KEYPAD SERVICE KEYS LOCATION
SERVICE KEYS
The
SERVICE
keys are provided for the service tech-
nicians use when performing routine maintenance or when
troubleshooting the system. The
WARNING RESET
and
PREROTATION VANES/ENGINE SPEED
keys are en-
abled in
SERVICE
mode only. The remainder of the
SER-
VICE
keys are enabled in
SERVICE
,
LOCAL
or
RE-
MOTE
mode.
REFRIGERANT LEVEL CONTROL
1. Description
2. Automatic operation
3. Manual Operation
4. Fixed Position Operation
(Refer to the YORK Service manual on setting the pa-
rameters in this section.)
The subject chillers can now be ordered with an optional
condenser refrigerant level control consisting of:
A. Level control actuator
B. Refrigerant level sensor, R134a - 025-31712-000
C. Refrigerant level control board, 031-01655-000
The refrigerant level sensor senses the actual refrigerant
level in the condenser and outputs an analog voltage to
the micro board that represents this level. During unit
run, the micro board modulates the refrigerant level ac-
tuator that is connected to the variable orifice to maintain
the condenser refrigerant level to the setpoint level pro-
grammed into the MicroComputer Control Center by the
field service technician.
The refrigerant level sensor outputs a voltage from TB-3
over the range of 0.24VDC to 4.31VDC corresponding to
a level of 0% to 100%. At the end of each
level control
period
(programmable from 1.0 to 5.0 seconds), the mi-
cro board drives the close output (J10-1) or open output
(J10-3) to <1 VDC for an appropriate number of seconds
to turn on the close or open triac driver on the refrigerant
level control board. When the appropriate triac turns on,
it shorts the close (2) or open (3) coil of the level control
actuator to common terminal (X). This causes the ac-
tuator to turn in the desired direction to open or close the
refrigerant level valve.
AUTOMATIC OPERATION
The entire chiller run time is divided into
level control
periods.
The
level control period
is programmable over
the range of 1.0 to 5.0 seconds. Upon entering system
run, the level control period timer is started. When it has
elapsed, it is again initiated. Each time the level control
period has elapsed, it is restarted.