York MaxE YK Скачать руководство пользователя страница 32

YORK INTERNATIONAL

FORM 160.73-O2 (605)

32

COMMERCIAL ACID CLEANING

In many major cities, commercial organizations now 
offer a specialized service of acid cleaning evaporators 
and condensers. If acid cleaning is required, YORK 
rec om mends the use of this type of organization. The 
Dow Industries Service Division of the Dow Chemical 
Com pa ny, Tulsa, Oklahoma, with branches in principal 
cit ies is one of the most reliable of these companies.

TESTING FOR EVAPORATOR AND CONDENSER 
TUBE LEAKS

Evaporator and condenser tube leaks in R-134a systems 
may result in refrigerant leaking into the wa ter circuit, 
or water leaking into the shell depending on the pres-
 sure levels. If refrigerant is leaking into the water, it 
can be de tect ed at the liquid head vents after a pe ri od 
of shut down. If water is leaking into the re frig er ant, 
sys tem capacity and effi ciency will drop off sharp ly. If 
a tube is leaking and water has entered the system, the 
evaporator and condenser should be valved off from 
the rest of the water circuit and drained im me di ate ly  to 
pre vent se vere rusting and corrosion. The refrigerant 
sys tem should then be drained and purged with dry ni-
 tro gen to prevent severe rusting and corrosion. If a tube 
leak is in di cat ed,  the  ex act lo ca tion of the leak may be 
de ter mined  as  fol lows:

  1. Remove the heads and listen at each section of tubes 

for a hiss ing sound that would indicate gas leakage. 
This will assist in locating the section of tubes to be 
fur ther  in ves ti gat ed.  If  the  prob a ble  lo ca tion  of  the 
leaky tubes has been de ter mined, treat that sec tion in 
the fol low ing  man ner  (if  the  lo ca tion is not defi   nite, 
all the tubes will re quire in ves ti ga tions).

 2. Wash off both tube heads and the ends of all tubes 

with water.

Do not use carbon tetrachloride for 
this pur pose since its fumes give the 
same fl ame dis col or a tion that the 
re frig er ant does. 

  3. With nitrogen or dry air, blow out the tubes to clear 

them of traces of re frig er ant laden moisture from the 
circulation water. As soon as the tubes are clear, a 
cork should be driven into each end of the tube. Pres-
surize the dry system with 50 to 100 PSIG (345 to 
690 kPa) of nitrogen. Repeat this with all of the oth er 
tubes in the sus pect ed  sec tion  or,  if  nec es sary,  with 
all the tubes in the evaporator or con dens er.  Allow 
the evaporator or con dens er  to  re main corked up to 
12 to 24 hours be fore pro ceed ing.  De pend ing  upon 
the amount of leak age, the corks may blow from the 
end of a tube, indicating the lo ca tion of the leak age. 
If not, if will be nec es sary to make a very thor ough 
test with the leak detector.

  4. After the tubes have been corked for 12 to 24 hours, 

it is recommended that two men working at both 
ends of the evaporator carefully test each tube – one 
man removing corks at one end and the other at the 
op po site end to remove corks and handle the leak 
de tec tor. Start with the top row of tubes in the sec-
 tion being investigated. Remove the corks at the ends 
of one tube simultaneously and insert the ex plor ing 
tube for 5 seconds – this should be long enough to 
draw into the detector any refrigerant gas that might 
have leaked through the tube walls. A fan placed at 
the end of the evaporator opposite the detector will 
as sure that any leakage will travel through the tube 
to the detector.

 5. Mark any leaking tubes for later identifi cation.

 6. If any of the tube sheet joints are leaking, the leak 

should be indicated by the detector. If a tube sheet 
leak is suspected, its exact location may be found 
by using a soap solution. A continuous buildup of 
bub bles around a tube indicates a tube sheet leak.

Maintenance

Содержание MaxE YK

Страница 1: ...CENTRIFUGAL LIQUID CHILLERS Supersedes 160 73 O2 1202 Form 160 73 O2 605 MODEL YK STYLE F R 134a COOLING ONLY WITH OPTIVIEWTM CONTROL CENTER FOR ELECTRO MECHANICAL STARTER SOLID STATE STARTER VARIABLE...

Страница 2: ...materials This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are...

Страница 3: ...NCLATURE YK CB CB P6 CM F MOTOR CODE 60 Hz 50 Hz CH CX 5CE 5CT CJ CY 5CF 5CU CK CZ 5CG 5CV CL CA 5CH 5CW CM CB 5CI 5CX CN DA 5CJ 5DA CP DB 5CK 5DB CR DC 5CL 5DC CS DD 5CM 5DD CT DE 5CN 5DE CU DF 5CO 5...

Страница 4: ...ystem and Fundamentals of Operation 6 SECTION 2 System Operating Procedures 9 SECTION 3 System Components Description 15 SECTION 4 Operational Maintenance 21 SECTION 5 Troubleshooting 23 SECTION 6 Mai...

Страница 5: ...M STARTER SOLID STATE STARTER 10 FIG 5 CHILLER STARTING SEQUENCE SHUTDOWN SEQUENCE VARIABLE SPEED DRIVE 11 FIG 6 LIQUID CHILLER LOG SHEETS 12 FIG 7 SYSTEM COMPONENTS 15 FIG 8 SCHEMATIC DRAWING YK COMP...

Страница 6: ...n external SECTION 1 DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION 00116vip CONDENSER CONTROL CENTER COMPRESSOR MOTOR EVAPORATOR FIG 1 MODEL YK MAXETM CHILLER SYSTEM OPERATION DESCRIPTION SEE FI...

Страница 7: ...ity for only a relatively small part of the time the unit is in operation CAPACITY CONTROL The major components of a chiller are selected for full load capacities therefore capacity must be controlled...

Страница 8: ...FORM 160 73 O2 605 8 FIG 2 REFRIGERANT FLOW THRU CHILLER PREROTATION VANES See Detail A SUCTION EVAPORATOR ELIMINATOR OIL COOLER LD00924 FLOW CONTROL ORIFICE SUB COOLER CONDENSER DISCHARGE BAFFLE DIS...

Страница 9: ...operated start the pump The Control Center will not allow the chiller to start unless chilled liquid ow is established through the unit A eld supplied chilled water ow switch is required If the chill...

Страница 10: ...rt to circulate oil for a 50 second pre run to establish oil ow and adequate lubrication to all bearings gears and rotating surfaces within the compressor The high and low oil pressure transducers OP...

Страница 11: ...current limit software function plus the 3 phase 100 solid state overload current limiter CM 2 on Electro Mechanical Starter applications or the Solid State Starter current Limit function will overrid...

Страница 12: ...ing condenser water temperature may be as much as 25 F 14 C colder than the standby return chilled water temperature Cooling tower fan cycling will normally provide adequate control of the entering co...

Страница 13: ...erant analysis NEED FOR MAINTENANCE OR SERVICE If the system is malfunctioning in any manner or the unit is stopped by one of the safety controls consult the Operation Analysis Chart Table 1 pages 23...

Страница 14: ...water from the cooling tower condenser condenser pump and the chilled water system chilled water pump and coils Open the drains on the evaporator and condenser liquid heads to assure complete drainage...

Страница 15: ...SECTION 3 SYSTEM COMPONENTS DESCRIPTION MOTOR EVAPORATOR COMPRESSOR SUCTION DUAL RELIEF VALVES SIGHT GLASS VARIABLE SPEED OIL PUMP CONTROL BOX REFRIGERANT CHARGING VALVE 00611vip FRONT VIEW FIG 7 SYS...

Страница 16: ...YORK INTERNATIONAL FORM 160 73 O2 605 16 FIG 7 SYSTEM COMPONENTS CONT D 28778A DISCHARGE LINE OIL COOLER OIL RESERVOIR PUMP REAR VIEW System Components Description...

Страница 17: ...d all interconnecting oil piping and passages There are main points within the motor compressor which must be supplied with forced lubri cation as follows 1 Compressor Drive Shaft Low Speed a Shaft se...

Страница 18: ...YORK INTERNATIONAL FORM 160 73 O2 605 18 LOW SPEED GEAR REAR BEARING DOUBLE BELLOWS SHAFT SEAL FIG 8 SCHEMATIC DRAWING YK COMPRESSOR LUBRICATION SYSTEM LD08577 System Components Description...

Страница 19: ...rcurrent transformers are furnished with all units HEAT EXCHANGERS Evaporator and condenser shells are fabricated from rolled carbon steel plates with fusion welded seams Heat exchanger tubes are inte...

Страница 20: ...refrigerant Isolation of the refrigerant in this sys tem must be performed by a quali ed service technician OPTIONAL HOT GAS BYPASS Hot gas bypass is optional and is used to eliminate compressor surge...

Страница 21: ...ducing the low pressure oil rich liquid to ow from the evaporator through the dehydrator to the compressor sump CHANGING THE DEHYDRATOR To change the dehydrator use the following pro cedure 1 Shut the...

Страница 22: ...mp discharge connection to the oil charging valve A located on the remote oil reservoir cover plate See Fig 10 Do not tighten the connection at the charging valve until after the air is forced out by...

Страница 23: ...ant into system greater than normal with high discharge Variable ori ce problem Remove obstruction temperature Temperature difference between leaving Evaporator tubes dirty or Clean evaporator tubes c...

Страница 24: ...SYMPTOM REDUCED OIL PUMP CAPACITY Oil pump pumping capacity Excessive end clearance Inspect and replace worn parts pump Other worn pump parts Partially blocked oil supply Check oil inlet for blockage...

Страница 25: ...ector can be used to detect any leaks too small to be found by the soap test To test with R 22 proceed as follows 1 With no pressure in the system charge R 22 gas into the system through the charging...

Страница 26: ...isconnect the vacuum pump leaving the vac uum indicator in place 6 Hold the vacuum obtained in Step 3 in the system for 8 hours the slightest rise in pressure indicates a leak or the presence of moist...

Страница 27: ...d found to be tight prior to evacuation then the saturation temperature recordings should follow a curve similar to the typical saturation curve shown as Fig 12 The temperature of the water in the tes...

Страница 28: ...iller model See Table 3 Charge the correct amount of refrigerant and record the level in the evaporator sight glass The refrigerant charge should always be checked and trimmed when the system is shut...

Страница 29: ...the condenser or evaporator compressor while making any necessary repairs While the main disconnect switch and compressor motor starter are open meg the motor as follows 1 Using a megohm meter megger...

Страница 30: ...ERNATIONAL FORM 160 73 O2 605 30 LD00476 FIG 14 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES Minimum Insulation Resistance vs Temperature per IEEE Std 43 Open Motors Maintenance TEMPERATURE F...

Страница 31: ...ead pressure over a period of time accompanied by a steady rise in condensing temperature and noisy operation These symptoms may also be due to foul gas buildup Purging will remove the foul gas reveal...

Страница 32: ...the ends of all tubes with water Do not use carbon tetrachloride for this purpose since its fumes give the same ame discoloration that the refrigerant does 3 With nitrogen or dry air blow out the tub...

Страница 33: ...lines passages or dirty oil lters If the unit is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil lter element Examine the oil lter element for the presence of alu minum...

Страница 34: ...re not supplied and bearings are designed for long life under standard conditions Frames 284T thru 587UZ are furnished with double shielded or open ball or roller bearings It is necessary to re lubric...

Страница 35: ...user to provide for proper water treatment to provide for a longer and more economical life of the equipment The following recommendation should be followed in determining the condition of the water...

Страница 36: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by YORK International Corporation 2005 ALL RIGHTS RESERVED Form 160 73 O2...

Отзывы: