
24
YORK INTERNATIONAL
SERVICE INTERVAL
This key shows engine setpoint
and compressor setpoint hours. Along with the hours re-
maining before the engine/compressor is due for serv-
ice. (See page 30).
DAILY SCHEDULE
This key displays the programmed
daily start and stop times, from Sunday through Satur-
day plus Holiday. If desired, the Control Center can be
programmed to automatically start and stop the chiller
as desired. This schedule will repeat on a 7-day calendar
basis. If the Daily Schedule is not programmed, the de-
fault value is 00:00 AM start and stop times for all days of
the week and the holiday. (Note that the system will not
automatically start and stop on a daily basis with these
default values because 00:00 is an Impossible time for
the Micro Board. See Programming System Setpoints,
page 27). Finally, one or more days in the week can be
designated as a holiday (See description under
HOLI-
DAY
setpoint) and the Control Center can be programmed
(using
DAILY SCHEDULE
setpoint) to automatically start
and stop the chiller on those days so designated. The
operator can override the time clock at any time using
the
COMPRESSOR
switch.
NOTE: If only a start time is entered for a particular
day, the compressor will not automatically stop
until a scheduled stop time is encountered
on a subsequent day.
HOLIDAY
This key indicates which days in the upcom-
ing week are holidays. On those designated days, the
chiller will automatically start and stop via the holiday
start and stop times programmed in the
DAILY SCHED-
ULE
setpoint. It will do this one time only and the follow-
ing week will revert to the normal daily schedule for that
day.
REMOTE/RESET TEMP RANGE
This key displays the
maximum offset of remote LCWT setpoint reset. This off-
set is either 10° or 20°F as programmed. When in the
remote mode, this value is added to the operator pro-
grammed chilled liquid temp setpoint and the sum equals
the temperature range in which the LCWT can be reset.
For example, if the operator programmed
REMOTE/RE-
SET TEMP RANGE
is programmed with a value of 10°F,
then the chilled liquid temp setpoint can be remotely re-
set over a range of 46°F to 56°F (46 + 10 = 56). If not
programmed, the default value for this parameter is 20°F.
For additional information on remote LCWT reset, refer to
Form 160.60-PW3 or 160.66-PW3.
NOTE: If an Energy Management System is inter-
faced to the Control Center for the purpose
of remote LCWT setpoint reset, then the op-
erator programmed
REMOTE RESET TEMP
RANGE
value determines the maximum value
of temperature reset controlled by the En-
ergy Management System.
DATA LOGGER
This key is used when an optional
printer is connected to the MicroComputer Control Cen-
ter. Refer to Form 160.60-N2 for operation instructions.
DISPLAYING SYSTEM SETPOINTS
The currently programmed Setpoint values can be viewed
at any time (See page 37) in
SERVICE
,
LOCAL
or
REMOTE
operating mode as follows:
Press and
release
the appropriate
SETPOINT
key
the message will be displayed for 2 seconds.
- or -
Press and
hold
the appropriate
SETPOINT
key
the message will be displayed as long as the key is
pressed.
- or -
Press and
release
the appropriate
SETPOINT
key,
then press and release the
DISPLAY HOLD
key.
The message will be displayed until the
DISPLAY
HOLD
key is again pressed and released, or 10 min-
utes have elapsed, whichever comes first.
To Display
CHILLED LIQUID TEMP
Setpoint:
Use
CHILLED LIQUID TEMP
setpoint key as described
on page 23 to produce the following message:
LEAVING SETPOINT = XX.X°F
NOTE: The value displayed is the actual LCWT
setpoint. For example, the value displayed in
LOCAL
or
PROGRAM
modes is that which
is operator programmed. The value displayed
in the
REMOTE
mode is that base setpoint
with added temperature reset by an Energy
Management System, via remote LCWT
setpoint (PWM signal) if a remote reset sig-
nal were received within 30 minutes.
To Display
% ENGINE LOAD LIMIT
Setpoint:
Use
% ENGINE LOAD LIMIT
setpoint key as described
above to produce the following message:
ENGINE LOAD LIMIT = XXX%
NOTE: The value displayed is the actual % engine
load limit setpoint. For example, the value
displayed in
LOCAL
or
PROGRAM
mode
is that which is operator programmed. The
value displayed in the
REMOTE
mode is
that which has been programmed by the En-
ergy Management System via the remote
engine limit setpoint input.