York MaxE YK Скачать руководство пользователя страница 31

FORM 160.73-O2 (605)

31

YORK INTERNATIONAL

CONDENSERS AND EVAPORATORS

GENERAL

Maintenance of condenser and evaporator shells is im-
 por tant to provide trouble free operation of the chiller. 
The water side of the tubes in the shell must be kept 
clean and free from scale. Proper maintenance such as 
tube cleaning, and testing for leaks, is covered on the 
fol low ing  pages.

CHEMICAL WATER TREATMENT

Since the mineral content of the water circulated through 
evaporators and condensers varies with almost every 
source of supply, it is possible that the water be ing used 
may corrode the tubes or deposit heat re sis tant  scale  in 
them. Reliable water treatment com pa nies  are  available 
in most larger cities to supply a wa ter treating process 
which will greatly reduce the cor ro sive and scale form-
 ing  prop er ties of almost any type of water.

As a preventive measure against scale and corrosion and 
to prolong the life of evaporator and condenser tubes, a 
chemical analysis of the water should be made pref er a bly 
before the system is installed. A reliable water treat ment 
company can be consulted to determine wheth er water 
treatment is necessary, and if so, to fur nish the proper 
treatment for the particular water con di tion.

CLEANING EVAPORATOR AND CONDENSER TUBES

Evaporator

It is diffi cult to determine by any particular test wheth er 
possible lack of performance of the water evaporator 
is due to fouled tubes alone or due to a combination 
of trou bles. Trouble which may be due to fouled tubes 
is indicated when, over a period of time, the cooling 
ca pac i ty  de creas es  and  the  split  (temperature  differ-
ence between water leaving the evaporator and the 
refrigerant tem per a ture in the evaporator) increases. A 
gradual drop-off in cool ing capacity can also be caused 
by a gradual leak of refrigerant from the system or by a 
com bi na tion of fouled tubes and shortage of refrigerant 
charge. An ex ces sive quantity of oil in the evaporator 
can also con trib ute to erratic performance.

Condenser

In a condenser, trouble due to fouled tubes is usually 
indicated by a steady rise in head pressure, over a pe ri od 
of time, accompanied by a steady rise in con dens ing 
temperature, and noisy operation. These symp toms may 
also be due to foul gas buildup. Purging will re move the 
foul gas revealing the effect of fouling.

TUBE FOULING

Fouling of the tubes can be due to deposits of two types 
as fol lows:

 1. 

Rust or sludge

 – which fi nds its way into the tubes 

and accumulates there. This material usually does not 
build up on the inner tube surfaces as scale, but does 
interfere with the heat transfer. Rust or sludge can 
generally be removed from the tubes by a thor ough 
brushing process.

 2. 

Scale

 – due to mineral deposits. These deposits, even 

though very thin and scarcely detectable upon phys-
 i cal inspection, are highly resistant to heat trans fer. 
They can be removed most effectively by cir cu lat ing 
an acid solution through the tubes.

TUBE CLEANING PROCEDURES

Brush Cleaning of Tubes

If the tube consists of dirt and sludge, it can usually be 
removed by means of the brushing process. Drain the 
water sides of the circuit to be cleaned (cooling water 
or chilled water) remove the heads and thoroughly clean 
each tube with a soft bristle bronze or nylon brush. 

DO 

NOT USE A STEEL BRISTLE BRUSH

. A steel brush 

may damage the tubes.

Improved results can be obtained by admitting water into 
the tube during the cleaning process. This can be done by 
mounting the brush on a suitable length of 1/8" pipe with a 
few small holes at the brush end and con nect ing  the  other 
end by means of a hose to the water supply.

The tubes should always be brush cleaned before acid 
cleaning.

ACID CLEANING OF TUBES

If the tubes are fouled with a hard scale deposit, they 
may require acid cleaning. It is im por tant that before acid 
clean ing, the tubes be cleaned by the brushing pro cess 
de scribed above. If the relatively loose foreign material 
is removed be fore the acid cleaning, the acid so lu tion  will 
have less material to dis solve and fl ush from the tubes 
with the re sult that a more satisfactory clean ing job will 
be accomplished with a prob a ble  sav ing  of  time.

Acid cleaning should only be per-
 formed by an ex pert. Please consult 
your local water treatment rep re -
sen ta tive for as sis tance in removing 
scale buildup and pre ven ta tive main-
 te nance pro grams to elim i nate future 
prob lems.

6

Содержание MaxE YK

Страница 1: ...CENTRIFUGAL LIQUID CHILLERS Supersedes 160 73 O2 1202 Form 160 73 O2 605 MODEL YK STYLE F R 134a COOLING ONLY WITH OPTIVIEWTM CONTROL CENTER FOR ELECTRO MECHANICAL STARTER SOLID STATE STARTER VARIABLE...

Страница 2: ...materials This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are...

Страница 3: ...NCLATURE YK CB CB P6 CM F MOTOR CODE 60 Hz 50 Hz CH CX 5CE 5CT CJ CY 5CF 5CU CK CZ 5CG 5CV CL CA 5CH 5CW CM CB 5CI 5CX CN DA 5CJ 5DA CP DB 5CK 5DB CR DC 5CL 5DC CS DD 5CM 5DD CT DE 5CN 5DE CU DF 5CO 5...

Страница 4: ...ystem and Fundamentals of Operation 6 SECTION 2 System Operating Procedures 9 SECTION 3 System Components Description 15 SECTION 4 Operational Maintenance 21 SECTION 5 Troubleshooting 23 SECTION 6 Mai...

Страница 5: ...M STARTER SOLID STATE STARTER 10 FIG 5 CHILLER STARTING SEQUENCE SHUTDOWN SEQUENCE VARIABLE SPEED DRIVE 11 FIG 6 LIQUID CHILLER LOG SHEETS 12 FIG 7 SYSTEM COMPONENTS 15 FIG 8 SCHEMATIC DRAWING YK COMP...

Страница 6: ...n external SECTION 1 DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION 00116vip CONDENSER CONTROL CENTER COMPRESSOR MOTOR EVAPORATOR FIG 1 MODEL YK MAXETM CHILLER SYSTEM OPERATION DESCRIPTION SEE FI...

Страница 7: ...ity for only a relatively small part of the time the unit is in operation CAPACITY CONTROL The major components of a chiller are selected for full load capacities therefore capacity must be controlled...

Страница 8: ...FORM 160 73 O2 605 8 FIG 2 REFRIGERANT FLOW THRU CHILLER PREROTATION VANES See Detail A SUCTION EVAPORATOR ELIMINATOR OIL COOLER LD00924 FLOW CONTROL ORIFICE SUB COOLER CONDENSER DISCHARGE BAFFLE DIS...

Страница 9: ...operated start the pump The Control Center will not allow the chiller to start unless chilled liquid ow is established through the unit A eld supplied chilled water ow switch is required If the chill...

Страница 10: ...rt to circulate oil for a 50 second pre run to establish oil ow and adequate lubrication to all bearings gears and rotating surfaces within the compressor The high and low oil pressure transducers OP...

Страница 11: ...current limit software function plus the 3 phase 100 solid state overload current limiter CM 2 on Electro Mechanical Starter applications or the Solid State Starter current Limit function will overrid...

Страница 12: ...ing condenser water temperature may be as much as 25 F 14 C colder than the standby return chilled water temperature Cooling tower fan cycling will normally provide adequate control of the entering co...

Страница 13: ...erant analysis NEED FOR MAINTENANCE OR SERVICE If the system is malfunctioning in any manner or the unit is stopped by one of the safety controls consult the Operation Analysis Chart Table 1 pages 23...

Страница 14: ...water from the cooling tower condenser condenser pump and the chilled water system chilled water pump and coils Open the drains on the evaporator and condenser liquid heads to assure complete drainage...

Страница 15: ...SECTION 3 SYSTEM COMPONENTS DESCRIPTION MOTOR EVAPORATOR COMPRESSOR SUCTION DUAL RELIEF VALVES SIGHT GLASS VARIABLE SPEED OIL PUMP CONTROL BOX REFRIGERANT CHARGING VALVE 00611vip FRONT VIEW FIG 7 SYS...

Страница 16: ...YORK INTERNATIONAL FORM 160 73 O2 605 16 FIG 7 SYSTEM COMPONENTS CONT D 28778A DISCHARGE LINE OIL COOLER OIL RESERVOIR PUMP REAR VIEW System Components Description...

Страница 17: ...d all interconnecting oil piping and passages There are main points within the motor compressor which must be supplied with forced lubri cation as follows 1 Compressor Drive Shaft Low Speed a Shaft se...

Страница 18: ...YORK INTERNATIONAL FORM 160 73 O2 605 18 LOW SPEED GEAR REAR BEARING DOUBLE BELLOWS SHAFT SEAL FIG 8 SCHEMATIC DRAWING YK COMPRESSOR LUBRICATION SYSTEM LD08577 System Components Description...

Страница 19: ...rcurrent transformers are furnished with all units HEAT EXCHANGERS Evaporator and condenser shells are fabricated from rolled carbon steel plates with fusion welded seams Heat exchanger tubes are inte...

Страница 20: ...refrigerant Isolation of the refrigerant in this sys tem must be performed by a quali ed service technician OPTIONAL HOT GAS BYPASS Hot gas bypass is optional and is used to eliminate compressor surge...

Страница 21: ...ducing the low pressure oil rich liquid to ow from the evaporator through the dehydrator to the compressor sump CHANGING THE DEHYDRATOR To change the dehydrator use the following pro cedure 1 Shut the...

Страница 22: ...mp discharge connection to the oil charging valve A located on the remote oil reservoir cover plate See Fig 10 Do not tighten the connection at the charging valve until after the air is forced out by...

Страница 23: ...ant into system greater than normal with high discharge Variable ori ce problem Remove obstruction temperature Temperature difference between leaving Evaporator tubes dirty or Clean evaporator tubes c...

Страница 24: ...SYMPTOM REDUCED OIL PUMP CAPACITY Oil pump pumping capacity Excessive end clearance Inspect and replace worn parts pump Other worn pump parts Partially blocked oil supply Check oil inlet for blockage...

Страница 25: ...ector can be used to detect any leaks too small to be found by the soap test To test with R 22 proceed as follows 1 With no pressure in the system charge R 22 gas into the system through the charging...

Страница 26: ...isconnect the vacuum pump leaving the vac uum indicator in place 6 Hold the vacuum obtained in Step 3 in the system for 8 hours the slightest rise in pressure indicates a leak or the presence of moist...

Страница 27: ...d found to be tight prior to evacuation then the saturation temperature recordings should follow a curve similar to the typical saturation curve shown as Fig 12 The temperature of the water in the tes...

Страница 28: ...iller model See Table 3 Charge the correct amount of refrigerant and record the level in the evaporator sight glass The refrigerant charge should always be checked and trimmed when the system is shut...

Страница 29: ...the condenser or evaporator compressor while making any necessary repairs While the main disconnect switch and compressor motor starter are open meg the motor as follows 1 Using a megohm meter megger...

Страница 30: ...ERNATIONAL FORM 160 73 O2 605 30 LD00476 FIG 14 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES Minimum Insulation Resistance vs Temperature per IEEE Std 43 Open Motors Maintenance TEMPERATURE F...

Страница 31: ...ead pressure over a period of time accompanied by a steady rise in condensing temperature and noisy operation These symptoms may also be due to foul gas buildup Purging will remove the foul gas reveal...

Страница 32: ...the ends of all tubes with water Do not use carbon tetrachloride for this purpose since its fumes give the same ame discoloration that the refrigerant does 3 With nitrogen or dry air blow out the tub...

Страница 33: ...lines passages or dirty oil lters If the unit is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil lter element Examine the oil lter element for the presence of alu minum...

Страница 34: ...re not supplied and bearings are designed for long life under standard conditions Frames 284T thru 587UZ are furnished with double shielded or open ball or roller bearings It is necessary to re lubric...

Страница 35: ...user to provide for proper water treatment to provide for a longer and more economical life of the equipment The following recommendation should be followed in determining the condition of the water...

Страница 36: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by YORK International Corporation 2005 ALL RIGHTS RESERVED Form 160 73 O2...

Отзывы: