YORK INTERNATIONAL
14
FORM 160.54-O2(1102)
FORM 160.54-O2(1102)
15
YORK INTERNATIONAL
1. Test all system joints for refrigerant leaks with a
leak detector. If any leaks are found, they should
be repaired before allowing the system to stand for
a long period of time.
During long idle periods, the tightness of the sys-
tem should be checked periodically.
2. If freezing temperatures are encountered while the
system is idle, carefully drain the cooling water
from the cooling tower, condenser, condenser
pump, and the chilled water system-chilled water
pump and coils.
Open the drains on the evaporator and condenser
liquid heads to assure complete drainage. (If a
Variable Speed Drive, drain its water cooling sys-
tem. If Solid State Starter. drain water from starter
cooling loop.)
3. On the
SETUP
Screen, disable the clock. This
conserves the battery.
4. Open the main disconnect switches to the com-
pressor motor, condenser water pump and the
chilled water pump. Open the 115 volt circuit to
the Control Center.