62
YORK INTERNATIONAL
SECTION 6
TROUBLE SHOOTING
TABLE 2
CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE
MICROCOMPUTER CONTROL CENTER DISPLAY
SHUTDOWN CAUSE CONTROL CENTER DISPLAY
GOVERNING CONTROL FUNCTION
DAY OF
TIME
CAUSE OF
METHOD OF
DESCRIPTION
OPERATING POINT
WEEK
OF DAY
SHUTDOWN
RESTART
ON RISE
ON FALL
MON.
10:00 AM
Low Water
Autostart
Low Water (LWT)
Chilled water
4°F below chilled
Temperature
setpoint
water setpoint
MON.
10:00 AM
Flow Switch
Manual
Flow Switch
MON.
10:00 AM
System Cycling
Autostart
A remote command
(computer relay contact or
manual switch)
MON.
10:00 AM
Multi-Unit Cycling
Autostart
(Optional)
Lead-Lag Sequence Control
MON.
10:00 AM
Internal Clock
Autostart
Internal Clock
Remote Stop
Energy Management System
MON.
10:00 AM
Low Evap. Press.
Manual
Low Evap. Pressure
25 PSIG (R-134A)
25.1 PSIG (R-134A)
Transducer (LEP)
MON.
10:00 AM
Low Evap. Press.
Manual
LEP external control
Set to Job Spec.
Set to Job Spec.
Brine
(Brine units only)
MON.
10:00 AM
Low Oil
Manual
Low Oil Pressure
25 PSID
15 PSID
Pressure
Transducer (OP)
MON.
10:00 AM
High Pressure
Manual
High Pressure
180 PSIG (R-134A)
120 PSIG (R-134A)
Safety Control (HP)
MON.
10:00 AM
Evap. Trans
Manual
Evap. Pressure Transducer
or Probe Error
or Leaving Chilled Water
Thermistor (RS1)
MON.
10:00 AM
High Discharge
Manual
Discharge Temperature
220°F
219°F
Temperature
Thermistor (RT2)
MON.
10:00 AM
High Oil
Manual
Oil Temperature
170°F
169°F
Temperature
Thermistor (RT3)
MON.
10:00 AM
Power
Manual
Micro Board undervoltage
8.29 VDC
7.84 VDC
Failure
circuit on 5V unregulated
supply
MON.
10:00 AM
High Oil
Manual
Compressor
100 PSID (during first 7
59 PSID
Pressure
Oil Pressure
minutes of compressor
Differential
operation); 60 PSID
after first 7 minutes of
compressor operation)
Vane Motor
Autostart
Vane Motor Switch
Switch Open
MON.
10:00 AM
Program Initiated
Autostart
Micro Board
Reset
Replace RTC-IC Chip
RTC-IC Chip
Reprogram Setpts.
Thermistor (RT3)
MON.
10:00 AM
Low Oil
Autostart
Oil Temperature
71.0°F
55°F
Temperature
Thermistor (RT3)
MON.
10:00 AM
Faulty Discharge
Manual
Discharge Temp. Thermistor
30.0°F
29.9°F
Temp. Sensor
(RT2) disconnected or faulty .
(min system oper. temp. = 32°F)