Manual Refrigerant Level Control:
OPEN
Press and release this key to drive the refrig-
erant level control valve open. If the chiller is running,
SYSTEM RUN LEVEL VALVE OPENING
is displayed. If
chiller is not running,
SYS READY TO START LEVEL VALVE OPENING
is dis-
played. The refrigerant level control valve will continue
to open until the
CLOSE
,
HOLD
, or
AUTO
keys are
pressed and released.
HOLD
Press and release this key to hold the refrig-
erant level control valve in its present position. If the
chiller is running,
SYSTEM RUN LEVEL VALVE HOLDING
is displayed. If chiller is not running,
SYS READY TO START LEVEL VALVE HOLDING
is displayed.
The refrigerant level control valve will remain station-
ary until the
OPEN
,
HOLD
, or
AUTO
keys are pressed
and released.
CLOSE
Press and release this key to drive the re-
frigerant level control valve closed. If the chiller is run-
ning,
SYSTEM RUN LEVEL VALVE CLOSING
is displayed. If
chiller is not running,
SYS READY TO START LEVEL VALVE CLOSING
is displayed.
When the refrigerant level control valve is fully closed,
SYS READY TO START LEVEL CLOSED
is displayed. The
refrigerant level control valve will continue to close un-
til the
OPEN
,
HOLD
, or
AUTO
keys are pressed.
AUTO
Press and release this key to return the refrig-
erant level control valve to automatic operation.
Manual Oil Pump Speed Control:
OPEN
Press and release this key with manual op-
eration of the oil pump will increase the VSD oil pump
speed by .5Hz.
CLOSE
Press and release this key with manual op-
eration of the oil pump will decrease the VSD oil pump
speed by .5Hz.
HOLD
Press and release this key will allow the VSD
oil pump to be driven to a specific pre-determined fre-
quency.
AUTO
Press and release this key to return VSD oil
pump to automatic operation.
OTHER SERVICE KEYS
WARNING RESET
Press and release this key to re-
set any WARNING or STATUS message that can
be reset with this key, unless the condition still exists.
To reset any cycling or warning message, place the
Control Center in
SERVICE
mode and press
WARN-
ING RESET
key. To reset any safety shutdown mes-
sage, press
WARNING RESET
key in
SERVICE
mode
with the
COMPRESSOR
switch in the
STOP/RESET
position.
MANUAL OIL PUMP
This key is operational in any
mode. Press and release this key to run the oil pump.
Press and release the key again to stop the oil pump.
A 10-minute maximum is imposed on the running of
the oil pump (i.e. the oil pump will automatically shut
off after 10 minutes). If a longer running time is de-
sired, the key must be pressed again. The manual oil
pump feature is disabled during START SEQUENCE
INITIALIZED to allow for auto-zeroing of oil pressure
transducers.
DISPLAY DATA
This key is operational in any three
of the Control Center modes of operation (
SERVICE
,
LOCAL
or
REMOTE
). It is used to display certain sys-
tem operating parameters that are relevant to trouble-
shooting the chiller system.
Press and the
DISPLAY DATA
key. The following mes-
sages will sequentially scroll on the display. Each mes-
sage will be displayed for 2 seconds.
NO. 1
MANUAL VANE OPERATION ALLOWED
Displayed when
the
PRE-ROTATION VANES
service keys have been
selected for manual VANE control. This allows these
keys to manually control the vanes in
Service
mode.
The procedure to select manual vanes control is in Ser-
vice manual, Form 160.49-M3 and should be performed
only by a qualified service technician.
or
NO. 1
MANUAL LEVEL CONTROL ALLOWED
Displayed when
the
PRE-ROTATION VANES
keys have been selected
for manual REFRIGERANT LEVEL control. This allows
these keys to manually control the refrigerant level con-
trol variable orifice in
Service
mode. When manual re-
frigerant level control is selected, the pre-rotation vanes
Service
keys cannot be used to control the vanes. The
procedure to select manual refrigerant level control is
in Service manual, Form 160.49-M3 and should be
performed only by a qualified service technician.
or
NO.1
MANUAL OIL PUMP SPEED CONTROL ALLOWED
Displayed
when the
PRE-ROTATION VANES
keys have been
selected for manual VSD OIL PUMP SPEED control.
This allows these keys to manually control the VSD oil
pump speed during manual oil pump operation in
Ser-
vice
mode. When manual oil pump speed control is
selected, the pre-rotation vanes
Service
keys cannot
be used to control the vanes. The procedure to select