York MILLENNIUM YT J Скачать руководство пользователя страница 11

FORM 160.55-PW7

11

YORK INTERNATIONAL

mote Analog Input Range” setpoint is set for 0-10
Volts, and Micro Board Program Jumper JP23 has been
placed on pins 1 and 2. Calculate the setpoint for vari-
ous inputs as follows:

SETPOINT (%) = 100 – (mA X 3.5)

For example, if the input is 8mA, the setpoint would be
set to 72% as follows:

SETPOINT (%)

= 100 – (8 X 3.5)
= 100 – 28 = 72%

4-20mA - As shown in Figure 16, connect input to Mi-
cro Board J22-2 (signal) and J2-5 (Gnd). The setpoint
varies linearly from 100% to 30% FLA as the input
varies from 4mA to 20mA. This input will only be ac-
cepted when “Analog” Remote Mode is selected, the
“Remote Analog Input Range” setpoint is set for
“2-10 Volts” and Micro Board Program Jumper JP23
has been placed on pins 1 and 2. Calculate the setpoint
for various inputs as follows:

SETPOINT (%) = 100 – [(mA – 4) X 4.375]

For example, if the input is 8mA, the setpoint would be
set to 83% as follows:

SETPOINT (%)

= 100 – [(8 – 4) X 4.375]
= 100 – (4 X 4.375)
= 100 – 17.5
= 82.5
= 83%

PWM - The Pulse Width Modulation input is in the form
of a 1 to 11 second relay contact closure that applies
115VAC to the I/O Board TB4-20 for 1 to 11 seconds.
As shown in Fig. 17, connect dry closure relay contacts
between I/O Board TB4-20 (signal) and TB4-1
(115VAC). The setpoint varies linearly from 100% to
30% as the relay contact closure time changes from 1
to 11 seconds. The relay contacts should close for 1 to
11 seconds at least once every 30 minutes to maintain
the setpoint to the desired value. If a 1 to 11 second
closure is not received within 30 minutes of the last clo-

FIG. 17 – REMOTE CURRENT LIMIT SETPOINT

WITH PWM SIGNAL

LD04502

sure, the setpoint is defaulted to 100%. A closure is
only accepted at rates not to exceed once every 70 sec-
onds. This input will only be accepted in “Digital” Re-
mote Mode. Calculate the setpoint for various pulse
widths as follows:

SETPOINT (%) = 100 – [(PULSE WIDTH IN SECONDS – 1) X 7]

For example, if the relay contacts close for 3 seconds,
the setpoint would be set to 86% as follows:

SETPOINT (%)

= 100 – [(3 – 1) X 7]
= 100 – (2 X 7)
= 100 – 14
= 86%

REMOTE LEAVING CHILLED LIQUID SETPOINT with
0-10VDC, 2-10VDC, 0-20mA, 4-20mA or Pulse Width
Modulation Signal

Remote Leaving Chilled Liquid Temperature Setpoint
Reset can be accomplished by supplying (by others) a
0-10VDC, 2-10VDC, 0-20mA, 4-20mA or 1 to 11 sec-
ond Pulse Width Modulated (PWM) signal to the Con-
trol Center. The Leaving Chilled Liquid Tempera-
ture Setpoint 
is programmable over the range of 38°F
to 70°F (water applications), 36°F to 70°F (water appli-
cations with Smart Freeze Protection enabled) or 10°F
to 70°F (brine applications). The Remote Input Signal
changes the setpoint by creating an offset above the
locally programmed Leaving Chilled Liquid Tempera-
ture Base Setpoint value. The setpoint can be remotely
changed over the range of 10° or 20º F (as per the lo-
cally programmed Remote Reset Temperature
Range 
setpoint) above the Local Leaving Chilled Liq-
uid Temperature Setpoint. For example, if the Local
Setpoint is 40°F and the Remote Reset Tempera-
ture Range 
setpoint is programmed for 10°F, the Leav-
ing Chilled Liquid Temperature setpoint can be remotely
reset over the range of 40°F to 50°F. The Control Cen-
ter must be configured appropriately to accept the de-
sired signal type as follows:

• The appropriate Remote Mode must be selected:

Analog Remote Mode must be selected when
using a voltage or current signal input. Digital Re-
mote Mode 
must be selected when using a PWM
input.

• If Analog Remote Mode is selected, the Remote

Analog Input Range setpoint must be set to
“0-10VDC” or “2-10VDC” as detailed below, re-
gardless of whether the signal is a voltage or cur-
rent signal type.

Содержание MILLENNIUM YT J

Страница 1: ...isions for remote setpoint reset of leaving chilled liquid tempera ture and current limit for EMS interfacing See Note 7 Five sets of unit status contacts are factory furnished through a field wiring...

Страница 2: ...f full load amperes for 1 to 255 minutes following each compressor start For more details refer to Graphic Control Center Instructions Form 160 55 O1 6 Controlling the maximum allowable compressor mot...

Страница 3: ...ical Starter Manual Reset Overloads 9 2300 To 4160 Volts U l Or C S A Approved Units Only Fig 15 Remote Current Limit Setpoint With 0 10VDC 0r 2 10VDC Signal 10 Fig 16 Remote Current Limit Setpoint Wi...

Страница 4: ...READY TO START CONTACTS When closed these contacts signify the following 1 The Graphic Control Center is in digital ana log or ISN remote operating mode allowing for energy management system or remot...

Страница 5: ...performed by plac ing the Graphic Control Center COMPRESSOR Switch in the Stop Reset position O The unit can then be restarted Safety Shutdown contacts function in all op erating modes FIG 5 ANTICIPAT...

Страница 6: ...essor from the Graphic Control Cen ter and prevent the chiller from restart ing However the operator cannot lo cally start the compressor using com pressor start switch when the con trol center is in...

Страница 7: ...e following message CYCLING SHUTDOWN AUTO RE START and CONDENSER FLOW SWITCH OPEN LD04390 FIG 8 MULTI UNIT SEQUENCE FIG 9 CONDENSER WATER FLOW INTERLOCK LD04391 FIG 8 MULTI UNIT SEQUENCE For multiple...

Страница 8: ...T SEQUENCE CONTROL Provides that cycling thermostat RWT will automati cally cycle either 1 or 2 unit Timer 3TR is an addi tional feature which prevents simultaneous starting of lead and lag unit follo...

Страница 9: ...ature when both units are operating When either unit is cycled off by the sequence control Fig 10 mixed chilled water temperature will rise as a result of uncooled return wa ter flowing through the in...

Страница 10: ...Liquid Temperature Reset then a 0 10VDC signal must be used for Re mote Current Limit Reset SIGNAL COMMON 5 1 J22 LD04498 0 10VDC As shown in Fig 15 connect input to Mi cro Board J22 1 signal and J22...

Страница 11: ...input will only be accepted in Digital Re mote Mode Calculate the setpoint for various pulse widths as follows SETPOINT 100 PULSE WIDTH IN SECONDS 1 X 7 For example if the relay contacts close for 3...

Страница 12: ...F LOCAL SETPOINT OFFSET For example if the input is 5VDC and the Remote Re set Temp Range setpoint is programmed for 10 F and the Local Leaving Chilled Liquid Temperature setpoint is programmed for 40...

Страница 13: ...ed offset 10 or 20 F above the local setpoint value The setpoint is changed linearly between these extremes as the input varies over the range of 0 20mA This input will only be accepted when Ana log R...

Страница 14: ...em perature high discharge temperature auxiliary safety power failure when the Auto Restart After Power Fail ure Dip Switch on the Micro Board Fig 21 is in the OFFposition SW1 position5 OFF whichimpli...

Страница 15: ...System EMS connect by others as shown in the diagram The EMS control relay shutdown and run lights are furnished by others When the N O contacts close between terminals 35 and 36 on field wiring ter...

Страница 16: ...onsor of the 2000 U S Olympic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1999 ALL RIGHTS RE...

Отзывы: