JOHNSON CONTROLS
FORM 201.23-EG1 (1007)
123
Model No./Nameplate
System 1
System 2
System 2
System 3
Std. & Ultra Quiet Cond. Fans
High Head/Static Cond. Fans
Two-Speed Cond. Fans
Std. & Ultra Quiet Cond. Fans
High Head/Static Cond. Fans
Two-Speed Cond. Fans
Std. & Ultra Quiet Cond. Fans
High Head/Static Cond. Fans
Two-Speed Cond. Fans
YCIV E/V Input Volts
(9)
Input Freq
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp. Condenser
Fans
Comp. Condenser
Fans
Comp.
Condenser Fans
RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA)
RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA)
0267
460
60
142
5
2.8
142
5
2.8
105
4
2.8
380
60
179
5
3.5
179
5
9.3
179
4
3.5
179
4
9.3
133
4
3.5
133
4
9.3
1050
400
50
170
5
3.1
170
5
9.3
180
5
3.8
170
5
3.1
170
5
9.3
180
5
3.8
126
4
3.1
126
4
9.3
132
4
3.8
0287
460
60
137
5
2.8
137
5
2.8
137
5
2.8
380
60
173
5
3.5
173
5
9.3
173
5
3.5
173
5
9.3
173
4
3.5
173
4
9.3
1120
400
50
164
5
3.1
164
5
9.3
173
5
3.8
164
5
3.1
164
5
9.3
173
5
3.8
164
5
3.1
164
5
9.3
173
5
3.8
0327
460
60
152
5
2.8
152
5
2.8
141
6
2.8
380
60
193
5
3.5
193
5
9.3
193
5
3.5
193
5
9.3
178
6
3.5
178
6
9.3
1220
400
50
183
5
3.1
183
5
9.3
194
5
3.8
183
5
3.1
183
5
9.3
194
5
3.8
169
6
3.1
169
6
9.3
178
6
3.8
0357
460
60
181
6
2.8
181
6
2.8
139
6
2.8
380
60
229
6
3.5
229
6
9.3
229
6
3.5
229
6
9.3
176
6
3.5
176
6
9.3
1380
400
50
218
6
3.1
218
6
9.3
229
6
3.8
218
6
3.1
218
6
9.3
229
6
3.8
167
6
3.1
167
6
9.3
175
6
3.8
YCIV S/P
Control
KVA (7)
Unit Short Circuit
Withstand (KA)
Field Wiring & Protection
Field Wiring & Protection
Field Wiring Lugs
Std. & Ultra Quiet Cond. Fans
High Head/High Static Fans
High Head/High Static Fans
Two-Speed Cond. Fans
STD Terminal Block
OPT Circuit Breaker
Terminal Block
(STD)
Circuit Breaker
(OPT)
Minimum Ckt.
Ampacity (MCA)
(3)
Recommended
Fuse/Ckt.
Breaker Rating
(4)
Max. Inverse
Time Ckt. Brkr.
Rating (2)
Max Dual
Element Fuse
Size (2)
Minimum Ckt.
Ampacity (MCA)
(3)
Recommended
Fuse/Ckt.
Breaker Rating
(4)
Max. Inverse
Time Ckt. Brkr.
Rating (2)
Max Dual
Element Fuse
Size (2)
Minimum Ckt.
Ampacity (MCA)
(3)
Recommended
Fuse/Ckt.
Breaker Rating
(4)
Max. Inverse
Time Ckt. Brkr.
Rating (2)
Max Dual
Element Fuse
Size (2)
Lugs/ Phase
(1)
Lug Wire Range Lugs/ Phase
(1)
Lug Wire Range
0287
2.4
30KA
65KA
463
600
600
600
4
#2 - 600 KCM
4
#4/0 - 500 KCM
2.4
30KA
65KA
581
700
700
700
632
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
1070
2.4
30KA
65KA
552
600
700
700
639
700
800
800
590
700
700
700
4
#2 - 600 KCM
4
#2 - 600 KCM
0307
2.4
30KA
65KA
486
600
600
600
4
#2 - 600 KCM
4
#2 - 600 KCM
2.4
30KA
65KA
610
700
700
700
659
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
1180
2.4
30KA
65KA
580
700
700
700
673
800
800
800
621
700
700
700
4
#2 - 600 KCM
4
#2 - 600 KCM
0357
2.4
30KA
65KA
528
600
600
600
4
#2 - 600 KCM
4
#2 - 600 KCM
2.4
30KA
65KA
667
800
800
800
728
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
1340
2.4
30KA
65KA
631
700
800
800
730
800
800
800
676
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
0397
2.4
30KA
65KA
598
700
700
700
4
#2 - 600 KCM
4
#2 - 600 KCM
2.4
30KA
65KA
755
800
800
800
818
1000
1000
1000
4
#2 - 600 KCM
4
#2 - 600 KCM
1500
2.4
30KA
65KA
713
800
800
800
824
1000
1000
1000
760
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
Содержание Latitude YCIV0157E
Страница 115: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 115 INTENTIONALLY LEFT BLANK...
Страница 127: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 127 INTENTIONALLY LEFT BLANK...
Страница 128: ...JOHNSON CONTROLS 128 Typical Control Wiring Two Compressor...
Страница 130: ...JOHNSON CONTROLS 130 Typical Control Wiring Three Compressor...
Страница 138: ...JOHNSON CONTROLS 138...
Страница 139: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 139...
Страница 140: ...Form 201 23 EG1 1007 Supersedes 201 23 EG1 607 File in ET2...