York MILLENNIUM YT J Скачать руководство пользователя страница 6

YORK INTERNATIONAL

6

FIG. 6 – REMOTE START AND STOP CONTACTS
FROM ENERGY MANAGEMENT SYSTEM

When the Graphic Control Center is in the “Digital”,
“Analog” or “ISN” remote operating mode and the
COMPRESSOR switch is in the “RUN” (

l

) position,

with the Remote Stop Contacts open, and the Remote
Mode Ready to Start Contacts closed (Fig. 1), the unit
will start via a closure of the Remote Start Contacts. A
subsequent closure of the Energy Management System
Remote Stop Contacts causes the chiller to shut down.
The Graphic Control Center will display “REMOTE
STOP” because the Energy Management System Re-
mote Stop Contact has commanded the unit to shut down.

It is recommended that maintained contacts be used for
both START and STOP.

Even when the chiller is applied with
Remote Start-Stop (when the Control
Center is in the “remote operating
mode), an EMERGENCY STOP by an
operator or others can STOP the com-
pressor from the Graphic Control Cen-
ter and prevent the chiller from restart-
ing. However, the operator cannot lo-
cally start the compressor using “com-
pressor” start switch, when the con-
trol center is in the “remote” operat-
ing mode.

FIG. 6 – REMOTE START-STOP CONTACTS FROM

ENERGY MANAGEMENT SYSTEM

FIG. 7 – REMOTE/LOCAL CYCLING DEVICES

FIG. 7 – REMOTE/LOCAL CYCLING DEVICES

The closure of an automatic reset device across this
input will permit the unit to operate in all operating
modes. Conversely, an opening of the device contacts
will inhibit the unit from operating; the Graphic Con-
trol Center will then display the following messages:
“CYCLING SHUTDOWN – AUTO RESTART” and
“SYSTEM CYCLING – CONTACTS OPEN”.

The Graphic Control Center contains
a seven day time clock to select daily
schedule Start/Stop times (Sunday
through Saturday including one or
more holidays in week) up to one full
week at a time. So automatic start and
stop of the unit on a daily basis, at pre-
determined times, can be programmed
as a standard feature; an additional
program timer is not required for this
function.

LD04387

LD04389

Содержание MILLENNIUM YT J

Страница 1: ...isions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contacts are factory furnished through a field wiring...

Страница 2: ...f full load amperes for 1 to 255 minutes following each compressor start For more details refer to Graphic Control Center Instructions Form 160 55 O1 6 Controlling the maximum allowable compressor mot...

Страница 3: ...ical Starter Manual Reset Overloads 9 2300 To 4160 Volts U l Or C S A Approved Units Only Fig 15 Remote Current Limit Setpoint With 0 10VDC 0r 2 10VDC Signal 10 Fig 16 Remote Current Limit Setpoint Wi...

Страница 4: ...READY TO START CONTACTS When closed these contacts signify the following 1 The Graphic Control Center is in digital ana log or ISN remote operating mode allowing for energy management system or remot...

Страница 5: ...performed by plac ing the Graphic Control Center COMPRESSOR Switch in the Stop Reset position O The unit can then be restarted Safety Shutdown contacts function in all op erating modes FIG 5 ANTICIPAT...

Страница 6: ...essor from the Graphic Control Cen ter and prevent the chiller from restart ing However the operator cannot lo cally start the compressor using com pressor start switch when the con trol center is in...

Страница 7: ...e following message CYCLING SHUTDOWN AUTO RE START and CONDENSER FLOW SWITCH OPEN LD04390 FIG 8 MULTI UNIT SEQUENCE FIG 9 CONDENSER WATER FLOW INTERLOCK LD04391 FIG 8 MULTI UNIT SEQUENCE For multiple...

Страница 8: ...T SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag unit follo...

Страница 9: ...ature when both units are operating When either unit is cycled off by the sequence control Fig 10 mixed chilled water temperature will rise as a result of uncooled return wa ter flowing through the in...

Страница 10: ...Liquid Temperature Reset then a 0 10VDC signal must be used for Re mote Current Limit Reset SIGNAL COMMON 5 1 J22 LD04498 0 10VDC As shown in Fig 15 connect input to Mi cro Board J22 1 signal and J22...

Страница 11: ...input will only be accepted in Digital Re mote Mode Calculate the setpoint for various pulse widths as follows SETPOINT 100 PULSE WIDTH IN SECONDS 1 X 7 For example if the relay contacts close for 3...

Страница 12: ...F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 10 F and the Local Leaving Chilled Liquid Temperature setpoint is programmed for 40...

Страница 13: ...ed offset 10 or 20 F above the local setpoint value The setpoint is changed linearly between these extremes as the input varies over the range of 0 20mA This input will only be accepted when Ana log R...

Страница 14: ...em perature high discharge temperature auxiliary safety power failure when the Auto Restart After Power Fail ure Dip Switch on the Micro Board Fig 21 is in the OFFposition SW1 position5 OFF whichimpli...

Страница 15: ...System EMS connect by others as shown in the diagram The EMS control relay shutdown and run lights are furnished by others When the N O contacts close between terminals 35 and 36 on field wiring ter...

Страница 16: ...onsor of the 2000 U S Olympic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1999 ALL RIGHTS RE...

Отзывы: