Installation
VAV Heat Relay Output
This is a field wired
OUTPUT
that is used to command
the VAV boxes to full open during heating mode and
smoke purge operation. This 24VAC signal should have
a maximum current draw not to exceed 20VA. If the
VA requirement of the VAV boxes approaches 20VA,
isolation relays should be field supplied and installed
to avoid overloading the unit power supply.
Note that this signal is used to drive the VAV boxes open
in heating and purge operations.
The VAV Heat Relay Output cannot
exceed a current draw of 20VA. If the
power requirement of the VAV boxes
exceed this amount, isolation relays
must be field supplied and installed
to prevent overloading the unit con
-
troller power supply.
This state is maintained until the input is deactivated
(contacts open).
Contacts Closed = Smoke Purge Operation
Contacts Open = Normal Operation.
Note that 24 volts (R), terminal 16, must be used as the
24 volt AC source for switching the contact to the unit
controller Shutdown input. Use of any power source
external to the controller will result in damage to the
unit controller.
No external power source may be used
when field wiring any of the above dry
contact inputs. The 24 volt AC source
on terminal 16 (R) of the Terminal
Block CTB1 must be used as the power
source when field wiring these inputs,
as shown in Fig. 1. Failure to do so
will result in improper unit operation
and damage to the unit controller.
Содержание J Series
Страница 85: ...FORM 100 50 NOM7 808 85 JOHNSON CONTROLS 6 ELECTRICAL NOTES AND LEGEND LD13862 ...
Страница 86: ...JOHNSON CONTROLS 86 FORM 100 50 NOM7 808 Service LD13863 CONNECTION DIAGRAM 25 40 TON CV VAV IGV ...
Страница 87: ...FORM 100 50 NOM7 808 87 JOHNSON CONTROLS 6 LD13864 ...
Страница 88: ...JOHNSON CONTROLS 88 FORM 100 50 NOM7 808 Service OPTI CONVERSION TO 25 40 TON LD13854 ...
Страница 89: ...FORM 100 50 NOM7 808 89 JOHNSON CONTROLS 6 LD13865 ELEMENTARY DIAGRAM ALL UNITS ...
Страница 90: ...JOHNSON CONTROLS 90 FORM 100 50 NOM7 808 Service LD13860 ELEMENTARY DIAGRAM GAS HEAT 25 40 TON 230V ...
Страница 91: ...FORM 100 50 NOM7 808 91 JOHNSON CONTROLS 6 ELEMENTARY DIAGRAM GAS HEAT 25 40 TON 575V LD13861 ...