292424-XIM-A-0307
8
Unitary Products Group
FIGURE 3 - UNIT DIMENSIONS AND CLEARANCES
F R O N T
1 6
( 4 0 6 )
3 9 - 7 / 8
( 1 0 1 3 )
B A C K
( C O I L E N D )
A P P R O X I M A T E
C E N T E R O F G R A V I T Y
3 2
( 8 1 3 )
7 6 - 7 / 8
( 1 9 5 3 )
A I R
O U T
A I R
O U T
A I R
I N
O
O
O
5 - 3 / 4
( 1 4 6 )
4 4 - 9 / 3 2
( 1 1 2 5 )
F A N M O T O R
A C C E S S
C O M P R E S S O R A N D
F A N M O T O R A C C E S S
E X T E R N A L P R E S S U R E
G A U G E F I T T I N G S
C O N T R O L B O X
A C C E S S
9 - 1 / 3 2
( 2 2 9 )
7 6 - 7 / 8
( 1 9 5 3 )
7 - 1 / 3 2
( 1 7 8 )
3 9 - 7 / 8
( 1 0 1 3 )
1 3 - 1 / 4
( 3 3 6 )
3 0 - 3 / 4
( 7 8 1 )
2 4 - 1 / 2
( 6 2 2 )
1 2 - 1 / 8
( 3 0 8 )
C
D
F
E
F
E
F
A
B
All dimensions are in inches and
millimeters. They are subject to
change without notice. Certified
dimensions will be provided upon
request.
TABLE 5: UNIT CLEARANCES
LOCATION
CLEARANCE
Overhead (Top)
1
1.
Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge.
120”/3048mm
Front (Piping and Access Panels)
30”/762mm
Left Side
24”/610mm
Right Side
24”/610mm
Rear
24”/610mm
Bottom
2
2.
Adequate snow clearance must be provided in winter
operation is expected.
0”/0mm
TABLE 6: UTILITIES ENTRY
CONNECTION
ENTRY
CONNECTION SIZE (in./mm.)
12-1/2 Ton
15 - 20 Ton
Suction Line
A
1-3/8 / 34.9 O.D.
2-1/8 / 53.9 O.D.
Liquid Line
B
5/8 / 15.8 O.D.
7/8 / 22.2 O.D.
Power Wiring
C
2-1/8 / 53.9 KO
2-1/8 / 53.9 KO
Control Wiring
D
7/8 / 22.2 KO
7/8 / 22.2 KO
Accessory Wiring
E
7/8 / 22.2 KO
7/8 / 22.2 KO
Accessory Wiring
F
1-3/8 / 34.9 KO
1-3/8 / 34.9 KO