background image

292424-XIM-A-0307

4

Unitary Products Group

LOCATION

Use the following guidelines to select a suitable location for 
these units.

1.

The condensing unit is designed for outdoor installation 
only. The condenser fans are the propeller type and are 
not suitable for use with ductwork.

2.

The condensing unit and the evaporator blower should 
be installed as close together as possible and with a 

 

minimum number of bends in the refrigerant piping. 
Refer to document 247077 “Application Data-General 
Piping Recommendations for Split Systems Air Condi-
tioners and Heat Pumps”.

3.

The condensing unit should not be installed where nor-
mal operating sounds may be objectionable. On either 
rooftop or ground level installations, rubber padding can 
be applied between the base rails and their supports to 
lessen any transmission of vibration.

ROOF-TOP LOCATIONS

Be careful not to damage the roof. Consult the building con-
tractor or architect if the roof is bonded. Choose a location 
with adequate structural strength to support the unit.

The condensing unit must be mounted on solid level sup-
ports. The supports can be channel iron beams or wooden 
beams treated to reduce deterioration.

A minimum of two (2) beams are required to support each 
unit. The beams should: (1) Be positioned perpendicular to 
the roof joists. (2) Extend beyond the dimensions of the unit 
to distribute the load on the roof. (3) Be capable of ade-
quately supporting the entire unit weight. Refer to Figure 1
and Table 7 for load distribution and weights.

These beams can usually be set directly on the roof. Flashing 
is not required.

NOTE:

On bonded roofs, check for special installation 
requirements.

GROUND LEVEL LOCATIONS

The units must be installed on a one-piece level concrete 
slab with a minimum thickness of 4 inches (102mm). The 
length and width should be at least 6 inches (153mm) greater 
than the units overall base dimensions. Refer to Figure 4.

Footers under the slab that extend below the frost line are 
recommended. Any strain on the refrigerant lines may cause 
a refrigerant leak. The slab should not be tied to the building 
foundation because noise and vibration will telegraph into 
your structure.

A unit can also be supported by concrete piers. These piers 
should (1) extend below the frost line, (2) be located under 
the unit's four corners, and (3) be sized to carry the entire unit 
weight. Refer to Figure 1 and Table 3 for the center of gravity 
and unit weight.

TABLE 1: UNIT APPLICATION DATA

MODEL

150, 180 & 240 Mbh

Voltage Variation

1

Min. / Max.

1.

Utilization Range “A” in ARI Standard 110.

380/415-3-50

342 /456 V

Ambient Air

2

 on

Condenser Coil

Min. / Max.

2.

The minimum allowed ambient temperature for 
mechanical cooling without the head pressure control 
accessory installed must be raised if the indoor air flow 
is less than the minimum value given in the capacity 
tables.

Standard

45°F/115°F

(-7°C/46°C)

Precautions should be taken to protect the unit 
from tampering and unauthorized persons from 
injury. Screws on access panels will prevent 
casual tampering. Additional safety precautions 
such as fences around the unit or locking devices 
on the panels may be advisable. Check local 
authorities for safety regulations.

TABLE 2: DIMENSIONS FOR CENTER OF 

GRAVITY

UNIT

DIMENSION mm.

A

B

C

D

150 Mbh

321

1086

293

807

180 Mbh

813

1953

407

1013

240 Mbh

813

1953

407

1013

FIGURE 1 - CENTER OF GRAVITY

A

B

C

D

B A C K

( C O I L   E N D )

A P P R O X I M A T E

C E N T E R   O F

G R A V I T Y

F R O N T

Содержание H5CE150A50

Страница 1: ...N and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment dam age may result if installation procedure is not handled properly INSTALLATION MANUAL CAUTION READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT SAVE THIS MANUAL SPLIT SYSTEM CONDENSING UN...

Страница 2: ...CONTINUOUS BLOWER 13 INTERMITTENT BLOWER 13 COOLING SEQUENCE OF OPERATION 13 FLASH CODES 13 CONDENSER FAN OPERATION 15 SAFETY FEATURES 15 SECURE OWNER S APPROVAL 15 MAINTENANCE 15 CLEANING CONDENSER SURFACE 15 LUBRICATION 15 COMPRESSOR REPLACEMENT 15 LIST OF FIGURES Fig Pg 1 CENTER OF GRAVITY 4 2 TYPICAL RIGGING 5 3 TYPICAL FIELD WIRING DIAGRAM 7 4 UNIT DIMENSIONS AND CLEARANCES 8 5 UNIT 4 POINT L...

Страница 3: ... Split Systems Air Conditioners and Heat Pumps RENEWAL PARTS Contact your local York parts distribution center for autho rized replacement parts for this equipment INSPECTION As soon as a unit is received it should be inspected for possi ble damage during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill A separate request for inspection by the car...

Страница 4: ...pecial installation requirements GROUND LEVEL LOCATIONS The units must be installed on a one piece level concrete slab with a minimum thickness of 4 inches 102mm The length and width should be at least 6 inches 153mm greater than the units overall base dimensions Refer to Figure 4 Footers under the slab that extend below the frost line are recommended Any strain on the refrigerant lines may cause ...

Страница 5: ...inst the data on the unit nameplate Check the size of the power wire the dis connect switch and the fuses against the data on Table 3 NOTE Copper conductors must be installed between the disconnect switch and the unit Refer to Figure 4 for the location of the power wire access opening through the front of the unit This opening will require a field supplied conduit fitting The field supplied discon...

Страница 6: ...onsists of two Copeland scroll compressors manifolded into a single refrigerant circuit Condenser Unit Weight lbs Kg Charge Refrigerant 22 Lbs Oz Kg 24 Fan Propeller Fan Motor2 2 The ball bearing 48 frame single phase condenser fan motor have internal protection are directly connected to the condenser fans Motor rotation is counterclockwise when viewing the lead end which is opposite the shaft end...

Страница 7: ... X X G Sol TB3 TABLE 4 ELECTRICAL DATA Model Unit Power Supply Compressor Condenser Fan Motor Unit Qty RLA1 LRA1 Qty Hp kW FLA Min Circuit Ampacity Amps Max Fuse2 Breaker Size3 Amps H3CE150A50 380 415 3 50 2 13 9 94 2 1 75 2 2 2 0 35 7 45 H4CE180A50 380 415 3 50 2 19 2 110 118 2 1 75 4 0 3 6 51 2 70 H3CE240A50 380 415 3 50 2 18 3 24 3 127 158 2 1 75 4 0 3 6 55 0 80 1 RLA and LRA values are for one...

Страница 8: ...ches and millimeters They are subject to change without notice Certified dimensions will be provided upon request TABLE 5 UNIT CLEARANCES LOCATION CLEARANCE Overhead Top 1 1 Units must be installed outdoors Overhanging struc tures or shrubs should not obstruct condenser air dis charge 120 3048mm Front Piping and Access Panels 30 762mm Left Side 24 610mm Right Side 24 610mm Rear 24 610mm Bottom2 2 ...

Страница 9: ...round refrigerant lines where they penetrate a wall to reduce vibrations and to retain some flexibility Support all refrigerant lines at minimum intervals with suitable hangers brackets or clamps Braze all copper to copper joints with Silfos 5 or equivalent brazing material Do not use soft solder Insulate all suction lines with a minimum of 1 2 12 7mm ARMAFLEX or equal Liquid lines exposed to dire...

Страница 10: ... 413 1 44 10 1 42 11 40 11 9 38 13 36 14 3 34 15 6 32 17 2 465 4 48 10 3 46 11 1 44 12 1 42 13 2 40 14 5 37 15 9 35 17 4 520 7 52 10 5 50 11 4 48 12 3 46 13 4 43 14 7 41 16 1 39 17 7 580 10 57 10 8 54 11 6 52 12 6 49 13 7 47 15 45 16 4 42 18 180 365 2 60 14 3 57 15 6 54 17 0 52 18 5 49 20 2 46 22 0 42 24 1 413 1 66 14 6 63 15 9 60 17 3 57 18 8 53 20 6 50 22 4 46 24 4 465 4 72 14 9 69 16 1 65 17 6 ...

Страница 11: ... touch to prove crankcase heater operation PRE START CHECK Before starting the unit complete the following check list 1 Have sufficient clearances been provided 2 Has all foreign matter been removed from the interior of the unit tools construction or shipping materials etc 3 Have the condenser fans been rotated manually to check for free rotation 4 Are all wiring connections tight 5 Does the avail...

Страница 12: ...ation of a compressor too soon after its previous run Additionally a minimum run time is imposed anytime a compressor is energized to allow proper oil return to the com pressor The ASCD is initiated on unit start up and on any compressor reset or lockout The Simplicity control board monitors the following inputs for each cooling system A high pressure switch is factory installed to protect against...

Страница 13: ... blower motor When the thermostat calls for the second stage of cooling the low voltage control circuit from R to Y2 is completed The control board will energize compressor two If there is an initial call for both stages of cooling the Simplic ity control board will delay energizing compressor two by 30 seconds in order to avoid an excessive power rush Once the thermostat has been satisfied the Si...

Страница 14: ...Compressor Lockout Off Off On Off On 6 Flashes Not Applicable Off Off On On Off 7 Flashes FS1 Compressor Lockout Off Off On On On 8 Flashes Not Applicable Off On Off Off Off 10 Flashes Compressors Locked Out on Low Outdoor Air Temperature1 Flashing On Off On Off 12 Flashes Unit Locked Out due to Fan Overload Switch Failure Off On On Off Off 13 Flashes Compressor Held Off due to Low Voltage1 Flashi...

Страница 15: ...wo will restart SAFETY FEATURES 1 The compressor is protected against over current and excessive temperature as described in the Sequence of Operation 2 The compressor is equipped with a crankcase heater to discourage refrigerant migration into the compressor sump during the OFF cycle 3 The condenser fan motors have auto reset internal pro tection 4 The secondary of every transformer is grounded 5...

Страница 16: ... change without notice Printed in U S A 292424 XIM A 0307 Copyright by Unitary Products Group 2007 All rights reserved Supersedes 66303 035 17263 002 A 0701 Unitary 5005 Norman Products York OK Group Drive 73069 ...

Отзывы: