YORK INTERNATIONAL
To Display
DATA LOGGER
setpoints:
Refer to YORK Form 160.60-N2 for operation of this key.
Example of Printout from Data Logger.
YORK SYSTEM 1 UPDATE
c 1995 YORK INTERNATIONAL CORP.
VERSION C.04F.00
TODAY IS THU 11:37AM 03/14/96
SYSTEM RUN LEAVING TEMP CONTROL
LEAVING CHILLED WATER TEMP = 51.5 F
RETURN CHILLED WATER TEMP = 57.4 F
LEAVING CONDENSER WATER TEMP = 82.2 F
RETURN CONDENSER WATER TEMP = 78.9 F
EVAPORATOR SATURATION TEMP = 50.2 F
CONDENSER SATURATION TEMP = 84.0 F
DISCHARGE TEMPERATURE = 100.2 F
OIL TEMPERATURE = 114.6 F
EVAPORATOR PRESSURE = 45.8 PSIG
CONDENSER PRESSURE = 93.7 PSIG
HIGH OIL PRESSURE = 79.4 PSIG
LOW OIL PRESSURE = 39.9 PSIG
OIL PRESSURE DIFFERENTIAL = 40.6 PSID
LEAVING CHILLED H20 SETPOINT = 51.0 F
REMOTE TEMP SETPOINT RANGE = 20.0 F
COMPRESSOR OIL PUMP ON
CHILLED WATER PUMP ON
VENT LINE VALVE ON
RETURN OIL SOLN VALVE ON
HIGH SPEED THRUST VALVE ON
REMOTE READY TO START OFF
SAFETY SHUTDOWN RELAY OFF
CYCLING SHUTDOWN RELAY OFF
PROXIMITY SENSOR POSITION = 66 MILS
PROXIMITY SENSOR REFERENCE = 67 MILS
HIGH SPEED DRAIN TEMPERATURE = 126.1 F
LEVEL CONTROL POSITION = 20%
LEVEL CONTROL SETPOINT = 20%
ENGINE SPEED = 1647 RPM
ENGINE RPMS TARGET = 1640 RPM
ENGINE LOAD LIMIT = 85%
ENGINE LOADING = 53%
PERCENT VANES OPEN = 24%
PERCENT DAC OUTPUT = 58%
ENGINE OIL PRESSURE = 63.2 PSIG
ENGINE MANIFOLD PRESSURE = 13.4 PSIA
ENGINE JACKET WATER TEMP = 191.1 F
ENGINE SCAC TEMPERATURE = 83.8 F
ENGINE MACH NUMBER = 12.14
PRESSURE RATIO (DP/P) = 0.83
SURFACE SPEED CONTROL = ACTIVE
ENGINE LOAD -> (30 - 39%): 0.1 HRS
ENGINE LOAD -> (40 - 49%): 0.7 HRS
ENGINE LOAD -> (50 - 59%): 0.5 HRS
ENGINE LOAD -> (60 - 69%): 0.3 HRS
ENGINE LOAD -> (70 - 79%): 0.1 HRS
ENGINE LOAD -> (80 - 89%): 0.0 HRS
ENGINE LOAD -> (90 - 100%): 0.1 HRS
ENGINE MODEL = G3412
COMPRESSOR MODEL = H2
COMPRESSOR GEAR CODE = FH
PULLDOWN LIMIT SETPOINT = 40%
PULLDOWN LIMIT TIME SETPOINT = 20 MIN
PULLDOWN LIMIT TIME LEFT = 0 MIN
WTO AUTO PRINT INTERVAL = NOT PROGRAMMED
OPERATING HOURS = 32
START COUNT = 54
SUN START = 00:00AM, STOP = 00:00AM
MON START = 00:00AM, STOP = 00:00AM
TUE START
= 00:00AM, STOP = 00:00AM
WED START = 00:00AM, STOP = 00:00AM
THU START
= 00:00AM, STOP = 00:00AM
FRI START
= 00:00AM, STOP = 00:00AM
SAT START
= 00:00AM, STOP = 00:00AM
HOL START = 00:00AM, STOP = 00:00AM