York MILLENNIUM YK Скачать руководство пользователя страница 42

42

YORK INTERNATIONAL

tion of Service manual, Form 160.49-M2.

While the chiller is shut down, the orifice will be in the

fully open position causing the sensed level to be ap-

proximately 0%. When the chiller is started, after the

vane motor end switch (VMS) opens when entering

“SYSTEM RUN”, if actual level is less than the level

setpoint, a linearly increasing ramp is applied to the

level setpoint. This ramp causes the setpoint to go from

the initial refrigerant level (approximately 0%) to the

programmed setpoint over a period of 15 minutes. While

this ramp is in effect,

  

   PULLDN  LEVEL = XXX%;  SETP = XXX%;   ACTUAL = XXX% 

      

is

one of the scrolled messages under the 

DISPLAY DATA

key. “PULLDN LEVEL” is the ramping setpoint that will

ramp up to the programmed setpoint “SETP”.  “SETP”

is the level setpoint programmed by the service techni-

cian. “ACTUAL” is the present refrigerant level in the

condenser. After the 15 minute pulldown period has

elapsed, this message is replaced by
  

 

ACTUAL  LEVEL = XXX%;   LEVEL  SETP = XXX%  

   

.

If the actual level is greater than the setpoint when the

VMS opens, there is no pulldown period, it immediately

begins to control to the programmed setpoint.

While the chiller is running, the refrigerant level is nor-

mally controlled to the level setpoint. However, any-

time the vanes fully close (VMS closes), normal level

control is terminated, any refrigerant level setpoint

pulldown in effect is cancelled and the outputs to the

level control will be opposite that which is supplied to

the vane motor (i.e., when a close pulse is applied to

the vane motor, an open pulse is applied to the level

control, etc.). When the VMS opens, if the refrigerant

level is less than the level setpoint, a refrigerant level

setpoint pulldown is initiated as described above. Oth-

erwise, the level is controlled to the programmed set-

point.

If the refrigerant level sensor output ever goes to greater

than 4.4VDC, indicating a level greater than 100%,
 

  

WARNING-REFRIGERANT  LEVEL  OUT  OF  RANGE  

    

is dis-

played and the level control actuator is driven open

until the level has decreased to a level within range.

When within range, the warning message is automati-

cally cleared and normal control is resumed.

OPTIONAL SERVICE ISOLATION VALVES

If your chiller is equipped with optional service isola-

tion valves on the discharge and liquid line, these valves

must remain open during operation. These valves are

used for isolating the refrigerant charge in either the

evaporator or condenser to allow service access to the

system. A refrigerant pump-out unit will be required to

isolate the refrigerant.

CAUTION: Isolation of the refrigerant in this sytem

must be performed by a qualified service

technician.

OPTIONAL HOT GAS BYPASS

Hot gas bypass is optional and is used to eliminate

compressor surge during light load or high head op-

eration. The hot gas control panel will automatically

modulate the hot gas valve open and closed as re-

quired. Adjustment of the hot gas control valve must

be performed by a qualified service technician follow-

ing the Hot Gas Set-up procedure.

NOTE: Changes in chilled water flow will require re-

adjsutment of the hot gas control to insure

proper operation.

MICROCOMPUTER CONTROL CENTER
(See Section 2)

The MicroComputer Control Center is factory mounted,

wired and tested. The electronic panel automatically

controls the operation of the unit in meeting system

cooling requirements while minimizing energy usage.

For detailed information on the Control Center, refer to

“Section 2” of this manual.

SOLID STATE STARTER (Optional)

The Solid State Starter is a reduced voltage starter that

controls and maintains a constant current flow to the

motor during start-up. It is mounted on the chiller. Power

and control wiring between the starter and chiller are

factory installed. Available for 380-600 volts, the starter

enclosure is NEMA-1 with a hinged access door with

lock and key. Electrical lugs for incoming power wiring

are provided.

VARIABLE SPEED DRIVE (Optional)

A 460V – 3-Ph – 60/50Hz Variable Speed Drive can be

factory packaged with the chiller. It is designed to vary

the compressor motor speed and prerotation vane po-

sition by controlling the frequency and voltage of the

electrical power to the motor. Operational information

is contained in Form 160.00-O1. The control logic au-

tomatically adjusts motor speed and compressor

prerotation vane position for maximum part load effi-

ciency by analyzing information fed to it by sensors

located throughout the chiller.

Содержание MILLENNIUM YK

Страница 1: ...ELECTRO MECHANICAL STARTER SOLID STATE STARTER VARIABLE SPEED DRIVE WARNING SYSTEM CONTAINS REFRIGERANT UNDER PRESSURE SERIOUS INJURY COULD RESULT IF PROPER PROCEDURES ARE NOT FOLLOWED WHEN SERVICING...

Страница 2: ...Maintenance 43 SECTION 6 Trouble Shooting 45 SECTION 7 Maintenance 50 SECTION 8 Preventive Maintenance 59 Page REFERENCE INSTRUCTIONS DESCRIPTION FORM NO Solid State Starter Operation Maintenance 160...

Страница 3: ...B DC DD EB EC ED FB FC FD GB GC GD HB HC HD JB JC JD TB TC TD VB VC VD COOLER CODE CB CC CD CE DB DC DD DE FB FC FD GB GC GD GF GH HB HC HF HH JF JG JH TF TG TH VF VH WF WH MODEL MOTOR CODE 60 HZ 50 H...

Страница 4: ...s applied with an electro mechanical starter YORK Solid State Starter optional or Variable Speed Drive optional In operation a liquid water or brine to be chilled flows through the cooler where boilin...

Страница 5: ...r components of a chiller are selected for full load capacities therefore capacity must be controlled to maintain a constant chilled liquid temperature leav ing the cooler Prerotation vanes PRV locate...

Страница 6: ...Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever action may be required to correct the inte...

Страница 7: ...EVAPORATOR AND CONDENSER DISCHARGE TEMPERATURE OIL TEMPERATURE HIGH LOW OIL PRESSURE TRANSDUCER PRESSURE SOLID STATE STARTER MOTOR CURRENT VOLTS When Supplied CONDENSER REFRIGERANT LEVEL The system s...

Страница 8: ...VICE 1 Service allows manual PRV control with visual display readout of PRV operation 2 Local allows manual compressor start from the COMPRESSOR switch on the Control Center front 3 Program allows ope...

Страница 9: ...the differential pressure The offset pressure calculation will not be performed if either transducer is out of range The offset value will be taken as 0 PSI in this instance To Display OPTIONS This k...

Страница 10: ...mmed by the system operator The Setpoints keys are located on the Control Center keypad see Fig 3 To program see Programming System Setpoints page 14 The following is a description of these setpoints...

Страница 11: ...ming week are holidays On those designated days the chiller will automatically start and stop via the holi day start and stop times programmed in the DAILY SCHEDULE setpoint It will do this one time o...

Страница 12: ...erator programmed The value displayed in the REMOTE mode is that which has been pro grammed by the Energy Management System via the remote current limit setpoint input If chiller is equipped with a YO...

Страница 13: ...age REMOTE RESET TEMP RANGE 10 F or REMOTE RESET TEMP RANGE 20 F To Display DATA LOGGER setpoints Refer to YORK Form 160 49 N2 for operation of this key To Display UNDERVOLTAGE setpoints Solid State S...

Страница 14: ...THORIZED is displayed NOTE Unless terminated by pressing the AC CESS CODE key again the operator will have access to the PROGRAM key for 10 minutes When 10 minutes have elapsed access to PROGRAM key w...

Страница 15: ...MODE SELECT SETPOINT message is displayed To Enter CURRENT LIMIT Setpoint Electro Mechanical Starter refer to Fig 7 1 Press and release CURRENT LIMIT setpoint key The following program prompt message...

Страница 16: ...y PROGRAM MODE SELECT SETPOINT message is displayed To Enter CLOCK Setpoint Refer to Fig 9 1 Assure Micro Board Program jumper J57 is in CLKON position 2 Press and release CLOCK setpoint key The follo...

Страница 17: ...desired hours and minutes stop time e If necessary press the AM PM key to change AM to PM or vice versa 3 Press and release ADVANCE DAY SCROLL key The following prompt message is displayed MON START X...

Страница 18: ...R key PROGRAM MODE SELECT SETPOINT message is displayed To cancel all of the designated holidays perform Step 1 press CANCEL key and then press ENTER key PROGRAM MODE SELECT SETPOINT message is displa...

Страница 19: ...13 KEYPAD SERVICE KEYS LOCATION SERVICE KEYS LD00963 HOLD Press and release this key to hold the pre rotation vanes in their present position If the chiller is running SYSTEM RUN VANES HOLDING is dis...

Страница 20: ...o reset any safety shutdown mes sage press WARNING RESET key in SERVICE mode with the COMPRESSOR switch in the STOP RESET position MANUAL OIL PUMP This key is operational in any mode Press and release...

Страница 21: ...celled or NO 2 ACTUAL LEVEL XXX LEVEL SETP XXX Displays the actual refrigerant level in the condenser and the refrigerant level setpoint programmed by the service technician This message replaces the...

Страница 22: ...MODE IN EFFECT is displayed If the Control Center is in SERVICE mode SERVICE OPERATING MODE IN EFFECT is displayed To change operating mode proceed as follows 1 Press ACCESS CODE key 2 ENTER VALID ACC...

Страница 23: ...lue the vanes will be driven closed not fully closed only far enough to allow the current to decrease to a value less than 104 of the operator programmed XXX FLA cur rent limit For example With the op...

Страница 24: ...rises to 28 PSIG 193 kPa R 134a the vanes will be per mitted to open Low pressure limit feature is not used when program jumper JP3 is cut Brine application SYSTEM RUN HIGH PRESSURE LIMIT IN EFFECT Di...

Страница 25: ...wn The flow switch is checked 25 seconds into Start Sequence Initiated and continuously thereafter MON XX XX AM SYSTEM CYCLING AUTOSTART A remote command computer relay contact or manual switch connec...

Страница 26: ...ut out settings will vary with the brine applica tion To restart the chiller wait until the safety contacts close press the COMPRESSOR switch to the STOP RESET position and then to the START position...

Страница 27: ...arge tem perature has increased to 220 F 104 C The system will be allowed to restart when the temperature has decreased to 219 F 103 C Temperature is sensed by a thermistor RT2 To restart the chiller...

Страница 28: ...r JP4 removed this period is extended to allow for a longer coastdown time EPROM version C 02F T 11 provides a 6 minute coastdown period EPROM version C 02F T 12 or later provides a 10 minute coastdow...

Страница 29: ...T position and then to the START position MON XX XX AM PROX SENSOR SAFETY SHUTDOWN The chiller is shut down because the Proximity Tem perature Sensor has detected that the distance be tween the compre...

Страница 30: ...orientation orientation notch must be UP Refer to Fig 14 MON XX XX AM OPEN DRAIN TEMP THERMOCOUPLE The chiller is shut down because the Proximity Tem perature Sensor thermocouple or high speed drain...

Страница 31: ...not start if the oil is less than 71 F 22 C If not possible the compressor oil should be drained and new oil must be charged into the oil sump See Charging Unit With Oil page 44 2 Oil Pump To check pr...

Страница 32: ...for a 50 sec ond pre run to establish oil flow and adequate lu brication to all bearings gears and rotating sur faces within the compressor The high and low oil pressure transducers OP and the oil te...

Страница 33: ...he Control Center as MON 10 30 AM LOW WATER TEMPERATURE AUTOSTART This occurs when the leaving water temperature falls to 4 F 2 2 C below setpoint or 36 F 2 2 C whichever is higher The LWT is part of...

Страница 34: ...erating condi tions temperatures and pressures recorded at regu lar intervals throughout each 24 hour operating period should be kept An optional status printer is available for this purpose or Fig 16...

Страница 35: ...ondenser saturation temperature based upon condenser pressure sensed by the condenser transducer Press the DISPLAY DATA key This key may be depressed repeatedly after depressing the DISPLAY HOLD key t...

Страница 36: ...Low Evaporator Pressure Low Oil Pressure High Oil Flow High Condenser Pressure Evaporator Transducer or Probe Error High Discharge Temp High Oil Temp Oil Pressure Transducer Starter Malfunction Detect...

Страница 37: ...ng temperatures are encountered while the system is idle carefully drain the cooling water from the cooling tower condenser condenser pump and the chilled water system chilled water pump and coils Ope...

Страница 38: ...COOLER OIL RESERVOIR PUMP 28778A FRONT VIEW SIGHT GLASS REFRIGERANT CHARGING VALVE 28815A COOLER MOTOR ADAPTER MOTOR SUPPORT COVER MICROCOMPUTER CONTROL CENTER SUCTION DUAL RELIEF VALVES VARIABLE SPE...

Страница 39: ...pump oil filter oil cooler and all interconnecting oil piping and passages There are main points within the motor com pressor which must be supplied with forced lubrication as follows 1 COMPRESSOR DRI...

Страница 40: ...40 YORK INTERNATIONAL FIG 18 SCHEMATIC DRAWING YK COMPRESSOR LUBRICATION SYSTEM LD03278...

Страница 41: ...HANGERS Evaporator and condenser shells are fabricated from rolled carbon steel plates with fusion welded seams Heat exchanger tubes are internally enhanced type The evaporator is a shell and tube flo...

Страница 42: ...ared and normal control is resumed OPTIONAL SERVICE ISOLATION VALVES If your chiller is equipped with optional service isola tion valves on the discharge and liquid line these valves must remain open...

Страница 43: ...drator to the compressor sump CHANGING THE DEHYDRATOR To change the dehydrator use the following procedure 1 Shut the stop valves on the condenser gas line oil return line to rotor support and inlet...

Страница 44: ...valve A located on the remote oil reservoir cover plate See Fig 20 Do not tighten the connection at the charging valve until after the air is forced out by pumping a few strokes of the oil pump This f...

Страница 45: ...remote com Automatic Restart Contact connected to Cycling mand computer upon remote the Remote Local relay contact or command cycling input of the manual switch Digital input board MON 10 00 AM Multi...

Страница 46: ...n RS1 LCWT minus satu tor RS1 ration temperature is less than 2 5 F or greater than 25 F Checked every 10 minutes following a 10 min bypass at start up MON 10 00 AM Motor Con CM2 or Solid Reset the de...

Страница 47: ...r Check motor starter Malfunction 15 for 10 swc STOP RESET operation Motor current Detected with Control Cen switch and then value greater than 15 ter not calling for FLA motor to run MON 10 00 AM Pro...

Страница 48: ...n normal with normal discharge temperature Temperature of chilled water too low with Insufficient load for Check prerotation vane motor opera with low motor amperes system capacity tion and setting of...

Страница 49: ...ALLY DECREASES Noted by Observation of Daily Log Sheets Oil pressure noted when pressing OIL Oil filter is dirty Change oil filter PRESSURE display key drops to 70 of oil pressure when compressor was...

Страница 50: ...or can be used to detect any leaks too small to be found by the soap test To test with R 22 proceed as follows 1 With no pressure in the system charge R 22 gas into the system through the charging val...

Страница 51: ...t the vacuum pump leaving the vacuum indicator in place 6 Hold the vacuum obtained in Step 3 in the system for 8 hours the slightest rise in pressure indicates a leak or the presence of moisture or bo...

Страница 52: ...to be tight prior to evacuation then the saturation tem perature recordings should follow a curve similar to the typical saturation curve shown as Fig 22 The temperature of the water in the test tube...

Страница 53: ...urnished in cylinders contain ing either 30 50 125 or 1750 lbs 207 345 862 or 12 066 kg of refrigerant TABLE 4 REFRIGERANT CHARGE CHECKING THE REFRIGERANT CHARGE DURING UNIT SHUTDOWN The refrigerant c...

Страница 54: ...enser or evaporator compressor while making any necessary repairs While the main disconnect switch and compressor motor starter are open meg the motor as follows 1 Using a megohm meter megger meg betw...

Страница 55: ...FORM 160 52 O1 55 YORK INTERNATIONAL FIG 24 MOTOR STATOR TEMPERATURE AND INSULATION RESISTANCES LD00476 TEMPERATURE F MEGOHMS Minimum Insulation Resistance vs Temperature per IEEE Std 43 Open Motors...

Страница 56: ...time accompanied by a steady rise in con densing temperature and noisy operation These symp toms may also be due to foul gas buildup Purging will remove the foul gas revealing the effect of fouling TU...

Страница 57: ...ube heads and the ends of all tubes with water NOTE Do not use carbon tetrachloride for this pur pose since its fumes give the same flame discoloration that the refrigerant does 3 With nitrogen or dry...

Страница 58: ...or Low Oil Pressure OP change the oil filter element Examine the oil filter element for the pres ence of aluminum particles Aluminum gas seal rings can contact the impeller and account for some alumi...

Страница 59: ...he unit should be leak tested quarterly Any leaks found must be repaired immediately COOLER AND CONDENSER The major portion of maintenance on the condenser and cooler will deal with the maintaining th...

Страница 60: ...controls operation and safety not be changed If the set tings are changed without YORK s approval the warranty will be jeopardized 3 A 5 11 year life battery is part of the RTC Real Time Clock To repl...

Отзывы: