FORM 100.50-NOM7 (808)
41
JOHNSON CONTROLS
4
*** UNIT STATUS ***
Ventilation System
Type = Min Dampr Pos
Status = Unocc/OFF
*** UNIT STATUS ***
Filter Status
Status = NORMAL
RA Bypass = NORMAL
*** UNIT STATUS ***
Occ Input
Status = Occ / ON
*** UNIT STATUS ***
Thermostat Input
Status = Y2
*** UNIT STATUS ***
G Input
Status = ON
The status displayed in Line 4 indicates one of the fol-
lowing:
N/A - Unit is not equipped with an economizer or econ-
omizer is not enabled.
Active - Economizer operation enabled and conditions
are suitable.
Inactive - Economizer operation enabled and conditions
are not suitable.
Line 2 Ventilation System
Line 3 Type = (Show Current Configuration)
Line 4 Status = Unocc/OFF (Occ/ON, N/A, Fault)
Line 3 displays one of the following configurations:
None (Line 4 Status = N/A)
Min Dampr Pos (Minimum damper position)
Min Airflow
25/75 Airflow
Full Airflow
Line 2 Filter Status
Line 3 Status = NORMAL (REPLACE, N/A)
Line 4 RA Bypass = Normal (Replace)
Line 2 Thermostat Input
Line 3 Status = Y2 (Y1,W1,W2, None)
Line 4 (Blank)
Line 2 Occ Input
Line 3 Status = Occ/ON (UnOcc/OFF)
Line 4 (Blank)
Line 2 G Input
Line 3 Status = ON (OFF)
Line 4 (Blank)
Содержание J Series
Страница 85: ...FORM 100 50 NOM7 808 85 JOHNSON CONTROLS 6 ELECTRICAL NOTES AND LEGEND LD13862 ...
Страница 86: ...JOHNSON CONTROLS 86 FORM 100 50 NOM7 808 Service LD13863 CONNECTION DIAGRAM 25 40 TON CV VAV IGV ...
Страница 87: ...FORM 100 50 NOM7 808 87 JOHNSON CONTROLS 6 LD13864 ...
Страница 88: ...JOHNSON CONTROLS 88 FORM 100 50 NOM7 808 Service OPTI CONVERSION TO 25 40 TON LD13854 ...
Страница 89: ...FORM 100 50 NOM7 808 89 JOHNSON CONTROLS 6 LD13865 ELEMENTARY DIAGRAM ALL UNITS ...
Страница 90: ...JOHNSON CONTROLS 90 FORM 100 50 NOM7 808 Service LD13860 ELEMENTARY DIAGRAM GAS HEAT 25 40 TON 230V ...
Страница 91: ...FORM 100 50 NOM7 808 91 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM GAS HEAT 25 40 TON 575V LD13861 ...