JOHNSON CONTROLS
FORM 201.23-EG1 (1007)
121
Model No./Nameplate
System 1
System 2
System 2
System 3
Std. & Ultra Quiet Cond. Fans
High Head/Static Cond. Fans
Two-Speed Cond. Fans
Std. & Ultra Quiet Cond. Fans
High Head/Static Cond. Fans
Two-Speed Cond. Fans
Std. & Ultra Quiet Cond. Fans
High Head/Static Cond. Fans
Two-Speed Cond. Fans
YCIV S/P Input Volts
(9)
Input Freq
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
Comp.
Condenser Fans
RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA)
RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA) RLA (5)
Qty.
FLA (EA)
0287
460
60
146
5
2.8
164
4
2.8
108
4
2.8
380
60
184
5
3.5
184
5
9.3
207
4
3.5
207
4
9.3
136
4
3.5
136
4
9.3
1070
400
50
175
5
3.1
175
5
9.3
186
5
3.8
196
4
3.1
196
4
9.3
202
4
3.8
129
4
3.1
129
4
9.3
135
4
3.8
0307
460
60
147
5
2.8
147
5
2.8
165
4
2.8
380
60
186
5
3.5
186
5
9.3
186
5
3.5
186
5
9.3
208
4
3.5
208
4
9.3
1180
400
50
177
5
3.1
177
5
9.3
188
5
3.8
177
5
3.1
177
5
9.3
188
5
3.8
198
4
3.1
198
4
9.3
203
4
3.8
0357
460
60
160
5
2.8
160
5
2.8
193
6
2.8
380
60
202
5
3.5
202
5
9.3
202
5
3.5
202
5
9.3
244
6
3.5
244
6
9.3
1340
400
50
192
5
3.1
192
5
9.3
204
5
3.8
192
5
3.1
192
5
9.3
204
5
3.8
232
6
3.1
232
6
9.3
245
6
3.8
0397
460
60
191
6
2.8
191
6
2.8
191
6
2.8
380
60
241
6
3.5
241
6
9.3
241
6
3.5
241
6
9.3
241
6
3.5
241
6
9.3
1500
400
50
229
6
3.1
229
6
9.3
243
6
3.8
229
6
3.1
229
6
9.3
243
6
3.8
229
6
3.1
229
6
9.3
243
6
3.8
YCIV S/P
Control
KVA (7)
Unit Short Circuit
Withstand (KA)
Field Wiring & Protection
Field Wiring & Protection
Field Wiring Lugs
Std. & Ultra Quiet Cond. Fans
High Head/High Static Fans
High Head/High Static Fans
Two-Speed Cond. Fans
STD Terminal Block
OPT Circuit Breaker
Terminal Block
(STD)
Circuit Breaker
(OPT)
Minimum Ckt.
Ampacity (MCA)
(3)
Recommended
Fuse/Ckt.
Breaker Rating
(4)
Max. Inverse
Time Ckt. Brkr.
Rating (2)
Max Dual
Element Fuse
Size (2)
Minimum Ckt.
Ampacity (MCA)
(3)
Recommended
Fuse/Ckt.
Breaker Rating
(4)
Max. Inverse
Time Ckt. Brkr.
Rating (2)
Max Dual
Element Fuse
Size (2)
Minimum Ckt.
Ampacity (MCA)
(3)
Recommended
Fuse/Ckt.
Breaker Rating
(4)
Max. Inverse
Time Ckt. Brkr.
Rating (2)
Max Dual
Element Fuse
Size (2)
Lugs/ Phase (1) Lug Wire Range Lugs/ Phase (1) Lug Wire Range
0287
2.4
30KA
65KA
494
600
600
600
4
#2 - 600 KCM
4
#4/0 - 500 KCM
2.4
30KA
65KA
624
700
800
800
676
800
800
800
4
#2 - 600 KCM
4
#4/0 - 500 KCM
1070
2.4
30KA
65KA
590
700
700
700
671
800
800
800
623
700
800
800
4
#2 - 600 KCM
4
#4/0 - 500 KCM
0307
2.4
30KA
65KA
540
600
700
700
4
#2 - 600 KCM
4
#4/0 - 500 KCM
2.4
30KA
65KA
682
800
800
800
731
800
800
800
4
#2 - 600 KCM
4
#4/0 - 500 KCM
1180
2.4
30KA
65KA
644
700
800
800
731
800
800
800
683
800
800
800
4
#2 - 600 KCM
4
#4/0 - 500 KCM
0357
2.4
30KA
65KA
607
700
800
800
4
#2 - 600 KCM
4
#4/0 - 500 KCM
2.4
30KA
65KA
766
1000
1000
1000
827
1000
1000
1000
4
#2 - 600 KCM
4
#4/0 - 500 KCM
1340
2.4
30KA
65KA
724
800
800
800
824
1000
1000
1000
776
1000
1000
1000
4
#2 - 600 KCM
4
#4/0 - 500 KCM
0397
2.4
30KA
65KA
671
800
800
800
4
#2 - 600 KCM
4
#4/0 - 500 KCM
2.4
30KA
65KA
847
1000
1000
1000
911
1000
1000
1000
4
#2 - 600 KCM
4
#4/0 - 500 KCM
1500
2.4
30KA
65KA
801
1000
1000
1000
913
1000
1000
1000
857
1000
1000
1000
4
#2 - 600 KCM
4
#4/0 - 500 KCM
Содержание Latitude YCIV0157E
Страница 115: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 115 INTENTIONALLY LEFT BLANK...
Страница 127: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 127 INTENTIONALLY LEFT BLANK...
Страница 128: ...JOHNSON CONTROLS 128 Typical Control Wiring Two Compressor...
Страница 130: ...JOHNSON CONTROLS 130 Typical Control Wiring Three Compressor...
Страница 138: ...JOHNSON CONTROLS 138...
Страница 139: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 139...
Страница 140: ...Form 201 23 EG1 1007 Supersedes 201 23 EG1 607 File in ET2...