FORM 160.52-O1
15
YORK INTERNATIONAL
FIG. 6
KEYPAD PROGRAMMING LEAVING
CHILLED WATER TEMP SETPOINT
FIG. 7
KEYPAD PROGRAMMING % CURRENT
LIMIT SETPOINT
LD00955
LD00956
To enter
CHILLED LIQUID TEMP
Setpoint: (Refer to
Fig. 6.)
1. Press and release
CHILLED LIQUID TEMP
setpoint
key. The following program prompt message will be
displayed:
LEAVING SETPOINT = XX.X °F (BASE)
(BASE) refers to the base or lowest setpoint avail-
able to an Energy Management System. If any En-
ergy Management System is applied, this value must
be entered into the Energy Management System.
Refer to previous explanation or
REMOTE/RESET
TEMP RANGE,
page 11.
2. Use
ENTRY
keys to enter desired value.
3. Press and release
ENTER
key.
PROGRAM MODE, SELECT SETPOINT
message is displayed.
To Enter
% CURRENT LIMIT
Setpoint:
(
Electro-Mechanical Starter,
refer to Fig. 7)
1. Press and release
% CURRENT LIMIT
setpoint key.
The following program prompt message is displayed:
CURRENT LIMIT = XXX% FLA
2. Use
ENTRY
keys to enter desired value.
3. Press and release
ENTER
key.
PROGRAM MODE, SELECT SETPOINT
message is displayed.
(
Solid State Starter,
refer to Fig. 7)
1. Press and release
% CURRENT LIMIT
setpoint key.
The following program prompt message is displayed:
CURRENT LIMIT = XXX% FLA; MTR CUR = _ _ _ FLA
2. Use
ENTRY
keys to enter desired value.
NOTE: Motor Current FLA value is entered by
YORK factory and checked at system start-
up. It cannot be changed without special
access code. (Note to service technician:
refer to Programming Instructions in Ser-
vice instruction, Form 160.49-M2.
3. Press and release
ENTER
key.
PROGRAM MODE, SELECT SETPOINT
message is displayed.