch in the Stop Reset position O The unit can then be restarted Safety Shutdown contacts function in all op erating modes FIG 5 ANTICIPAT...

Страница 6: ...essor from the Graphic Control Cen ter and prevent the chiller from restart ing However the operator cannot lo cally start the compressor using com pressor start switch when the con trol center is in...

Страница 7: ...e following message CYCLING SHUTDOWN AUTO RE START and CONDENSER FLOW SWITCH OPEN LD04390 FIG 8 MULTI UNIT SEQUENCE FIG 9 CONDENSER WATER FLOW INTERLOCK LD04391 FIG 8 MULTI UNIT SEQUENCE For multiple...

Страница 8: ...T SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag unit follo...

Страница 9: ...ature when both units are operating When either unit is cycled off by the sequence control Fig 10 mixed chilled water temperature will rise as a result of uncooled return wa ter flowing through the in...

Страница 10: ...Liquid Temperature Reset then a 0 10VDC signal must be used for Re mote Current Limit Reset SIGNAL COMMON 5 1 J22 LD04498 0 10VDC As shown in Fig 15 connect input to Mi cro Board J22 1 signal and J22...

Страница 11: ...input will only be accepted in Digital Re mote Mode Calculate the setpoint for various pulse widths as follows SETPOINT 100 PULSE WIDTH IN SECONDS 1 X 7 For example if the relay contacts close for 3...

Страница 12: ...F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 10 F and the Local Leaving Chilled Liquid Temperature setpoint is programmed for 40...

Страница 13: ...ed offset 10 or 20 F above the local setpoint value The setpoint is changed linearly between these extremes as the input varies over the range of 0 20mA This input will only be accepted when Ana log R...

Страница 14: ...em perature high discharge temperature auxiliary safety power failure when the Auto Restart After Power Fail ure Dip Switch on the Micro Board Fig 21 is in the OFFposition SW1 position5 OFF whichimpli...

Страница 15: ...System EMS connect by others as shown in the diagram The EMS control relay shutdown and run lights are furnished by others When the N O contacts close between terminals 35 and 36 on field wiring ter...

Страница 16: ...onsor of the 2000 U S Olympic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1999 ALL RIGHTS RE...

Отзывы: