background image

279747-YTG-A-0407

4

Unitary Products Group

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM).
2. Motor voltage at 115 V.

BLOWER PERFORMANCE CFM - (WITHOUT FILTER)

MODELS

Speed

Airflow Data

Ext. Static Pressure (in. H2O)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

(G,L)Y8S040A12DH11

High

1620

1590

1480

1400

1310

1240

1140

1040

910

760

Medium High

1430

1390

1340

1280

1220

1140

1050

960

820

710

Medium Low

1210

1210

1190

1200

1100

1020

940

850

730

620

Low

980

980

970

950

920

870

810

720

620

520

(G,L)Y8S060A12DH11

High

1500

1470

1390

1320

1240

1170

1070

960

830

700

Medium High

1380

1340

1280

1210

1150

1060

970

870

760

610

Medium Low

1220

1200

1160

1110

1050

990

910

820

700

600

Low

960

950

940

920

890

840

770

710

630

530

(G,L)Y8S080A12DH11

High

1550

1480

1410

1330

1250

1150

1050

940

810

700

Medium High

1400

1360

1290

1220

1150

1060

970

860

730

590

Medium Low

1230

1210

1170

1120

1060

990

910

810

680

560

Low

980

970

960

930

890

830

760

680

550

450

(G,L)Y8S080B16DH11

High

2070

2000

1930

1850

1770

1670

1580

1470

1360

1250

Medium

1650

1630

1610

1560

1490

1420

1360

1270

1170

1040

Low

1410

1400

1370

1340

1320

1270

1210

1140

1050

950

(G,L)Y8S080C16DH11

High

1895

1812

1736

1624

1544

1437

1311

1153

1032

836

Medium

1726

1645

1581

1491

1412

1311

1192

1049

908

750

Low

1561

1493

1430

1373

1304

1199

1089

967

816

699

(G,L)Y8S100B12DH11

High

1710

1650

1580

1510

1420

1330

1260

1160

1090

930

Medium High

1480

1440

1380

1330

1270

1180

1090

980

790

630

Medium Low

1240

1230

1200

1170

1110

1030

950

850

710

600

Low

980

980

980

970

930

890

800

720

630

530

(G,L)Y8S100C16DH11

High

2210

2160

2100

2030

1940

1850

1750

1640

1520

1400

Medium

1640

1640

1620

1590

1530

1500

1430

1360

1270

1160

Low

1410

1410

1370

1360

1300

1260

1210

1150

1090

1010

(G,L)Y8S100C20DH11

High

2400

2330

2240

2130

2030

1960

1820

1710

1570

1390

Medium High

2130

2070

2000

1940

1840

1760

1660

1540

1420

1230

Medium Low

1800

1760

1730

1650

1580

1510

1430

1300

1200

1030

Low

1480

1450

1390

1360

1300

1240

1180

1080

960

860

(G,L)Y8S115C16DH11

High

2210

2160

2100

2030

1940

1850

1750

1640

1520

1400

Medium

1640

1640

1620

1590

1530

1500

1430

1360

1270

1160

Low

1410

1410

1370

1360

1300

1260

1210

1150

1090

1010

(G,L)Y8S115C20DH11

High

2400

2310

2220

2120

2010

1910

1800

1660

1520

1350

Medium High

2090

2030

1970

1880

1790

1730

1640

1520

1370

1190

Medium Low

1720

1690

1650

1600

1550

1460

1370

1270

1150

980

Low

1440

1430

1400

1340

1280

1220

1140

1040

930

830

(G,L)Y8S130D20DH11

High

2530

2420

2340

2250

2110

2020

1920

1750

1590

1410

Medium High

2190

2150

2070

1970

1910

1790

1680

1550

1400

1250

Medium Low

1800

1760

1720

1680

1610

1490

1410

1300

1160

1040

Low

1450

1440

1410

1360

1310

1250

1170

1080

980

860

Содержание GY8S-DH

Страница 1: ...and may be common vented with another gas appliance as allowed by the National Fuel Gas Code ANSI Z223 1 latest edition WARRANTY 20 year limited warranty on the heat exchanger 10 year heat exchanger w...

Страница 2: ...net Dimension A B C D G L Y8S040A12DH11 1200 A 14 1 2 13 1 4 12 10 3 8 G L Y8S060A12DH11 1200 A 14 1 2 13 1 4 12 10 3 8 G L Y8S080A12DH11 1200 A 14 1 2 13 1 4 12 10 3 8 G L Y8S080B16DH11 1600 B 17 1 2...

Страница 3: ...1 2 12 0 80 0 40 70 G L Y8S100C16DH11 100 80 1600 21 12 0 80 0 25 55 G L Y8S100C20DH11 100 80 2000 21 14 0 80 0 25 55 G L Y8S115C16DH11 115 92 1600 21 12 0 80 0 35 65 G L Y8S115C20DH11 115 92 2000 21...

Страница 4: ...1491 1412 1311 1192 1049 908 750 Low 1561 1493 1430 1373 1304 1199 1089 967 816 699 G L Y8S100B12DH11 High 1710 1650 1580 1510 1420 1330 1260 1160 1090 930 Medium High 1480 1440 1380 1330 1270 1180 10...

Страница 5: ...em Static Pressure ESP without the filter 4 Select a filter pressure drop from the table based upon the number of return air openings or return air opening size and add to the ESP from Step 3 to deter...

Страница 6: ...ion of compatible thermosets are available to provide optimum performance and features for any installation 1H 1C manual change over electronic non programmable thermostat 1H 1C auto manual changeover...

Страница 7: ...eat W First Stage Heat W Single Stage Heat HM1 Humidistat Thermostat Installer Setup Number 1 System Type must be set to 0 Selection of GAS ELEC switch on thermostat not necessary Thermostat Installer...

Страница 8: ...change without notice Printed in U S A 279747 YTG A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 246794 YTG C 0706 Unitary 5005 Norman Products York OK Group Drive 73...

Отзывы: